3

2. Installation location

Refer to the outdoor unit installation manual.

3. Installing the indoor unit

3.1. Check the indoor unit accessories (Fig. 3-1)

The indoor unit should be supplied with the following accessories.

Accessory name

Q’ty

1

Installation template

1

2

Washers (with insulation)

4

Washers (without insulation)

4

3

Pipe cover (for refrigerant piping joint)
Small diameter

1

Large diameter

1

4

Band (large)

6

Band (small)

2

5

Screw with washer (M5 

×

 25) for mounting grille

4

6

Drain socket

1

7

Insulation

1

3

2

5

4

7

6

Fig. 3-1

1

3.2. Ceiling openings and suspension bolt installation

locations (Fig. 3-2)

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

* Before using, check the dimensions of template and gauge, because they

change due to fluctuations of temperature and humidity.

* The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, en-
suring that the respective opposite sides on all sides of the clearance between
them becomes identical.

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• Install securely, ensuring that there is no clearance between the ceiling panel &

grille, and between the main unit & grille.

A

Outer side of main unit

B

Bolt pitch

C

Ceiling opening

D

Outer side of Grille

E

Grille

F

Ceiling

G

Multi function casement (option)

H

Entire periphery

*

Note that the space between ceiling panel of the unit and ceiling slab and etc must be 10 to
15 mm.

159

192

159

159

98

860–910

20–45

20

45

20

45

20–45

810

950

840

197

159

605

840

950

860

910

A

B

C

D

C

B

D

A

135

F

G

E

17

+5

  0

17

+5

  0

50

70

105

30

C

D

Min. 1000

Min. 500

F

H

E

Fig. 3-2

Models

C

D

RP1.6,2,2.5,3

241

258

RP4,5,6

281

298

(mm)

Содержание Mr.Slim PLA-AA

Страница 1: ...Air Conditioners PLA RP AA English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ... around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dr...

Страница 3: ...fore using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in following diagram so center the main unit against the opening of ceiling en suring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension...

Страница 4: ...g plate Make sure that step A is performed within 17 22 mm Damage could result by failing to adhere to this range Fig 3 6 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when ap plying ceiling materials 3 6 Confirming the position of main unit and tighten ing the suspension bolts Fig 3...

Страница 5: ...eat insulation for refrigerant pipes 1 Wrap the enclosed large sized pipe cover around the gas pipe making sure that the end of the pipe cover touches the side of the unit 2 Wrap the enclosed small sized pipe cover around the liquid pipe making sure that the end of the pipe cover touches the side of the unit 3 Secure both ends of each pipe cover with the enclosed bands Attach the bands 20 mm from ...

Страница 6: ... DC24V DC14V DC14V C Support metal K Air bleeder L Raised M Odor trap 1 Correct piping 2 Wrong piping A Insulation 9 mm or more B Downward slope 1 100 or more Grouped piping D O D ø32 PVC TUBE E Make it as large as possible F Indoor unit G Make the piping size large for grouped pip ing H Downward slope 1 100 or more I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation J Up to 85 cm 1 Conn...

Страница 7: ...ler is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or hot winds Area in which the remote controller can be operated easily Area in which the remote controller is beyond the reach of children 2 Installation method Fig 7 5 1 Attach the remote controller holder to the desired location using two tapping screw...

Страница 8: ...e setting depending on the voltage used 1 Go to the function select mode Press the CHECK button F twice continuously Start this operation from the status of remote controller display turned off CHECK is lighted and 00 blinks Press the temp button C once to set 50 Direct the wireless remote controller toward the receiver of the indoor unit and press the h button A 2 Setting the unit number Press th...

Страница 9: ...onditioner if the insulation resistance is less than 1 0MΩ Insulation resistance 8 2 Test run The following 3 methods are available 8 2 1 Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and...

Страница 10: ...rheating safeguard operation Single beep 6 Lit for 1 sec 6 P8 Pipe temperature error Single beep 8 Lit for 1 sec 8 P9 TH5 sensor error Single beep 2 Lit for 1 sec 2 U0 UP Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 F1 FA Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 E0 E5 Signal error between remote controller and indoor units Sounds other than above Lights other than a...

Страница 11: ... to 5 cm B Cover of water supply inlet C About 1000 cc D Water E Drain plug 9 System controll Refer to the outdoor unit installation manual 10 1 Checking the contents Fig 10 1 This kit contains this manual and the following parts Accessory name Q ty Remark 1 Grille 1 950 950 mm 2 Screw with captive washer 4 M5 0 8 25 3 Gauge 1 Divided into four parts 4 Fastener 2 5 Screw 4 4 8 6 Wireless remote co...

Страница 12: ...at there are no gaps E Adjust the nut of the main unit using a wrench etc Fig 10 7 A D C B E Fig 10 8 A Clamp of the main unit B Tube C Connector of the main unit D Grille connector E Fastener 10 4 4 Wire connection Fig 10 8 Be sure to connect the unit to the connector white 10 pole Next attach the white glass tube that comes with the main unit so that the tube covers the connector Close the openi...

Страница 13: ...n the unit and the grille or between the grille and the surface of the ceiling If there is any gap between the unit and the grille or between the grille and the surface of the ceiling it may cause dew to collect Make sure that the wires have been securely connected C A B A Screw 4 8 5 B Corner panel C Safety wire D H G E F Fig 10 11 10 8 Installing the intake grille Fig 10 11 Note When reinstallin...

Страница 14: ...KKKKKKKKKKKKKKKKKKKKKKKK NT RK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NT SK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NU TK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NU UK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK...

Страница 15: ...1234 5678 jNM PLU G 0 1234 A B C D E F G H G NM NR 159 192 159 159 98 860 910 20 45 20 45 20 45 20 45 810 950 840 197 159 605 840 950 860 910 A B C D C B D A 135 F G E 17 5 0 17 5 0 50 70 105 30 C D F H E Fig 3 2 a omNKSI OI OKRI P OQN ORU omQIRIS OUN OVU E F HM04A433_PAC IM_ch p65 12 3 04 6 15 PM Page 15 Adobe PageMaker 6 5C PPC ...

Страница 16: ...K EcáÖK PJTF 01 23 01 23 0123456789 G 01 A B C D E F G A D C B A 17 5 0 C D B A 17 5 0 A B A C D E F C B G A B C D A B C D Fig 3 5 Fig 3 6 Fig 3 7 D E A C A B 90 90 100 100 130 350 70 100 G F H I J 155 167 L K M N O 158 120 120 Fig 3 3 PKPK EcáÖK PJPF 01234 5678 01213 W G NPR A B C D E F E F G H NQJøOKU I øNRM J øNTR K L PJøOKU M øNOR N øNMM O HM04A433_PAC IM_ch p65 12 3 04 6 16 PM Page 16 Adobe P...

Страница 17: ...G Fig 5 2 A B C D E F G H I J C D RKOK EcáÖK RJOF 1 2 3 OM 012 3 45670 RKPK L Ø SKPR NT NQ J NU Ø SKPR OO PQ J QO Ø VKRO OO PQ J QO Ø NOKT OS QV J SN Ø NOKT OV SU J UO Ø NRKUU OV SU J UO Ø NRKUU PS NMM J NOM Ø NVKMR PS NMM J NOM omNKSI O omOKRI P omQJS oQMT mrEeFJmNKSLO mrEeFJmOKRLP mrEeFJmQLRLS øNRKUU øNRKUU øNVKMR N N N N N N øVKRO øVKRO øVKRO N N N N N N omNKSI O omOKRI P omQJS oQNM mrewJomNKSL...

Страница 18: ... L H D E E I J C K Fig 6 1 Fig 6 2 E F TK TKNK EcáÖK TJNF NK OK 0123 RM NMM A B C D E F mie G L H I J K A E D J K B C I G F H N L S3 S2 S1 1 2 Fig 7 1 mi mie úLk RM OOMJOPMJOQM NS O NKR N NKR P OKR P OKR N OKR N OKR O MKSV O MKSV OOMJOPMJOQM OOMJOPMJOQM OOMJOPMJOQM OQ OQ NQ NQ NK P kc ks OK NM PK pP pO OQ pP pN 01234 NK OK L 01234 5 OQR fb RT PK N J J J O iJk P J pNJpO P J pOJpP P J P HM04A433_PAC...

Страница 19: ...OF mreI mrew MMN mr MPP mhe EOKRI PI QF mre MMP mh EOKRI PI QF mreI mrew MMP mr MPR 30 46 30 30 120 83 5 A B C F A H C D E G I I I H B J H B 1 B 2 Fig 7 3 A AB TB6 B 1 2 3 4 ON 1 2 3 4 ON C D B 1 C A 2 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 2 4 3 A Fig 7 5 Fig 7 6 Fig 7 2 Fig 7 4 YN pt pt L lkLlcc L L YO pt pt lkLlcc L 0 1234 L YP pt ...

Страница 20: ...E CLOCK ON OFF ßC CHECK CHECK MODE FILTER TEST RUN FUNCTION ßC 1Hr NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP TIMER SET F G E C D B A 4 3 2 1 STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C 1Hr C CHECK MODE FILTER CLOCK FUNCTION 4 1 STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C 1Hr C CHECK MODE FILTER CLOCK FUNCTION STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C ...

Страница 21: ...éÉÉÇz 6 x áêÑäçïz xiçìîÉêz 0 7 xlkLlccz L 8 UKOKOK cáÖK UJO 1 NO 2 TEST RUN A 3 MODE 4 MODE 5 FAN 6 VANE 7 lkLlcc L 2 7 c k aov rql ON OFF CENTRALLY CONTROLLED ERROR CODE CLOCK ON OFF ßC CHECK CHECK MODE FILTER TEST RUN FUNCTION ßC 1Hr NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP TIMER SET D E F H IJKL M G C B A ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RE...

Страница 22: ...ESSNO CENTRALLY CONTROLLED CLOCK ON OFF C 1Hr NOT AVAILABLE C CHECK MODE FILTER CHECK FUNCTION STAND BY DEFROST INDOOR UNIT ADDRESS NO ERROR CODE OAUNITADDRESSNO CENTRALLY CONTROLLED CLOCK ON OFF C 1Hr NOT AVAILABLE C CHECK MODE FILTER CHECK FUNCTION a D E F Fig 8 3 1 2 3 P1 N N N P2 O N O P4 Q N Q P5 R N R P6 L S N S P8 U N U P9 qeR O N O UO UP N MKQ H MKQ N F1 FA N MKQ H MKQ N E0 E5 E6 EF F F F ...

Страница 23: ...KU OR 3 N 4 O 5 Q Q U 6 N mimJS ij 7 N mimJS j NMK 1 4 5 6 7 2 0 ON OFF 2 3 Fig 10 1 Fig 10 2 A D C B A 17 5 0 Fig 10 3 B A C 1 1 D E 2 F G F B 1 NMKOK cáÖK NMJO 3 0123 USM USM VNM VNM NTJOO A B C 3 D NMKOKNK cáÖK NMJP 1 G 2 0 123 45 NMKOKOK cáÖK NMJQ 1 A B C D E F G Fig 10 4 iba M iba ibaN ibaO ibaP HM04A433_PAC IM_ch p65 12 3 04 6 26 PM Page 23 Adobe PageMaker 6 5C PPC ...

Страница 24: ... F 2 G H _ I Fig 10 6 NMKQKOK EcáÖK NMJSF _ NMKQKPK EcáÖK NMJTF 01 23456789 01 E A B C D E Fig 10 7 A D C B E Fig 10 8 A B C D E NMKQKQK EcáÖK NMJUF NM 012 0123456 NMKPK NN 01234 01 23 NF OF 012 3456789 O P Q P N Q O S NMK HM04A433_PAC IM_ch p65 12 3 04 6 27 PM Page 24 Adobe PageMaker 6 5C PPC ...

Страница 25: ...D Fig 10 10 NMKSK EcáÖK NMJNMF 012345678 9 01234567 kVM 0123 NMKTK 01 2 0123 C A B A Q U 5 B C D H G E F Fig 10 11 NMKUK EcáÖK NMJNNF 0123456789 Q Q U 0123 01234 NNKOK 0 12 34567 012345678 9 012345 E F A B C D 012345678 0 E mimJS ij HM04A433_PAC IM_ch p65 12 3 04 6 27 PM Page 25 Adobe PageMaker 6 5C PPC ...

Страница 26: ......

Страница 27: ......

Страница 28: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U156H02 ...

Отзывы: