6
6. Drainage piping work
6.1. Drainage piping work (Fig. 6-1)
• Use VP25 (O. D. ø32 PVC TUBE) for drain piping and provide 1/100 or more down-
ward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.
Max. 20m
1.5–2m
A
B
C
B
M
L
K
D
E
D
H
I
G
D
F
F
F
Max. 15cm
J
F
G
11
25
25
25
B
A
C
K
F
L
H
D
E
E
I
J
C
,
K
Fig. 6-1
Fig. 6-2
(mm)
7. Electrical work
7.1. Indoor unit (Fig. 7-1)
1. Remove the two electrical wiring service panels.
2. Wire the power cable and control cable separately through the respective wiring
entries given in the diagram.
• Do not allow slackening of the terminal screws
• Leave excess cable so that the electrical box can be suspended below the unit
during servicing. (Approx. 50 to 100 mm)
A
Entry for control cable
B
Entry for power
C
Clamp
D
Service panel for indoor controller switch setting
E
Service panel for electrical wiring
F
Electric heater power supply terminals (PLH models)
G
Indoor / Outdoor unit connecting terminals
H
Remote controller connector
I
Secure with the clamp
J
Intake sensor
K
Holder
Fig. 7-1
Indoor unit model
Indoor unit power supply (Heater)
Indoor unit input capacity (Heater)
*1
Main switch (Breaker)
Indoor unit power supply (Heater)
Indoor unit power supply (Heater) earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
*2
Indoor unit (Heater) L-N
*3
Indoor unit-Outdoor unit S1-S2
*3
Indoor unit-Outdoor unit S2-S3
*3
Remote controller-Indoor unit
*3
PLA
PLH
–
~/N (single), 50Hz, 220-230-240V
–
16 A
–
2
×
Min. 1.5
–
1
×
Min. 1.5
3
×
2.5 (polar)
3
×
2.5 (polar)
1
×
Min. 2.5
1
×
Min. 2.5
2
×
0.69 (Non-polar)
2
×
0.69 (Non-polar)
–
AC 220-230-240V
AC 220-230-240V
AC 220-230-240V
DC24V
DC24V
DC14V
DC14V
C
Support metal
K
Air bleeder
L
Raised
M
Odor trap
1
Correct piping
2
Wrong piping
A
Insulation (9 mm or more)
B
Downward slope (1/100 or more)
Grouped piping
D
O. D. ø32 PVC TUBE
E
Make it as large as possible
F
Indoor unit
G
Make the piping size large for grouped pip-
ing.
H
Downward slope (1/100 or more)
I
O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)
J
Up to 85 cm
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 6-2)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A
Unit
B
Insulating material
C
Band (large)
D
Drain port (transparent)
E
Insertion margin
F
Matching
G
Drain pipe (O.D. ø32 PVC TUBE)
H
Insulating material (purchased locally)
I
Transparent PVC pipe
J
O.D. ø32 PVC TUBE (Slope 1/100 or more)
K
Band (small)
L
Drain socket
Circuit
rating
A
E
D
J
,
K
B
C
I
G
F
H
N
L
S3
S2
S1
1
2
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. A 10 m wire is attached in the remote controller accessory.
*3. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer and thicker than other cables.
Wir
ing
Wire No
.
×
siz
e
(mm
2
)