58
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Piping temperature. (TH3)
– 40~90
– 40~90
(When the coil thermistor is 0
:
or below, “–” and
temperature displays by turns.)
(Example) When -10
:
One second interval
– 10
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Discharge temperature. (TH4)
0~216
FAN output step.
0~16
The number of ON / OFF times.
0~9999
Compressor integrating operation times.
0~9999
0~216
(When the discharge thermistor is 100 or more, the
hundreds digit and tens, units digit are displayed by
turns.)
(Example) When 150
:
One second interval
1 50
:
Step
100 times
10 hours
0~16
0~9999
(When the number of times is 100 or more, the
hundreds digit and tens, units digit are displayed by
turns.)
(Example) When 42500 times
One second interval
4 25
0~9999
(When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 2450 hours
One second interval
2 45
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Compressor operating current.
0~40
LEV opening.
0~440
0~40
Output pulse is displayed by one fifth of actual value.
(Example) When the display shows 300
300
✕
5 = 1500 pulse
1500 pulse is the actual output pulse
A
Pulse
New error postponement code.
New outdoor unit error postponement
display.
No postponement code is “00”.
Code
display
Code
display
Operation mode on error occurring.
Operation mode on error stop.
SW2 setting is displayed at below code.
1
ON
2 3 4 5 6
(SW2)
1
ON
2 3 4 5 6
OC336--2.qxp 05.8.29 7:20 PM Page 58