G. Timer operation
Enables control
of start and stop.
* For control by
external timer,
refer to Remote/
local combined
control operation".
H.Interlock opera-
tion with periph-
eral equipment
Enables control of
Mitsubishi Lossnay
ventilator by remote
controller.
I.Rotation
• Weekly timer:
In addition to ON/OFF, up to 8 temperature
patterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
performed once within 72 hours (can
be set in 1-hour increments).
• Auto off timer: Operation is stopped when the preset
time elapses following the start of
operation.
The time can be set from 30 minutes
to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
• Connecting a Lossnay ventilator and an indoor unit
enables control of interlock/solo ventilation opera-
tion and airflow.
(Only the microcomputer type Lossnay ventilator
can be used.)
•
•
MA Remote controller
(PAR-21MAA)
Indoor unit
Remote
Controller
Lossnay
ventilator
When abnormality occurs while operating, it
changes into operating the backup unit, and
operating is continued.
(Unit function Mode No. 20 setting No.3 , Indoor
controller board SW-5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
Each system operates alternately for 24 hours or
168 hours.
(Unit function Mode No. 20 setting No.1: 24 hours/.
No.2 : 168 hours, Indoor controller board SW 5-4
ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
This function is available when
only 2 indoor units are connected
to each outdoor unit.