8 CANopen
®
417 Mode
8.2 Lift Number
152
FX
3U
-CAN User's Manual
8.2
Lift Number
This BFM contains the lift number to which the FX
3U
-CAN is assigned.
The Bit for the assigned lift number is set to ON (1).
Note
Only the application BFMs for which the Lift corresponding bit is set will be updated.
Data save to Flash ROM
Data can be saved in Flash ROM by CIF.
→
For Store Object Dictionary Settings in the CIF, refer to Section 10.6
8.3
Virtual Input/Output Mapping
When BFM #3001 to #3003 and #12001 to #12003 are read, the virtual input mapping information is read
from BFMs. When BFM #13001 to #13003 are read, the virtual output mapping information is read from
BFMs. And when BFM #3001 to #3003 and #13001 to #13003 are written to, the virtual output mapping
information is written to BFMs.
8.3.1
Virtual input mapping
These BFMs contain the last received input data from one of the digital input panel group objects.
Receive Ring Buffer for 252 messages. The oldest data will be shown as first.
The current numbers of messages in the receive Buffer can be read from BFM #3004 or #12004.
When the receive buffer is empty, BFM #3001 to #3003 or #12001 to #12003 shows the value H0.
1. Basic function field [Low byte in BFM #3001 and #12001]
BFM No.
Description
Bit 15
.....
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
BFM #3000
BFM #13000
Reserved
Lift 8
Lift 7
Lift 6
Lift 5
Lift 4
Lift 3
Lift 2
Lift 1
BFM No.
Description
BFM #3003
BFM #12003
BFM #3002
BFM #12002
BFM #3001
BFM #12001
High Byte
Low Byte
High Byte
Low Byte
High Byte
Low Byte
BFM #3001 to #3003
BFM #12001 to #12003
Function data field
Door field
Floor field
Lift field
Sub-function field Basic function field
BFM #3001
BFM #12001
Low Byte
Value (hex)
Description
BFM #3001
BFM #12001
Low Byte
Value (hex)
Description
00
Reserved
0D
High priority call to destination floor
01
Generic input
0E
Special function
02
Standard hall call request
0F
Access code upload request
03
Low priority hall call request
10
Speech connection request
04
High priority hall call request
11
Area monitoring connection request
05
Standard car call request
12
Fire detector
06
Low priority car call request
13 to 15
Reserved
07
High priority car call request
16
Status of safety-related circuitries
(This is not safety-related information.)
08
Standard destination call
09
Low priority destination call
17 to 1F
Reserved
0A
High priority destination call
20
Guest call
0B
Standard call to destination floor
21 to 7F
Reserved
0C
Low priority call to destination floor
80 to FF
Manufacturer-specific