119
13-1-2. Indoor controller board
PLA-RP • AA
PKA-RP • GAL
PKA-RP • FAL
PCA-RP • GA
PEAD-RP • EA
PEAD-RP • GA
CN6V
Vane motor output
(MV)
CN32
Connector
(Remote switch)
CN90
Connect to the wireless
remote controller board
(CNB)
CN2D
Connect to the indoor
power board (CN2S)
(12~16V DC)
CN22
Connect to the terminal block(TB5)
(Remote controller connecting wire)
(10~16V DC)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN20
Room temperature
thermistor (TH1)
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN31
Drain sensor (DS)
CN29
Condenser/evaporator
temperature thermistor (TH5)
CN25
Humidifier output
(12~16V DC)
Jumper connector J11~J15
Unit setting
Jumper connector J21~J24
Capacity setting
SWE
Emergency operation
LED1
Power supply (I.B)
LED2
Power supply (R.B)
LED3
Transmission
(Indoor/outdoor)
CN03
Connect to the indoor
power board (CN02)
Between
1
to
3
220~240V AC
Between
3
to
5
0~24V DC
(Indoor/outdoor transmission)
CNC
Dew prevention heater (H2)
Between
1
to
3
220~240V AC
CNP
Drain-up machine output (DP)
Between
1
to
3
220~240V AC
FAN
Fan motor output (MF)
Between
1
to
5
220~240V AC
–
+
}
}
+
–
}
+
–
}
–
+
CN27
Drain pump
output (DP)
(12~16V DC)
–
+
}
OCT04A-4.qxp 04.9.29 9:17 AM Page 119