Para
meter
list
8
24
∗1
Differs according to the capacity.
6%: FR-CS84-022 or lower, FR-CS82S-042 or lower
4%: FR-CS84-036 to FR-CS84-080, FR-CS82S-070, FR-CS82S-100
3%: FR-CS84-120 and FR-CS84-160
2%: FR-CS84-230 or higher
∗2
Differs according to the capacity.
5 s: FR-CS84-080 or lower
10 s: FR-CS84-120 and FR-CS84-160, FR-CS82S-042 or lower
15 s: FR-CS84-230 or higher
∗3
The Initial value for the FR-CS84-160 or lower and the FR-CS82S-100 or lower.
∗4
The initial value for the FR-CS84-230 or higher.
∗5
Available only for the three-phase power input model.
∗6
The value for the 200 V class.
∗7
The value for the 400 V class.
∗8
The parameter number in parentheses is the one used (displayed) on the LCD operation panel and the parameter unit.
T
rav
er
se
592
A300
Traverse function selection
0 to 2
1
0
593
A301
Maximum amplitude amount
0 to 25%
0.1%
10%
594
A302
Amplitude compensation amount during
deceleration
0 to 50%
0.1%
10%
595
A303
Amplitude compensation amount during
acceleration
0 to 50%
0.1%
10%
596
A304
Amplitude acceleration time
0.1 to 3600 s
0.1 s
5 s
597
A305
Amplitude deceleration time
0.1 to 3600 s
0.1 s
5 s
—
598
H105
Undervoltage detection enable/disable
selection
0, 1
1
1
—
611
F003
Acceleration time at a restart
0 to 3600 s, 9999
0.1 s
9999
—
631
H104
Inverter output fault detection enable/disable
selection
0, 1
1
1
In
creased
mag
net
ic
excit
a
tion
de
ce
lerat
ion
660
G130
Increased magnetic excitation deceleration
operation selection
0, 1
1
0
661
G131
Magnetic excitation increase rate
0 to 40%, 9999
0.1%
9999
662
G132
Increased magnetic excitation current level
0 to 200%
0.1%
100%
—
665
G125
Regeneration avoidance frequency gain
0 to 200%
0.1%
100%
Mon
ito
ring
774
M101
Operation panel monitor selection 1
1 to 3, 5, 8, 10, 14, 20,
23 to 25, 52 to 55, 61, 62,
100
1
1
775
M102
Operation panel monitor selection 2
1
2
776
M103
Operation panel monitor selection 3
1
3
—
778
T054
4 mA input check filter
0 to 10 s
0.01 s
0 s
P
rot
ective
funct
ion
872
H201
Input phase loss protection selection
0, 1
1
1
Reg
ener
ati
on
avoid
ance
882
G120
Regeneration avoidance operation selection
0 to 2
1
0
883
G121
Regeneration avoidance operation level
300 to 800 V
0.1 V
885
G123
Regeneration avoidance compensation
frequency limit value
0 to 10 Hz, 9999
0.01 Hz
6 Hz
886
G124
Regeneration avoidance voltage gain
0 to 200%
0.1%
100%
Cali
bration
p
a
ra
meter
C2
(902)
T200
Terminal 2 frequency setting bias frequency
0 to 400 Hz
0.01 Hz
0 Hz
C3
(902)
T201
Terminal 2 frequency setting bias
0 to 300%
0.1%
0%
125
(903)
T202
Terminal 2 frequency setting gain frequency
0 to 400 Hz
0.01 Hz
50 Hz
C4
(903)
T203
Terminal 2 frequency setting gain
0 to 300%
0.1%
100%
C5
(904)
T400
Terminal 4 frequency setting bias frequency
0 to 400 Hz
0.01 Hz
0 Hz
C6
(904)
T401
Terminal 4 frequency setting bias
0 to 300%
0.1%
20%
126
(905)
T402
Terminal 4 frequency setting gain frequency
0 to 400 Hz
0.01 Hz
50 Hz
C7
(905)
T403
Terminal 4 frequency setting gain
0 to 300%
0.1%
100%
PU
990
E104
PU buzzer control
0, 1
1
1
991
E105
PU contrast adjustment
0 to 63
1
58
Clear
pa
ra
mete
r
PrCL
Parameter clear
(0), 1
1
0
ALLC
All parameter clear
(0), 1
1
0
Er.CL
Fault history clear
(0), 1
1
0
—
Pr.CH
Initial value change list
—
1
0
—
Pr.MD
Group parameter setting
(0), 1, 2
1
0
Function
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increment
Initial
value
Customer
setting
Содержание FREQROL-CS80
Страница 1: ...COMPACT SMART INVERTER FREQROL CS80 FACTORY AUTOMATION ...
Страница 36: ...36 ...
Страница 37: ...37 ...