16 TROUBLESHOOTING
16.9 Error Code List
169
16
D214H
Transient data request error
Correct the data length at the request source, and retry the operation.
D215H
Transient data request error
Change the mode to Online, and retry the operation.
D216H to
D217H
Transient data request error
Correct the request command at the request source, and retry the operation.
D218H
Transient data request error
At the request source, correct the number of the data to be read from or written to the device, and retry
the operation.
D219H
Transient data request error
Correct the attribute code at the request source, and retry the operation.
D21AH
Transient data request error
Correct the access code at the request source, and retry the operation.
D21BH to
D21CH
Transient data request error
Abnormal transient data were issued from the CPU module.
Replace the CPU module and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D21DH
Network No. error in transient data
A cable test cannot be applied to a network of a different network number. Correct the data in "Testing
Station Setting", and retry the cable test.
Transient data that is not applicable to a different network were received. Correct the network number or
target station number at the request source, and retry the operation.
D21EH
Target station No. error in transient
data
The communication test cannot be executed with the relay station(s) specified. Correct "Communication
Destination Setting", and then execute the communication test again.
Transient data of the application type that is not executable for the own station were received. Correct
the application type or target station number at the request source, and retry the operation.
D21FH
Target station type error (dedicated
instruction)
The SEND instruction is not applicable to head modules.
Modify the program so that the SEND instruction will not be used for head modules.
D220H
No master station
Add a master station to the network.
D222H
Transient data request error
Correct the request command at the request source, and retry the operation.
D223H
Transient error
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
Check if the cables and switching hub are connected properly.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
If this error persists, please consult your local Mitsubishi representative.
D22EH
Station No. setting not available for
the target station
Although change of the target station number was attempted online from the master station, the target
station does not have the online station number setting function.
• Check the manual for the target station for availability of the station number setting function.
• If the function is supported by the model, please consult your local Mitsubishi representative.
D22FH
No baton pass for the target station
Check the communication status of the station whose station number will be changed.
D230H
Incorrect station No. specified
Station number change was attempted for the own station (master station).
Check if no station number has been set for the target station of station number change.
D231H
Station No. already set for the target
station
For the target station of station number change, a station number has already been set.
Check if no station number has been set for the target station of station number change.
D232H
Station No. setting target not exist
The target station of station number change does not exist.
Check if no station number has been set for the target station of station number change.
D234H
No baton pass
Check the communication status.
D235H
Transient error
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
Check if the cables and switching hub are connected properly.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
If this error persists, please consult your local Mitsubishi representative.
D240H to
D243H
Target network module failure
(dedicated instruction)
Correct the following settings at the request source of the dedicated instruction, and retry the operation.
• D240H: Network number
• D241H: Target station number
• D242H: Command code
• D243H: Channel used (correct within the range)
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
D244H
Incorrect transient data
Correct the transient data at the request source, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D245H
Target station No. error (dedicated
instruction)
Correct the target station number at the request source of the dedicated instruction, and retry the
operation.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
D246H
Incorrect transient data
Correct the transient data at the request source, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
Error
code
Error code
Corrective action
Содержание MELSEC Q80BD-J71GF11-T2
Страница 2: ......
Страница 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 118: ...116 12 MONITORING MEMO ...
Страница 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Страница 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Страница 243: ...241 I U Utility 83 ...
Страница 247: ......