background image

9

7. Test run

• For description of each check code, refer to the following table.

1

 Check code

Symptom

2

 Buzzer sound

3

 OPE LED

P1

Intake sensor error

Single beep 

×

 1

Lit for 1 sec. 

×

 1

P2

Pipe sensor error

Single beep 

×

 2

Lit for 1 sec. 

×

 2

P4

Drain sensor error

Single beep 

×

 4

Lit for 1 sec. 

×

 4

P5

Drain pump error

Single beep 

×

 5

Lit for 1 sec. 

×

 5

P6

Freezing / Overheating safeguard operation

Single beep 

×

 6

Lit for 1 sec. 

×

 6

P8

Pipe temperature error

Single beep 

×

 8

Lit for 1 sec. 

×

 8

P9

TH5 sensor error

Single beep 

×

 2

Lit for 1 sec. 

×

 2

U0–UP

Outdoor unit error

Double beep 

×

 1

Lit for 0.4 sec. + 0.4 sec. 

×

 1

F1–FA

Outdoor unit error

Double beep 

×

 1

Lit for 0.4 sec. + 0.4 sec. 

×

 1

E0–E5

Signal error between remote controller and indoor units

Sounds other than above

Lights other than above

E6–EF

Communication error between indoor and outdoor units

Sounds other than above

Lights other than above

– –

No alarm history

No sound

Not lit

F F F F

No unit

Triple beep

Not lit

• On wireless remote controller

2

The continuous buzzer sounds from receiving section of indoor unit.

3

Blink of operation lamp

• On wired remote controller

1

Check code displayed in the LCD.

• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit)

H0

H0 

 Error code

Display messages do not apper even
when operation switch is turned ON
(operation lamp does not light up).

For about 2
minutes following
power-on

After about 2
minutes has
expired following
power-on

After LED 1, 2 are lighted, LED 2 is turned off,
then only LED 1 is lighted. (Correct operation)

Only LED 1 is lighted. 

 LED 1, 2 blink.

Only LED 1 is lighted. 

 LED 1 blinks twice,

LED 2 blinks once.

• For about 2 minutes following power-on, operation of the

remote controller is not possible due to system start-up. (Cor-
rect operation)

• Connector for the outdoor unit’s protection device is not con-

nected.

• Reverse or open phase wiring for the outdoor unit’s power

terminal block (L1, L2, L3)

• Incorrect wiring between indoor and outdoor units (incorrect

polarity of S1, S2, S3)

• Remote controller wire short

On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short pipng sound.

Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED 1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED 3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.

Содержание Mr.SLIM PKA-RP FAL

Страница 1: ...Air Conditioners PKA RP FAL English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ... combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install t...

Страница 3: ...80 240 225 18 18 A B C G I H F E D 1270 18 18 900 19 91 295 225 240 180 280 314 90 750 60 280 80 29 30 30 30 10 184 13 91 1183 245 285 595 I H H E D B G A C F 1 RP2 5 RP3 mm 1 2 3 4 5 6 7 8 9 A C D E B 2 RP4 Fig 3 1 Fig 3 2 Fig 3 3 3 2 Installing the wall mounting fixture Fig 3 2 1 Setting the wall mounting fixture and piping positions s Using the wall mounting fixture determine the unit s install...

Страница 4: ...pipe drain pipes internal external connection lines etc are to be embedded into the wall in advance the extruding pipes etc may have to be bent and have their length modified to the unit Make the pipes to be embedded slightly longer than necessary and install A Right side panel C On site piping B Through hole D Wall fixing bracket 1 2 Remove the five screws indicated by the arrows in the diagram F...

Страница 5: ...R 0 8 A 45 2 B C D Fig 4 1 C Apply refrigerating machine oil over the entire flare seat surface D Use the flare nuts as follows 3 4 Mounting the indoor unit Fig 3 11 1 Make sure to hang the metal catches of the indoor unit over the hooks of the wall mounting fixture 2 When the piping has been completed use the securing screws to fix the indoor unit on the wall mounting fixture Note Check that the ...

Страница 6: ...ed according to this Installation Manual to en sure correct drainage Thermal insulation of the drain pipes is necessary to prevent condensation If the drain pipes are not properly installed and insu lated condensation may drip on the ceiling floor or other possessions 6 Electrical work 6 1 Indoor unit Fig 6 1 1 Remove the right side panel To do this remove the screws on the lower and right sides R...

Страница 7: ...ant to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off A Pair No of wireless remote controller Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42 3 9 Cut J41 J42 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 1 4 3 A 2 Fig 6 4 3 CHECK 4 CHECK ON OFF TEMP FAN VANE TEST ...

Страница 8: ...he resistance between the power supply terminals and ground is at least 1 0MΩ s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Insulation resistance Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch...

Страница 9: ... operation lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possibl...

Страница 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U167H01 The product at hand is based on the following EU regulations ...

Отзывы: