Appendix 1 Precautions for Accessing Redundant CPU System
179
A
Checking method of path switching occurrence
When the system is communicating with the redundant CPU specification, whether communication is continued by path
switching due to communication error occurrence can be estimated.
Create a program that monitors the following special relay and special registers to check the occurrence of path switching.
<Special relay and special registers to be monitored and estimated possibility of path switching>
*1 Even if SM1600 is ON, path switching does not occur when the CPU is not accessed via the tracking cable.
*2 When using SM1600, SD1590, and SD1690 to estimate the occurrence of path switching for the Redundant CPU connected via
MELSECNET/H, check the following items on the Redundant settings in the network parameter of GX Developer.
Issue system switch in Cable disconnection timeout
Issue system switch in communication error
Check the following based on the statuses of the above special relay and special registers, and remove the error cause.
• Check the Redundant CPU for an error.
• Check the tracking cable status and whether the tracking cable is correctly connected.
• Check both the relevant network module and the network where that relevant network module is connected for an error.
Access examples of path switching
The following shows examples of path switching during access to the control system.
<Figure 1 When system switching occurs due to communication error>
SD1590
SD1690
Possibility of path switching
Reference
OFF
Either one is other than 0
Since a system switching request from the network module was detected, path
switching may have been executed.
Page 179 Access
examples of path
switching
Figure 1
ON
0
0
Since another system error occurred, path switching may have been executed.
Page 179 Access
examples of path
switching
Figure 2
ON
Either one is other than 0
Since another system error occurred or a system switching request from the
network module was detected, path switching may have been executed.
Page 179 Access
examples of path
switching
Figure 1, Figure 2
MELSECNET/H
MELSECNET/H
Control system
Standby system
Control system
Standby system
Connection to the
control system
Connection to the
control system
Communication
error
CC-Link IE Field Network module
MELSECNET/H module
CC-Link IE Field Network
CC-Link IE Field Network
CC-Link IE Field Network module
MELSECNET/H module
Tracking cable
Tracking cable
Personal computer
(CC-Link IE Field
Network board)
Personal computer
(CC-Link IE Field
Network board)
Содержание MELSEC Q80BD-J71GF11-T2
Страница 2: ......
Страница 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 118: ...116 12 MONITORING MEMO ...
Страница 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Страница 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Страница 243: ...241 I U Utility 83 ...
Страница 247: ......