1
1. OVERVIEW
This user's manual explains the specifications, names and setting of parts, wiring
and others of Type AJ65SBT-64AD analog-digital converter module (hereafter
abbreviated to the “AJ65SBT-64AD”) which is used as a remote device station of
a CC-Link system.
2. SPECIFICATION
2.1 General specifications
The general specifications of the AJ65SBT-64AD are shown below.
Item Specification
Operating ambient
temperature
Température
ambiante de
fonctionnement
0 to 55°C
0 à 55 °C
Storage ambient
temperature
-20 to 75°C
Operating ambient
humidity
10 to 90%RH, non-condensing
Storage ambient
humidity
Vibration
resistance
Compliant
with JIS B
3502 and
IEC
61131-2
Frequency
Constant
acceleration
Half
amplitude
Sweep
count
Under
Intermittent
vibration
5 to 8.4Hz
—
3.5mm
10 times
each in X,
Y, Z
directions
8.4 to
150Hz
9.8m/s
2
—
Under
continuous
vibration
5 to 8.4Hz
—
1.75mm
—
8.4 to
150Hz
4.9m/s
2
—
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2
(147 m/s
2
, 3 times each in 3 directions X, Y, Z)
Operating
atmosphere
No corrosive gases
Operating
altitude*
3
0 to 2000m
Installation
location
Inside a control panel
Overvoltage
category*
1
II or less
Pollution degree*
2
2 or less
*1 This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery
within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*2 This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity
caused by condensing must be expected occasionally.