1. BEFORE INSTALLATION

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

• Be sure to read these safety precautions and instructions.

‡ %HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUH

• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.

JG79A015H01

SPLIT-TYPE AIR CONDITIONERS

INSTALLATION MANUAL

 ENGLISH

Required Tools for Installation

Phillips screwdriver
Level
Scale
Utility knife or scissors
2-9/16 in. (65 mm) hole saw
Torque wrench
Wrench (or spanner)

5/32 in. (4 mm) hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer

MSZ-FD09/12NA

When installing multi units, refer to
the installation manual of the multi
unit for outdoor unit installation.

N

Do not install the unit by yourself (user).

 ,PSURSHURULQFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHHOHFWULFVKRFNLQMXU\GXHWR

WKHXQLWIDOOLQJRUZDWHUOHDNDJH&RQVXOWDTXDOL¿HGLQVWDOOHURUWKHGHDOHUIURP

whom you purchased the unit.

N

Follow the instructions detailed in the installation manual.

 ,QFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHRUHOHFWULFVKRFNLQMXU\GXHWRWKHXQLWIDOO

-

ing, or leakage of water.

N

Install the unit securely in a place that can bear the weight of the unit.

 If the installation location cannot bear the weight of the unit, the unit could fall

causing injury.

N

Perform electrical work according to the installation manual and be sure to use 
an exclusive circuit. Do not connect other electrical appliances to the circuit.

 ,IWKHFDSDFLW\RIWKHSRZHUFLUFXLWLVLQVXI¿FLHQWRUWKHUHLVLQFRPSOHWHHOHFWULFDO

ZRUNLWFRXOGUHVXOWLQD¿UHRUDQHOHFWULFVKRFN

N

Ground the unit correctly.

 Do not connect the ground wire to a gas pipe, water pipe, lightning rod or tel-

ephone ground. Defective grounding could cause electric shock.

N

Do not damage the wires.

 'DPDJHGZLUHVFRXOGFDXVH¿UH

N

Be sure to shut off the main power when setting up the indoor P.C. board or 
wiring.

 Failure to do so could cause electric shock.

N

 8VHWKHVSHFL¿HGZLUHVWRVHFXUHO\FRQQHFWWKHLQGRRUDQGRXWGRRUXQLWV$W

-

WDFKWKHZLUHV¿UPO\WRDYRLGDSSO\LQJVWUHVVWRWKHWHUPLQDOEORFN

 ,PSURSHUFRQQHFWLRQFRXOGFDXVH¿UH

N

'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHÀDPPDEOHJDVPD\OHDN

 If gas leaks and accumulates around the unit, it could cause an explosion.

N

Do not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.

 ,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFN

N

8VHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWVIRUWKHLQVWDOODWLRQZRUN

 7KHXVHRIGHIHFWLYHSDUWVFRXOGFDXVHDQLQMXU\RUOHDNDJHRIZDWHUGXHWRD¿UH

an electric shock, the unit falling, etc.

N

When plugging the power supply plug into the outlet, make sure that there is 
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that 
the power supply plug is completely in the outlet. 

If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could

FDXVHHOHFWULFVKRFNRU¿UH,IORRVHSDUWVDUHIRXQGRQWKHSRZHUVXSSO\SOXJUHSODFHLW

N

Securely attach the electrical cover to the indoor unit and the service panel to 
the outdoor unit.

If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are

QRWDWWDFKHGVHFXUHO\GXVWZDWHUHWFFRXOGFROOHFWLQWKHXQLWDQGFRXOGFDXVHD¿UHRU

an electric shock.

N

When installing or relocating the unit, make sure that no substance other than 

WKHVSHFL¿HGUHIULJHUDQW5$HQWHUVWKHUHIULJHUDQWFLUFXLW

 Any foreign substances in the refrigerant circuit can cause abnormal pressure rise

or an explosion.

N

Do not discharge the refrigerant into the atmosphere. Check that the refrigerant gas 
does not leak after installation has been completed. If refrigerant leaks during 
installation, ventilate the room.

 ,IUHIULJHUDQWFRPHVLQFRQWDFWZLWKD¿UHKDUPIXOJDVFRXOGEHJHQHUDWHG
 ,IUHIULJHUDQWJDVOHDNVLQGRRUVDQGFRPHVLQWRFRQWDFWZLWKWKHÀDPHRIDIDQ

heater, space heater, stove, etc., harmful gases will be generated.

N

Use appropriate tools and piping materials for installation. 

 The pressure of R410A is 1.6 times higher than R22. Not using the appropriate

tools and materials, or improper installation could cause the pipes to burst causing
an injury.

N

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes.

 If the refrigerant pipes are disconnected while the compressor is running and the

stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.

N

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor.

 If the compressor is started before the refrigerant pipes are connected and the

stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.

N

)DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKLVPDQXDO

 ,IIDVWHQHGWRRWLJKWDÀDUHQXWFRXOGEUHDNDQGFDXVHUHIULJHUDQWOHDNDJH

N

Install the unit  according to national wiring regulations.

N

Depending on the installation area, install a Ground Fault Interrupt (GFI) circuit 
breaker.

 If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric shock

could occur.

N

Perform the drainage/piping work securely according to the installation 
manual.

 If there is defect in the drainage/piping work, water could drip from the unit, and

damage household items.

N

 'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKHRXWGRRUXQLW

 This could cause injury.

N

Do not install the outdoor unit where small animals may live.

 If small animals enter the unit and damage its electrical parts, it could cause a

PDOIXQFWLRQVPRNHHPLVVLRQRU¿UH.HHSWKHDUHDDURXQGWKHXQLWFOHDQ

CAUTION

(Could lead to serious injury when operated incorrectly.)

 WARNING

(Could lead to death or serious injury.)

Содержание Mr. Slim MSZ-FD09NA

Страница 1: ... parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cov...

Страница 2: ...sibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the infrared remote control can operate t...

Страница 3: ...ver D Seal the wall hole gap with putty H Attach the pipe to wall with pipe at tachment strap E Attachment screw F After the leak test apply insulating mate rial tightly so that there is no gap When the piping is to be attached to a wall comprised of tin plate or metal netting use chemically treated wooden piece 25 32 in 20 mm or thicker between the wall and the piping or wrap insulation vinyl tap...

Страница 4: ... A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 7 Firmly tighten the terminal screws After tightening verify that the wires are tightly fas tened 8 Secure indoor outdoor unit connecting wire A and the ground wire with c...

Страница 5: ...the section to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall...

Страница 6: ... pipe in the dimension shown in the table Select A mm from the table according to the tool you use 5 Check RPSDUH WKH ÀDUHG ZRUN ZLWK LJ I ÀDUH LV GHIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Conduit cover Lead wire 3 OUTDOOR UNIT INSTALLATION Power supply cord K Indoor outdoor unit connecting wire A Make earth wire a little longer than others More than 2 3 8 in 60 mm For futu...

Страница 7: ... 7 After refrigerant pipes are connected and evacuated fully open all stop valves on both sides of gas pipe and liquid pipe Operating the unit without fully opening the valves lowers the performance and causes problems 8 Refer to 1 3 SPECIFICATIONS and charge the prescribed amount of refrigerant if needed Be sure to charge slowly with liquid refrigerant Otherwise composition of the refrigerant in ...

Страница 8: ...ws 0 05 to 0 MPa Gauge approx 7 25 to 0 lbf in2 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW twice to stop the operation 5 RELOCATION AND MAINTENANCE HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN 5 1 REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1 Remove the two screws that attach the panel assembly 5HPRYH WKH SDQHO DVVHPEO H VXUH W...