81
Supplementary information
1) Energy-saving warm airflow control
Start timing: Starts when thermostat is switched from ON to OFF after HEAT mode and the hot adjust process
have finished.
End timing: Ends when any of the following conditions is met:
(1) The unit is switched to any mode other than HEAT.
(2) The unit enters DEFROST operation.
(3) Intake temperature ! Set temperature
(4) More than 5 minutes after the start of energy-saving warm airflow fan control
(5) The unit is switched to hot adjust.
•Energy-saving warm airflow control keeps the vane in the downward position and maintains the fan speed
when thermostat is turned OFF.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
Model No.
Temperature
button
SET button
Procedure
1. Press the SET button using a pointed implement.
"MODEL SELECT" flashes and the currently set
model No. appears (steadily-lit).
2. Press the temperature
buttons to select the
model No. to set.
3. Press the SET button using a pointed implement.
"MODEL SELECT" and the set model No. appear
(steadily-lit) for 3 seconds, then disappear.
•When setting a model No., make sure it is the correct
model No. for the unit's functions. If an incorrect model
No. is set, the unit's operation will not correspond with
the remote controller's display.
Setting model No.
•By setting the wireless remote controller model No., you can change the functions that the remote controller
provides. Change the model No. as needed.
PLA–RP·AA
001
PCA–RP·GA
001
PKA–RP·GAL
001
PKA–RP·FAL
003
Heat pump
Type
Model No.
Model
OCT04A-3.qxp 04.9.29 9:16 AM Page 81
Содержание Mr.SLIM PUHZ-RP1.6VHA
Страница 12: ...12 PEAD RP2 5GA PEAD RP3GA PEAD RP4GA ...