Operating Description

1.  Protection function 

The power supply can be derived from VT secondary. 

Set  using  condition  switches  according  to  your 
using  condition  (frequency,  output  contact,  and 
max. sensitivity angle). 

Zero-sequence  voltage  input  is  supplied  from 

secondary output of MPD-3 type ZVT combined with 
the relay. This input is transmitted to V

0

 expanded 

output terminals (M-N). 

Zero-sequence  current  input  is  supplied  from 

secondary output of MZT type ZCT combined with the 
relay. 

If  both  zero-sequence  current  and  zero-sequence 
voltage  is  greater  than  or  equal  to  the  setting 
value,  and  if  the  phase  difference  between  them 
is within the operating area, the operation timer 
starts. The relay actuates the output contact and 
operation  indicator  after  a  preset  time  of  the 
operation timer. 

After  the  relay  operation,  if  zero-sequence 

current or zero-sequence voltage falls below the 
setting value, or if the phase difference between 
them  is  out  of  the  operating  area,  the  output 
contact  will  be  in  the  state  set  by  the  using 
condition setting switch (auto-reset or self-hold). 
The operation indicator keeps the operation status 
(orange color). To reset the indicator,  move the 
reset lever up and down. 

 
2.  RUN display (Self-monitoring function) 
This  relay  monitors  control  voltage,  electric 
circuit, and program data at all time. The RUN LED 
(green) lights up in the normal condition. 
In the abnormal condition, the RUN LED goes out and 
the  error  message 

E r r

  is  displayed  on  the 

numerical  display  LED,  with  the  output  contact 
locked. 
 
3.  Numerical display function 
By  switching  the  position  of  the  indicator  select 
switch,  following  items  can  be  displayed  on  the 
numerical display LED. 

V

0

 voltage measurement 

The  display  shows  the  value  of  zero-sequence 
voltage. The display range is from 1.0% to 12.0%.  
(If input voltage is less than 1.0%, the display 
goes out. If input voltage is more than 12.0%, the 
error message 

.

. is displayed.) 

Here,  "100%"  denotes  complete  single-phase  fault 
in  6.6kV  power  systems:  V

0

  primary  =  3810V,  ZVT 

secondary = 7V. 
This  function  makes  it  possible  to  measure  the 
residual V

0

 voltage in sound condition. 

I

0

 current measurement 

The  display  shows  the  value  of  zero-sequence 
current. The display range is from 0.05A to 1.5A. 
(If input current is less than 0.05A, the display 

goes out. If input current is more than 1.5A, the 
error message 

.

. is displayed.) 

Phase measurement 

The  display  shows  the  phase  of  zero-sequence 
current relative to the zero-sequence voltage. 
The display range is 0

°

to 359

°

(lag). 

V

0

, I

0

 pickup 

When input zero-sequence voltage and zero-sequence 
current  exceeds  setting  value, 

.

- I

.  is 

displayed.  
(V

0

 pickup: 

.

   , I

0

 pickup:    

-I

.) 

When the indicator select switch is set to "PICKUP", 

   

    is displayed.  

This function can be used for operation value tests. 

Setting value 

It  displays  the  setting  condition  of  the  relay 
including  V

0

  value,  I

0

  value,  and  operating  time 

setting. 

Using condition 

When  the  indicator  select  switch  is  set  to 
"CONDITIONS",  the  using  condition  settings  of 
frequency, output contact, and maximum sensitivity 
angle are sequentially displayed at approximately 
2 second intervals in accordance with the setting 
switches of SW1 to SW3. 
For example, the settings are 50Hz, Self-hold, and 
Lead 10

°

, the display shows "50", "Ho.", and "10" 

sequentially.  
For another example, the settings are 60Hz, Auto-
reset, and Lead 45

°

, the display shows "60", "FU.", 

and "45" sequentially. 

 
4.  Fault record function 

Display of fault records 

When  a  fault  occurs,  the  relay  outputs  the 
operating signal, and at the same time the  input 
values  of  zero-sequence  voltage,  zero-sequence 
current and phase are recorded. When the indicator 
select switch is set to the position of each fault 
record,  the  records  are  displayed  starting  from 
the  latest  record  to  the  oldest  one  at 
approximately  2  second  intervals.  The  relay  can 
save the newest five phenomena. 
The records are saved in the non-volatile memory, 
therefore  the  records  can  be  read  again  after 
shutting the power off. 
Note that the fault record may not be saved if the 
auxiliary  power  supply  is  turned  off  soon  after 
the relay operation. 

Clearing of fault records 

Set indicator select switch to "CLEAR FAULT REC." 
and hold for 5s or more, then 

.

. is displayed 

and all of the fault record are cleared. 

 
5.  Display function of setting change 
When a setting is changed, the setting value after 
changing is displayed for approx. 3s preferentially.

Содержание MELPRO MDG-A3V-R

Страница 1: ...1 JEP0 IL9554 Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager ...

Страница 2: ...t Failure to do so may lead to the risk of electric shock equipment failure malfunction or failure to operate Ensure that the equipment is connected correctly in accordance with the details e g polarity or phase sequence shown on the connection terminals Otherwise there is the risk of failure burning malfunction or maloperation All power supplies and transformers to the equipment must be of suitab...

Страница 3: ...el Otherwise there are risks of electric shock injury failure malfunction and maloperation Handling and maintenance of the equipment must only be carried out after gaining a thorough understanding of the instruction manual Otherwise there is the risk of electric shock injury failure malfunction or maloperation When replacing the equipment use a product of same model rating and specifications Other...

Страница 4: ... special damages and secondary damages whether foreseeable or not compensation for accidents and compensation for damages to products other than MITSUBISHI ELECTRIC CORPORATION products and other tasks 4 Applications of products 1 The user is requested to confirm the standards the regulations and the restrictions which should be applied in case of utilizing this product and another one in combinat...

Страница 5: ...ecommended to replace 2 Product supply including repair parts is not available after production is discontinued 6 Changes in product specification The specification given in the catalogue manuals or technical documents are subject to change without prior notice 7 Scope of service The technical service fee such as engineer dispatching fee is excluded in the price of our products Please contact to o...

Страница 6: ...requency 50 60Hz switchable Auxiliary power supply AC110V Range 90 120V Settings I0 Operation value 0 1 0 2 0 4 0 6 0 8 1 0A ZCT primary value V0 Operation value LOCK 2 2 5 3 4 5 6 7 7 5 8 9 10 Single phase fault in 6 6kV power systems V0 primary 3810V ZVT secondary 7V Operating time Instantaneous 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0s Using condi tion Frequency 50Hz SW1 ON 60Hz SW1 OFF Output conta...

Страница 7: ... 6kg Approx 0 7kg shows factory setting Note It is necessary to combine MZT type ZCT and MPD 3 type ZVT with MDG A3V relay Don t combine other transformers with this relay Application to 3 3kV system voltage The MPD 3 type ZVT is intended for use at 6 6kV system voltage When applied to a system voltage of 3 3 kV ZVT secondary output voltage at single phase fault is 3 5V Half of the rating voltage ...

Страница 8: ...ax sensitivity angle 45 Max sensitivity angle 10 Lag 45 20 Lead 135 20 0 2 0 4 0 6 0 8 1 0A 90 90 180 0 Operation area Non operation area Max sensitivity angle 45 For non grounding system 0 2 0 4 0 6 0 8 1 0A 90 90 180 0 Max sensitivity angle 10 For reactor grounding system 25 65 50 85 115 155 130 Lead Lag V0 V0 Operation area Non operation area Lead Lag Operating time characteristics Input V0 0 1...

Страница 9: ...Apply standard waveform 1 2 50 μs to positive negative pole for 3 times respectively Between ZVT ZCT primary and earth 60kV Between all circuits of the relay and earth E terminal 4 5kV Between ZVT ZCT secondary and control circuit 4 5kV Between contact terminal and power supply terminal 3 0kV Between terminals of power supply 3 0kV Noise proof Apply damped oscillatory wave prescribed in JIS C 4609...

Страница 10: ...and time Set the setting values The black part is equal to maximum value but the numerical display is turned off Don t leave the switches with halfway state Setting switches for using condition Don t use any tool with a sharp point when the switches are set It may cause damage to the switch lever SW1 Frequency ON 50Hz OFF 60Hz SW2 Output contact ON Self hold Ho OFF Auto reset FU SW3 Max sensitivit...

Страница 11: ...esidual V0 voltage in sound condition I0 current measurement The display shows the value of zero sequence current The display range is from 0 05A to 1 5A If input current is less than 0 05A the display goes out If input current is more than 1 5A the error message O F is displayed Phase measurement The display shows the phase of zero sequence current relative to the zero sequence voltage The displa...

Страница 12: ...y that supplies V0 voltage from the expansion terminals must receive V0 voltage directly from the MPD 3 type ZVT Each relay directly connected to the ZVT can supply V0 voltage for 20 relay units Note To supply V0 voltage from the expansion terminals the control power of the supply source relay must be turned on The relay that receives V0 supply from the expansion terminals cannot be operated if th...

Страница 13: ...ed the number of connectable relays is limited to 5 Don t exceed the maximum number of relay units If many units more than the limitation are needed to apply V0 voltage supply V0 from expansion terminals M N to Y1 Y2 terminals The MDG A3V relay that supplies V0 voltage from the expansion terminals must receive V0 voltage directly from the MPD 3 type ZVT Each relay directly connected to the ZVT can...

Страница 14: ...T The secondary terminal k ℓ and the test terminal kt ℓt are double nuts The wiring is connected between the nuts When connecting do not loosen the inner side ZCT side nut 4 Polarity Polarity is very important to this relay Please pay attention to polarity for connecting from ZCT and ZVT and grounding point is also important 5 ZVT position The position of ZVT does not affect the characteristics or...

Страница 15: ...ic inspection Usually once a year 1 At the time of testing The input waveform should be a sine wave with little distortion During the test set the position of the indicator select switch to V0 MEASURE I0 MEASURE PHASE MEASURE or PICKUP Set the other setting switches according to the test conditions of the operating characteristic control point If user defined control point is specified e g accurac...

Страница 16: ...output contact can be forced to operate except for the case of LOCK setting 4 Operation characteristic control point Perform the test periodically according to the following test conditions and criteria Test item Test condition Criteria I0 setting V0 setting Time setting Input I0 operation value Each setting Minimum Instantaneous V0 Setting 150 at the max sensitivity angle 10 of setting value V0 o...

Страница 17: ...est method using relay tester Notes These figures show that the V0 voltage is applied from the primary side high voltage side of MPD 3C capacitor simultaneously in three phase If the V0 voltage is applied from the test terminal T of MPD 3T the voltage value should be one tenth of the value from MPD 3C high voltage side Do not apply voltage into test terminal T more than 380V If there is no test te...

Страница 18: ...hold the drawer handle or the frame part when transporting Touching the electrical circuit may cause electric shock or damage to the circuit Before the subunit is to be drawn out ensure that the following items are checked in order not to carry out the work in hot line condition Lock of the tripping circuit Turning off the main circuit Disconnect CT VT circuit Turning off the auxiliary power suppl...

Страница 19: ...the subunit with your finger hooked on the drawer handle on both sides Support the frame of subunit and pull out 2 Procedure of housing Drawer fixing screw Support the frame of subunit and place the subunit in the case along the rails Insert the subunit into the case horizontally Open the cover and tighten the drawer fixing screw Cover Cover ...

Страница 20: ...p the upper side of the cover from the inner surface Then remove from the protrusion of the body Installing the cover As shown in Fig 2 10 mount the holes on the upper side of the cover to the protrusion of the body Then press down lightly on the lower side of the cover and mount to the protrusion of the body in the same way as above When replacing the cover during operation be careful not to touc...

Страница 21: ...ied to the protection relay have limited lifetime which will bring the degradation to the relay The degree of degradation will be variable depending on the purpose aging usage environment and unevenness on the performance of each part Our company designs its products so that the recommended renewal period is 15 years or more However there may be some possibilities to occur any failures before reac...

Страница 22: ...HEAD OFFICE 7 3 MARUNOUCHI 2 CHOME CHIYODA KU TOKYO 100 8310 JAPAN First edition Jan 2021 ...

Отзывы: