32
MSZ-GC50/60/71NA
Turn OFF the power supply.
Is there rated voltage in the
power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between outdoor termi-
nal block S1 and S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICA-
TOR lamp light up? <Con
fi
rmation of the
power to the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor
contact, or wire disconnection
of the indoor/outdoor connect-
ing wire?
Yes
Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3. 1
B
1. Miswiring may damage indoor electronic control P.C. board
during the operation.
Be sure to con
fi
rm the wiring is correct before the operation
starts.
3. Be sure to check this within 3 minutes after turning ON. After
3 minutes, LED blinks 6 times. Even when the inverter P.C.
board or the outdoor electronic control P.C. board is normal,
LED blinks 6 times after 3 minutes.
(Except for outdoor unit of multi system type)
Turn ON the power supply.
Does the LED on the inverter P.C. board or
the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-second-
ON quick blinking"? 3
Yes
No
(Lighted
or not
lighted)
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
2
2. Be careful to the residual voltage of smoothing
capacitor.
Turn OFF the power supply.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC
between outdoor terminal block S2 and
S3? <Con
fi
rmation of serial signal>
Yes
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/
outdoor connecting
wire.
Turn OFF inverter-controlled lighting
equipment.
Turn OFF the power supply and then
turn ON again.
Press EMERGENCY OPERATION
switch.
•
•
•
A
Is serial signal
error indicated 6
minutes later?
B
Yes
Reinstall
either the unit
or the light
each other
away.
Attach a
fi
lter
on remote
control receiv-
ing section
of the indoor
unit.
•
•
No
Is there rated voltage between
indoor terminal block S1 and S2?
<Con
fi
rmation of power voltage>
No
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/
outdoor connecting
wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function after checking.
Yes