27
MSZ-GC50/60/71NA
Turn OFF the power supply.
Is there any foreign matter that interferes
the rotation of the line
fl
ow fan?
Yes
No
Remove the foreign matter and
adjust the line
fl
ow fan.
Pay careful attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, then press EMER-
GENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMER-
GENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and
turn ON it again, then measure the voltage.
1. Measure the voltage between CN211 (+) and (-).
2. Measure the voltage between CN211 (+) and (-).
If more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned above 2 goes 0 VDC although the
indoor electronic control P.C. board is normal
Is there 311-325 VDC between
CN211 (+) and (-), and does the
voltage between CN211 (+) and (-)
rise to the range of 3 to 6 VDC within
12 seconds after EMERGENCY
OPERATION switch is pressed?
Replace the indoor fan motor.
CN211
Indoor electronic
control P.C. board
Yes
No
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
(+) and (-) while the fan motor is
rotating.
Replace the indoor electronic control P.C. board.
Is it unchanged holding
0 or 15 VDC?
No
(Changed)
Yes
(Unchanged)
Replace the indoor electronic control P.C. board.
Replace the indoor fan motor.