16 TROUBLESHOOTING
16.9 Error Code List
173
16
D62DH
Failed to start data link
The system failed to start data link due to any of the following causes.
Remove the cause of the problem, and retry the operation.
• No station number setting
• Own station error
• Master station duplication
• Station type mismatch
• No master station
• Invalid station number of the own station
• Duplication of the own station number
• Own station specified as reserved station
• Parameter error
• Parameters being sent
• Parameters not received (Only the master station, and no slave stations exist.)
• Link stop instruction
D630H
CCPASET execution error at local
station
Specify the network number, station type, and station number in the switch setting, and execute the
instruction again in the condition in which the network parameters are not set.
D701H
No station specified for Reserved
station function disable/temporary
error invalid station setting
Specify relevant station(s) in Reserved station function disable/temporary error invalid station setting
(SW0010 to SW0017), and retry the operation.
D706H
Request error of temporary error
invalid station setting/cancel or
reserved station function disable/
enable
(when the own station is a local
station)
For a local station, temporary error invalid station setting/cancel and reserved station function disable/
enable cannot be executed. Retry it on the master station.
D70BH
Request error of temporary error
invalid station setting/cancel or
reserved station function disable/
enable
(when concurrently requested to
multiple stations)
Temporary error invalid station setting/cancel by SB0010 and SB0011 and reserved station function
disable/enable by SB0012 and SB0013 cannot be executed at the same time.
Turn OFF all bits in SB0010 to SB0013, and turn ON only one bit of them in the relay.
D720H
Data link start/stop instruction out of
range
Check the setting, and then stop or start data link.
D721H
Link start/stop retry error (to another
station)
Retry the operation after stop or restart of cyclic transmission is completed.
D722H
Link start/stop retry error (to own
station)
D723H
Link start/stop retry error (to entire
system)
D724H
Link start/stop station error
Check the setting, and then stop or start cyclic transmissions.
D725H
Station type error (station executing
data link start/stop to the entire
system)
A local station cannot start or stop data link of all or multiple stations. Execute data link start/stop of all or
multiple stations from the master station
D726H
Transient data request error
Correct the request command at the request source, and retry the operation.
D727H
Data link start/stop instructing station
error
Link start was instructed from a station different from the station that instructed the link stop. The station
instructing a link start must be the same as the station that instructed the link stop.
The method of the link start (data link start instruction in CC-Link IE Field Network diagnostics or by
using the link special relay (SB) or link special register (SW) in the program) is different from that of the
link stop. Instruct the link start by the same method as used for the link stop instruction.
Link start has failed in the past. Force the system to restart data link.
D728H
Data link start/stop instructing station
error
Link start was instructed during execution of data link. Instruct link start after instruction of link stop.
D780H
History acquisition setting data full
The area for writing history acquisition setting data for the network event history is insufficient. Reset or
power OFF and then ON the module.
D781H
Hardware error
Refer to corrective action for hardware error. (
D782H
History acquisition setting data error
The previous history acquisition setting data for the network event history was not written successfully.
Reset or power OFF and then ON the module.
D783H to
D784H
Transient data request error
The read request in "CC-Link IE Field Network Diagnostics" is incorrect. Close the CC-Link IE Field
Network diagnostics dialog box, and request it again.
Check the read request data at the request source station, and retry the operation.
D785H
Flash ROM failure
The maximum number of writes to the flash ROM is exceeded. Replace the master/local module or
board.
Error
code
Error code
Corrective action
Содержание MELSEC Q80BD-J71GF11-T2
Страница 2: ......
Страница 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 118: ...116 12 MONITORING MEMO ...
Страница 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Страница 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Страница 243: ...241 I U Utility 83 ...
Страница 247: ......