6. WIRING
6.1 Wiring precautions
To obtain maximum performance from the functions of AJ65SBT-64AD and
improve the system reliability, an external wiring with high durability against noise
is required.
The precautions when performing external wiring are as follows:
(1) Use separate cables for the AC and AJ65SBT-64AD external input signals,
in order not to be affected by the AC side surge or conductivity.
(2) Do not bundle or place with load carrying wires other than the main circuit
line, high voltage line or programmable controller. Noises, surges, or
conductivity may affect the system.
(3) Place a one-point grounding on the programmable controller side for the
shielded line or shielded cable. However, depending on the external noise
conditions, it may be better have a grounding externally.
6.2 Module connection example
English
French
For voltage input
Pour entrée de tension
Signal source 0 to 10 V
Source de signal 0 à 10V
Shield
Pour entrée de courant
For current input
Pour entrée de courant
Signal source 0 to 20mA
Source de signal 0 à 20mA
V+
I+
COM
SLD
V+
I+
COM
SLD
FG1
CH1
*4
*1 Shield
*5
*3
CH4
*2
AG
(1) For voltage input
(2) For current input
Signal source 0 to –10 V
Signal source 0 to –20mA
*1 Shield
500k
500k
500k
500k
250
250