3. Installing the indoor unit

3) Installing the wall mounting fixture

s

Since the indoor unit weighs near 30 kg, selection of the mounting location
requires thorough consideration. If the wall does not seem to be strong
enough, reinforce it with boards or beams before installation.

s

The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
(Fig. 3-4)

s

Secure the wall mounting fixture through its middle row of 12-mm-dia. holes
using locally purchased bolts (through bolts, bolt anchor and nut anchor) of
M10 or W3/8 threading. The bolt tip must not protrude by more than
15 mm from the wall surface. (Fig. 3-5)
Use at least two bolts for a concrete wall, and at least four bolts for a foamed
concrete wall.

A

Wall-fixing bracket

B

Mounting bolt

C

Wall

 Warning:

If possible, secure the fixture at all the positions marked with a bold arrow.

 Caution:

The unit body must be mounted horizontally.

3.3. Preparation for piping connection

Remove the vinyl band that holds the drain piping.
• This vinyl band can be used to temporarily attach the pipes to the wall mounting

fixture while connecting the left pipe.

1) Rear, right and lower piping (Fig. 3-6)

1

Remove the right side panel.

2) Left and left rear piping

1

Remove the side panel.

When embedding pipes into the wall (Fig. 3-7)

When the refrigerant pipe, drain pipes, internal/external connection lines, etc., are to
be embedded into the wall in advance, the extruding pipes, etc., may have to be bent
and have their length modified to the unit.
• Make the pipes to be embedded slightly longer than necessary, and install.

A

Right side panel

C

On-site piping

B

Through hole

D

Wall-fixing bracket 

1

2

Remove the five screws indicated by the arrows in the diagram. (Fig. 3-8)

3

Remove the left side panel, then the lower panel.

1. While pushing up the front lower portion of the side panel (to disengage the side

panel catch from the unit catch), slide the upper portion of the side panel to the
left.

• When the indoor unit is already mounted, be sure the unit does not fall from the wall

mounting fixture.

• For reassembly, put the catch at the front lower portion of the side panel over the

unit body and push it to the right.

A

Grille

D

Catch

B

Left side panel

E

Side panel

C

Lower panel

F

Unit body

Structure of the side panel and the unit body (Fig. 3-9)

1. Panel catch engages the unit body catch.
2. Panel catch is put in the unit body hole.
3. Panel catch engages the unit body catch.
4. Sheet metal of the unit body enters the panel.
5. Panel catch enters the unit body hole.

4

The drain hose can be connected at two different positions. Use the most conven-
ient position and, if necessary, exchange the position of the drain pan, rubber plug
and the drain hose. (Fig. 3-10)

G

Drain pan

H

Band

I

Plug

J

Drain hose

K

Screwdriver

D

D

B

C

D

1

2

3

B

C

A

5

4

3

2

1

E

F

4

G

I

K

J

H

K

I

G

H

Fig. 3-7

Fig. 3-9

Fig. 3-10

Fig. 3-4

Fig. 3-5

Fig. 3-6

Fig. 3-8

Min.165

Min.60

Min.500

A

Min.165

Min.60

Min.500

A

Max.15

C

B

1

 RP2.5, RP3

2

 RP4

A

Содержание Mr.SLIM PKA-RP FAL

Страница 1: ...Air Conditioners PKA RP FAL English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ... combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install t...

Страница 3: ...80 240 225 18 18 A B C G I H F E D 1270 18 18 900 19 91 295 225 240 180 280 314 90 750 60 280 80 29 30 30 30 10 184 13 91 1183 245 285 595 I H H E D B G A C F 1 RP2 5 RP3 mm 1 2 3 4 5 6 7 8 9 A C D E B 2 RP4 Fig 3 1 Fig 3 2 Fig 3 3 3 2 Installing the wall mounting fixture Fig 3 2 1 Setting the wall mounting fixture and piping positions s Using the wall mounting fixture determine the unit s install...

Страница 4: ...pipe drain pipes internal external connection lines etc are to be embedded into the wall in advance the extruding pipes etc may have to be bent and have their length modified to the unit Make the pipes to be embedded slightly longer than necessary and install A Right side panel C On site piping B Through hole D Wall fixing bracket 1 2 Remove the five screws indicated by the arrows in the diagram F...

Страница 5: ...R 0 8 A 45 2 B C D Fig 4 1 C Apply refrigerating machine oil over the entire flare seat surface D Use the flare nuts as follows 3 4 Mounting the indoor unit Fig 3 11 1 Make sure to hang the metal catches of the indoor unit over the hooks of the wall mounting fixture 2 When the piping has been completed use the securing screws to fix the indoor unit on the wall mounting fixture Note Check that the ...

Страница 6: ...ed according to this Installation Manual to en sure correct drainage Thermal insulation of the drain pipes is necessary to prevent condensation If the drain pipes are not properly installed and insu lated condensation may drip on the ceiling floor or other possessions 6 Electrical work 6 1 Indoor unit Fig 6 1 1 Remove the right side panel To do this remove the screws on the lower and right sides R...

Страница 7: ...ant to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off A Pair No of wireless remote controller Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42 3 9 Cut J41 J42 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 1 4 3 A 2 Fig 6 4 3 CHECK 4 CHECK ON OFF TEMP FAN VANE TEST ...

Страница 8: ...he resistance between the power supply terminals and ground is at least 1 0MΩ s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Insulation resistance Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch...

Страница 9: ... operation lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possibl...

Страница 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U167H01 The product at hand is based on the following EU regulations ...

Отзывы: