Appendix 4 Link Special Register (SW) List
SW0051
Data link stop status
(own station)
Stores the results when cyclic transmission is stopped by Link stop (own station)
(SB0001).
• 0: Normal
• 1 or higher: Abnormal (
When Link stop (own station) (SB0001) is turned OFF, the stored error definition is
cleared.
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW0052
Data link start status
(entire system)
Stores the results when cyclic transmission is started by System link start (SB0002).
• 0: Normal
• 1 or higher: Error definition in own station (
When System link start (SB0002) is turned OFF, the stored error definition is cleared.
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW0053
Data link stop status
(entire system)
Stores the results when cyclic transmission is stopped by System link stop (SB0003).
• 0: Normal
• 1 or higher: Error definition in own station (
When System link stop (SB0003) is turned OFF, the stored error definition is cleared.
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW0054
Temporary error
invalid station setting
result
Stores the results when executing the temporary error invalid station setting.
• 0: Normal
• 1 or higher: Abnormal (
When Temporary error invalid request (SB0010) is turned OFF, the stored error
definition is cleared.
SW0055
Temporary error
invalid station setting
cancel result
Stores the results when canceling the temporary error invalid station setting.
• 0: Normal
• 1 or higher: Abnormal (
When Temporary error invalid setting cancel request (SB0011) is turned OFF, the
stored error definition is cleared.
SW0056
Result of reserved
station function
disable
Stores the result when disabling reserved station function.
• 0: Normal
• 1 or higher: Abnormal (
When Reserved station function disable request (SB0012) is turned OFF, the stored
error definition is cleared.
SW0057
Result of reserved
station function
enable
Stores the result when reserved station function disable is undone.
• 0: Normal
• 1 or higher: Abnormal (
When Reserved station specification enable request (SB0013) is turned OFF, the
stored error definition is cleared.
SW0058
Number of total slave
stations (setting)
Stores the number of total slave stations that are set by the parameters.
• Range: 1 to 120
SW0059
Number of total slave
stations (current
value)
Stores the number of total slave stations that are actually connected by data link in the
CC-Link IE Field Network.
• Range: 1 to 120 (0 when own station is disconnected)
SW005A
Maximum baton
pass station
Stores the maximum station number of the stations where the baton pass is
performed.
• Range: 1 to 120 (0 when own station is disconnected)
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW005B
Maximum cyclic
transmission station
Stores the maximum station number of the station where the cyclic transmission is
performed.
• Range: 1 to 120 (0 when own station is disconnected)
(Conditions)
This is enabled when the Data link status (own station) (SB0049) is OFF.
SW0060
Maximum link scan
time
Stores the maximum value of the link scan time during cyclic transmission. (Unit: ms)
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
SW0061
Minimum link scan
time
Stores the minimum value of the link scan time during cyclic transmission. (Unit: ms)
(Conditions)
This is enabled when the Baton pass status (own station) (SB0047) is OFF.
Number
Name
Description
Availability
Master
station
Local
station
Содержание MELSEC Q80BD-J71GF11-T2
Страница 2: ......
Страница 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 118: ...116 12 MONITORING MEMO ...
Страница 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Страница 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Страница 243: ...241 I U Utility 83 ...
Страница 247: ......