11
5
DATA
5-1. REFILLING REFRIGERANT CHARGE (R407C : kg)
Piping length (one way)
10m
20m
30m
40m
50m
Factory
charged
1.6
2.4
2.4
2.5
2.5
2.9
2.9
2.9
2.9
3.4
3.4
4.0
4.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.1
3.1
3.7
3.7
4.3
4.6
1.8
2.6
2.6
3.1
3.1
3.3
3.3
3.3
3.3
4.0
4.0
4.6
4.9
—
3.0
3.0
3.7
3.7
3.9
3.9
3.9
3.9
4.7
4.7
5.3
5.6
—
—
—
—
—
4.5
4.5
4.5
4.5
5.4
5.4
6.0
6.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.3
3.3
4.0
4.0
4.6
4.9
Service Ref.
PUH-P140YGAA.UK
PU-P140YGAA.UK
PUH-P125YGAA.UK
PU-P125YGAA.UK
PUH-P100VGAA.UK
PU-P100VGAA.UK
PUH-P100YGAA.UK
PU-P100YGAA.UK
PUH-P71YGAA.UK
PU-P71YGAA.UK
PUH-P71VGAA.UK
PU-P71VGAA.UK
PUH-P60YGAA.UK
PU-P60YGAA.UK
PUH-P60VGAA.UK
PU-P60VGAA.UK
PUH-P50YGAA.UK
PU-P50YGAA.UK
PUH-P50VGAA.UK
PU-P50VGAA.UK
PUH-P35YGAA.UK
PU-P35YGAA.UK
PUH-P35VGAA.UK
PU-P35VGAA.UK
PUH-P25VGAA.UK
PRE- CHARGED REFRIGERANT IS SUPPLIED
FOR PIPING LENGTH AT SHIPMENT.
5-2. COMPRESSOR TECHNICAL DATA
Compressor model
Winding
Resistance
(
"
)
U-V
(R-C)
U-W
(S-C)
W-V
U-V
(R-C)
U-W
(S-C)
W-V
RE277VHSMT
RE277YFKM
Unit
NE36VMJMT
1.80
3.00
—
10.8
10.8
10.8
5.01
5.01
5.01
NE36YEKMT
0.89
2.03
—
Unit
Compressor model
Winding
Resistance
(
"
)
(at 20
°
C)
BE96YADMT
BE82YADMT
2.123
2.123
2.123
NE52VNJMT
0.64
1.67
—
3.59
3.59
3.59
1.963
1.963
1.963
NE56YDKMT
3.32
3.32
3.32
PUH-P35VGAA.UK
PU-P35VGAA.UK
PUH-P35YGAA.UK
PU-P35YGAA.UK
PUH-P50VGAA.UK
PU-P50VGAA.UK
PUH-P50YGAA.UK
PU-P50YGAA.UK
PUH-P25VGAA.UK
PUH-P60YGAA.UK
PU-P60YGAA.UK
PUH-P60VGAA.UK
PU-P60VGAA.UK
PUH-P71VGAA.UK
PU-P71VGAA.UK
PUH-P100VGAA.UK
PU-P100VGAA.UK
PUH-P71YGAA.UK
PU-P71YGAA.UK
PUH-P125YGAA.UK
PU-P125YGAA.UK
PUH-P100YGAA.UK
PU-P100YGAA.UK
U-V
(R-C)
U-W
(S-C)
W-V
Unit
Compressor model
Winding
Resistance
(
"
)
NE41VMJMT
NE41YEKMT
5.00
5.00
5.00
NE56VNJMT
0.62
1.59
—
RE189VHSMT
2.79
3.36
—
0.87
2.22
—
NE52YDKMT
PUH-P140YGAA.UK
PU-P140YGAA.UK