![Mitsubishi Electric melsec q03ud(E)cpu Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/mitsubishi-electric/melsec-q03ud-e-cpu/melsec-q03ud-e-cpu_user-manual_239150069.webp)
67
CHAPTER 5 MC PROTOCOL COMMUNICATION
5
5.2 Sending a C
ommand fr
om the CPU Mod
ule to
an Exter
nal Device
5.2.1 Sen
ding a
n SLMP frame (
S
P
.S
LM
P
SND
)
(2) Control data
Device
Item
Description
Setting range
Set by
*1
+0
Execution/error
completion type
[1] Execution type
• 0: Without arrival check (The instruction is regarded as completed
when a request message is sent from the host station.)
*2
• 1: With arrival check (The instruction is regarded as completed
when a response message is received from the external device.)
[2] Error completion type
Specify whether to set data the instruction is completed with an
error.
• 0: Do not set data in
+13 and later at completion with an error.
(Clear
+13 and later.)
• 1: Set data in
+13 and later at completion with an error.
-
User
+1
Completion status
The completion status is stored.
0000
H
: Completed normally
Other than 0000
H
: Completed with an error (error code)
-
System
+2
Host station
channel No.
Specify the channel to be used by own station. Since whether or not
a serial number
*3
is given to the request message depends on the
channel, specify the channel as follows according to the application.
• 1: No serial number is given
• 2 to 9: Serial number is given
1 to 9
User
+3
IP address of
external device
(third and fourth
octets)
Specify the IP address (third and fourth octets) of external device.
3, 4: Indicates the octets of the IP address.
00000001H to
FFFFFFFEH (1 to
4294967294)
(both +3
and
+4 together)
User
+4
IP address of
external device
(first and second
octets)
Specify the IP address (first and second octets) of external device.
1, 2: Indicates the octets of the IP address.
User
+5
Target device port
number
Specify the port number of the target device.
1 to 65534
(1 to FFFE
H
)
User
+6
Request
destination
network number
Fixed to 0000
H
0000
H
User
+7
Request
destination station
number
Fixed to 00FF
H
00FF
H
User
S1
b15
b7
b0
1
0
0
[2]
[1]
S1
S1
S1
S1
S1
S1
b15
b7
b8
b0
3
4
S1
S1
S1
b15
b7
b8
b0
1
2
S1
S1
S1
Содержание melsec q03ud(E)cpu
Страница 2: ......
Страница 11: ...9 Memo ...
Страница 209: ...207 APPENDICES A Appendix 4 Specifications Comparison with Ethernet Module Memo ...
Страница 213: ...211 Memo ...
Страница 219: ......