En-18
S
PECIFICATIONS
Rating condition
Model
Set name
MS-GS18VF
MS-GS24VF
MS-GS30VF
MS-GS36VF
Indoor
MS-GS18VF
MS-GS24VF
MS-GS30VF
MS-GS36VF
Outdoor
MU-GS18VF
MU-GS24VF
MU-GS30VF
MU-GS36VF
Power supply
~/N, 220-230-240 V, 50 Hz
Capacity
kW
5.2-5.2-5.2
6.7-6.7-6.7
8.2-8.2-8.2
9.5-9.5-9.5
Input (set)
kW
1.47-1.475-1.48
1.90-1.90-1.91
2.32-2.33-2.34
2.70-2.70-2.79
Rated current (set)
A
6.8-6.5-6.4
8.9-8.7-8.5
10.7-10.3-10.0
12.9-12.6-12.2
Weight
Indoor
kg
14.9
14.9
20
Outdoor
kg
34.0
58.5
66.5
81.5
Dimension
Indoor
mm
325x1100x238
365x1170x295
Outdoor
mm
525x718x255
880x840x330
1258x870x295
T3 condition
Power supply
~/N, 230 V, 50 Hz
Net total cooling capacity
kW
4.70
5.92
7.034
8.215
Btu/h
16037
20200
24000
28031
Energy Ef
fi
ciency Ratio (EER)
Btu/h/W
8.60
8.60
8.60
8.60
Annual energy consumption
kWh
3730
4700
5580
6520
Guaranteed operating range
Indoor
Outdoor
Upper limit
32°C DB
23°C WB
46°C DB
—
Lower limit
21°C DB
15°C WB
21°C DB
—
DB: Dry Bulb
WB: Wet Bulb
Note:
Rating condition
Indoor: 27°C DB, 19°C WB
Outdoor: 35°C DB, 24°C WB
T3 condition
Indoor: 29°C DB, 19°C WB
Outdoor: 46°C DB, 24°C WB
01_VG79Y359H01_EN.indd 18
01_VG79Y359H01_EN.indd 18
23/6/21 10:11