7.1 Power Supply Wiring
7 - 3
7
WIRING
7.1.2
Wiring example
Connect the power supply to the power terminals on the back panel of the GOT.
7.1.3
GOT's ground
■1.
Grounding the GOT and other devices
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible.
Provide class D (class 3) grounding. (Ground resistance must be 100W or less.)
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
• Use the cable of 2mm
2
or longer for grounding.
Set the grounding point closer to the GOT to make the grounding cable short as possible.
Tightening torque for the power terminals
0.5 to 0.6N
·
m
Class D
grounding
Other
device
GOT
Other
device
GOT
Other
device
GOT
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
Grounding
(100
Ω
or less)
Grounding
(100
Ω
or less)
Содержание GOT SIMPLE GS2107-WTBD
Страница 1: ...GRAPHIC OPERATION TERMINAL User s Manual GOT SIMPLE Series ...
Страница 2: ......
Страница 22: ...1 4 1 1 Features ...
Страница 26: ...2 4 2 2 Component List ...
Страница 34: ...4 4 4 3 Bottom ...
Страница 42: ...5 8 5 2 EMC Directive Requirements ...
Страница 48: ...6 6 6 5 Installation Procedure ...
Страница 56: ...7 8 7 2 Wiring Inside and Outside the Panel ...
Страница 68: ...9 10 9 3 Utility Display ...
Страница 96: ...11 26 11 7 Keyword Step 5 Touch the Execute key Step 6 The keyword is deleted Touch OK Touch Touch ...
Страница 98: ...11 28 11 7 Keyword Step 5 Touch the Execute key Step 6 The protection is cleared Touch OK Touch Touch ...
Страница 100: ...11 30 11 7 Keyword ...
Страница 116: ...12 16 12 4 GOT internal device monitor ...
Страница 134: ...13 18 13 3 Login Logout ...
Страница 146: ...14 12 14 1 Time Setting and Display ...
Страница 260: ...17 6 17 3 Clean ...
Страница 266: ...20 2 ...
Страница 282: ...23 2 ...
Страница 288: ...REVISIONS 2 ...
Страница 291: ......