background image

6

6. Drainage piping work

6.1. Drainage piping work (Fig. 6-1)

• Use VP25 (O. D. ø32 PVC TUBE) for drain piping and provide 1/100 or more down-

ward slope.

• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.

Max. 20m

1.5–2m

A

B

C

B

M

L

K

D

E

D

H

I

G

D

F

F

F

Max. 15cm

J

F

G

11

25

25

25

B

A

C

K

F

L

H

D

E

E

I

J

C

,

K

Fig. 6-1

Fig. 6-2

(mm)

7. Electrical work

7.1. Indoor unit (Fig. 7-1)

1. Remove the two electrical wiring service panels.
2. Wire the power cable and control cable separately through the respective wiring

entries given in the diagram.

• Do not allow slackening of the terminal screws
• Leave excess cable so that the electrical box can be suspended below the unit

during servicing. (Approx. 50 to 100 mm)

A

Entry for control cable

B

Entry for power

C

Clamp

D

Service panel for indoor controller switch setting

E

Service panel for electrical wiring

F

Electric heater power supply terminals (PLH models)

G

Indoor / Outdoor unit connecting terminals

H

Remote controller connector

I

Secure with the clamp

J

Intake sensor

K

Holder

Fig. 7-1

Indoor unit model
Indoor unit power supply (Heater)
Indoor unit input capacity (Heater)

*1

Main switch (Breaker)

Indoor unit power supply (Heater)
Indoor unit power supply (Heater) earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit

*2

Indoor unit (Heater) L-N

*3

Indoor unit-Outdoor unit S1-S2

*3

Indoor unit-Outdoor unit S2-S3

*3

Remote controller-Indoor unit

*3

PLA

PLH

~/N (single), 50Hz, 220-230-240V

16 A

×

 Min. 1.5

×

 Min. 1.5

×

 2.5 (polar)

×

 2.5 (polar)

×

 Min. 2.5

×

 Min. 2.5

×

 0.69 (Non-polar)

×

 0.69 (Non-polar)

AC 220-230-240V

AC 220-230-240V

AC 220-230-240V

DC24V

DC24V

DC14V

DC14V

C

Support metal

K

Air bleeder

L

Raised

M

Odor trap

1

Correct piping

2

Wrong piping

A

Insulation (9 mm or more)

B

Downward slope (1/100 or more)

Grouped piping

D

O. D. ø32 PVC TUBE

E

Make it as large as possible

F

Indoor unit

G

Make the piping size large for grouped pip-
ing.

H

Downward slope (1/100 or more)

I

O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)

J

Up to 85 cm

1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 6-2)

(Affix the tube using PVC adhesive then secure it with a band.)

2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).

(Affix the pipe using PVC adhesive then secure it with a band.)

3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a

band.  (Both insulating material and band are supplied with the unit.)

A

Unit

B

Insulating material

C

Band (large)

D

Drain port (transparent)

E

Insertion margin

F

Matching

G

Drain pipe (O.D. ø32 PVC TUBE)

H

Insulating material (purchased locally)

I

Transparent PVC pipe

J

O.D. ø32 PVC TUBE (Slope 1/100 or more)

K

Band (small)

L

Drain socket

Circuit

rating

A

E

D

J

,

K

B

C

I

G

F

H

N

L

S3

S2

S1

1

2

*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. A 10 m wire is attached in the remote controller accessory.
*3. The figures are NOT always against the ground.

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer and thicker than other cables.

Wir

ing

Wire No

×

 siz

e

(mm

2

)

Содержание Mr.Slim PLA-AA

Страница 1: ...Air Conditioners PLA RP AA English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ... around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dr...

Страница 3: ...fore using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in following diagram so center the main unit against the opening of ceiling en suring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension...

Страница 4: ...g plate Make sure that step A is performed within 17 22 mm Damage could result by failing to adhere to this range Fig 3 6 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when ap plying ceiling materials 3 6 Confirming the position of main unit and tighten ing the suspension bolts Fig 3...

Страница 5: ...eat insulation for refrigerant pipes 1 Wrap the enclosed large sized pipe cover around the gas pipe making sure that the end of the pipe cover touches the side of the unit 2 Wrap the enclosed small sized pipe cover around the liquid pipe making sure that the end of the pipe cover touches the side of the unit 3 Secure both ends of each pipe cover with the enclosed bands Attach the bands 20 mm from ...

Страница 6: ... DC24V DC14V DC14V C Support metal K Air bleeder L Raised M Odor trap 1 Correct piping 2 Wrong piping A Insulation 9 mm or more B Downward slope 1 100 or more Grouped piping D O D ø32 PVC TUBE E Make it as large as possible F Indoor unit G Make the piping size large for grouped pip ing H Downward slope 1 100 or more I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation J Up to 85 cm 1 Conn...

Страница 7: ...ler is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or hot winds Area in which the remote controller can be operated easily Area in which the remote controller is beyond the reach of children 2 Installation method Fig 7 5 1 Attach the remote controller holder to the desired location using two tapping screw...

Страница 8: ...e setting depending on the voltage used 1 Go to the function select mode Press the CHECK button F twice continuously Start this operation from the status of remote controller display turned off CHECK is lighted and 00 blinks Press the temp button C once to set 50 Direct the wireless remote controller toward the receiver of the indoor unit and press the h button A 2 Setting the unit number Press th...

Страница 9: ...onditioner if the insulation resistance is less than 1 0MΩ Insulation resistance 8 2 Test run The following 3 methods are available 8 2 1 Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and...

Страница 10: ...rheating safeguard operation Single beep 6 Lit for 1 sec 6 P8 Pipe temperature error Single beep 8 Lit for 1 sec 8 P9 TH5 sensor error Single beep 2 Lit for 1 sec 2 U0 UP Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 F1 FA Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 E0 E5 Signal error between remote controller and indoor units Sounds other than above Lights other than a...

Страница 11: ... to 5 cm B Cover of water supply inlet C About 1000 cc D Water E Drain plug 9 System controll Refer to the outdoor unit installation manual 10 1 Checking the contents Fig 10 1 This kit contains this manual and the following parts Accessory name Q ty Remark 1 Grille 1 950 950 mm 2 Screw with captive washer 4 M5 0 8 25 3 Gauge 1 Divided into four parts 4 Fastener 2 5 Screw 4 4 8 6 Wireless remote co...

Страница 12: ...at there are no gaps E Adjust the nut of the main unit using a wrench etc Fig 10 7 A D C B E Fig 10 8 A Clamp of the main unit B Tube C Connector of the main unit D Grille connector E Fastener 10 4 4 Wire connection Fig 10 8 Be sure to connect the unit to the connector white 10 pole Next attach the white glass tube that comes with the main unit so that the tube covers the connector Close the openi...

Страница 13: ...n the unit and the grille or between the grille and the surface of the ceiling If there is any gap between the unit and the grille or between the grille and the surface of the ceiling it may cause dew to collect Make sure that the wires have been securely connected C A B A Screw 4 8 5 B Corner panel C Safety wire D H G E F Fig 10 11 10 8 Installing the intake grille Fig 10 11 Note When reinstallin...

Страница 14: ...KKKKKKKKKKKKKKKKKKKKKKKK NT RK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NT SK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NU TK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NU UK KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK...

Страница 15: ...1234 5678 jNM PLU G 0 1234 A B C D E F G H G NM NR 159 192 159 159 98 860 910 20 45 20 45 20 45 20 45 810 950 840 197 159 605 840 950 860 910 A B C D C B D A 135 F G E 17 5 0 17 5 0 50 70 105 30 C D F H E Fig 3 2 a omNKSI OI OKRI P OQN ORU omQIRIS OUN OVU E F HM04A433_PAC IM_ch p65 12 3 04 6 15 PM Page 15 Adobe PageMaker 6 5C PPC ...

Страница 16: ...K EcáÖK PJTF 01 23 01 23 0123456789 G 01 A B C D E F G A D C B A 17 5 0 C D B A 17 5 0 A B A C D E F C B G A B C D A B C D Fig 3 5 Fig 3 6 Fig 3 7 D E A C A B 90 90 100 100 130 350 70 100 G F H I J 155 167 L K M N O 158 120 120 Fig 3 3 PKPK EcáÖK PJPF 01234 5678 01213 W G NPR A B C D E F E F G H NQJøOKU I øNRM J øNTR K L PJøOKU M øNOR N øNMM O HM04A433_PAC IM_ch p65 12 3 04 6 16 PM Page 16 Adobe P...

Страница 17: ...G Fig 5 2 A B C D E F G H I J C D RKOK EcáÖK RJOF 1 2 3 OM 012 3 45670 RKPK L Ø SKPR NT NQ J NU Ø SKPR OO PQ J QO Ø VKRO OO PQ J QO Ø NOKT OS QV J SN Ø NOKT OV SU J UO Ø NRKUU OV SU J UO Ø NRKUU PS NMM J NOM Ø NVKMR PS NMM J NOM omNKSI O omOKRI P omQJS oQMT mrEeFJmNKSLO mrEeFJmOKRLP mrEeFJmQLRLS øNRKUU øNRKUU øNVKMR N N N N N N øVKRO øVKRO øVKRO N N N N N N omNKSI O omOKRI P omQJS oQNM mrewJomNKSL...

Страница 18: ... L H D E E I J C K Fig 6 1 Fig 6 2 E F TK TKNK EcáÖK TJNF NK OK 0123 RM NMM A B C D E F mie G L H I J K A E D J K B C I G F H N L S3 S2 S1 1 2 Fig 7 1 mi mie úLk RM OOMJOPMJOQM NS O NKR N NKR P OKR P OKR N OKR N OKR O MKSV O MKSV OOMJOPMJOQM OOMJOPMJOQM OOMJOPMJOQM OQ OQ NQ NQ NK P kc ks OK NM PK pP pO OQ pP pN 01234 NK OK L 01234 5 OQR fb RT PK N J J J O iJk P J pNJpO P J pOJpP P J P HM04A433_PAC...

Страница 19: ...OF mreI mrew MMN mr MPP mhe EOKRI PI QF mre MMP mh EOKRI PI QF mreI mrew MMP mr MPR 30 46 30 30 120 83 5 A B C F A H C D E G I I I H B J H B 1 B 2 Fig 7 3 A AB TB6 B 1 2 3 4 ON 1 2 3 4 ON C D B 1 C A 2 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 2 4 3 A Fig 7 5 Fig 7 6 Fig 7 2 Fig 7 4 YN pt pt L lkLlcc L L YO pt pt lkLlcc L 0 1234 L YP pt ...

Страница 20: ...E CLOCK ON OFF ßC CHECK CHECK MODE FILTER TEST RUN FUNCTION ßC 1Hr NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP TIMER SET F G E C D B A 4 3 2 1 STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C 1Hr C CHECK MODE FILTER CLOCK FUNCTION 4 1 STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C 1Hr C CHECK MODE FILTER CLOCK FUNCTION STAND BY DEFROST INDOOR UNIT ADDRESS NO CLOCK ON OFF C ...

Страница 21: ...éÉÉÇz 6 x áêÑäçïz xiçìîÉêz 0 7 xlkLlccz L 8 UKOKOK cáÖK UJO 1 NO 2 TEST RUN A 3 MODE 4 MODE 5 FAN 6 VANE 7 lkLlcc L 2 7 c k aov rql ON OFF CENTRALLY CONTROLLED ERROR CODE CLOCK ON OFF ßC CHECK CHECK MODE FILTER TEST RUN FUNCTION ßC 1Hr NOT AVAILABLE STAND BY DEFROST FILTER CHECK TEST TEMP TIMER SET D E F H IJKL M G C B A ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RE...

Страница 22: ...ESSNO CENTRALLY CONTROLLED CLOCK ON OFF C 1Hr NOT AVAILABLE C CHECK MODE FILTER CHECK FUNCTION STAND BY DEFROST INDOOR UNIT ADDRESS NO ERROR CODE OAUNITADDRESSNO CENTRALLY CONTROLLED CLOCK ON OFF C 1Hr NOT AVAILABLE C CHECK MODE FILTER CHECK FUNCTION a D E F Fig 8 3 1 2 3 P1 N N N P2 O N O P4 Q N Q P5 R N R P6 L S N S P8 U N U P9 qeR O N O UO UP N MKQ H MKQ N F1 FA N MKQ H MKQ N E0 E5 E6 EF F F F ...

Страница 23: ...KU OR 3 N 4 O 5 Q Q U 6 N mimJS ij 7 N mimJS j NMK 1 4 5 6 7 2 0 ON OFF 2 3 Fig 10 1 Fig 10 2 A D C B A 17 5 0 Fig 10 3 B A C 1 1 D E 2 F G F B 1 NMKOK cáÖK NMJO 3 0123 USM USM VNM VNM NTJOO A B C 3 D NMKOKNK cáÖK NMJP 1 G 2 0 123 45 NMKOKOK cáÖK NMJQ 1 A B C D E F G Fig 10 4 iba M iba ibaN ibaO ibaP HM04A433_PAC IM_ch p65 12 3 04 6 26 PM Page 23 Adobe PageMaker 6 5C PPC ...

Страница 24: ... F 2 G H _ I Fig 10 6 NMKQKOK EcáÖK NMJSF _ NMKQKPK EcáÖK NMJTF 01 23456789 01 E A B C D E Fig 10 7 A D C B E Fig 10 8 A B C D E NMKQKQK EcáÖK NMJUF NM 012 0123456 NMKPK NN 01234 01 23 NF OF 012 3456789 O P Q P N Q O S NMK HM04A433_PAC IM_ch p65 12 3 04 6 27 PM Page 24 Adobe PageMaker 6 5C PPC ...

Страница 25: ...D Fig 10 10 NMKSK EcáÖK NMJNMF 012345678 9 01234567 kVM 0123 NMKTK 01 2 0123 C A B A Q U 5 B C D H G E F Fig 10 11 NMKUK EcáÖK NMJNNF 0123456789 Q Q U 0123 01234 NNKOK 0 12 34567 012345678 9 012345 E F A B C D 012345678 0 E mimJS ij HM04A433_PAC IM_ch p65 12 3 04 6 27 PM Page 25 Adobe PageMaker 6 5C PPC ...

Страница 26: ......

Страница 27: ......

Страница 28: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U156H02 ...

Отзывы: