4 - 7
4.3 List of the EMC Directive compliant filters and their applicable inverters
●
FR-A701 series
Outline
dimension
(Unit: mm)
EMC filter
model name
Applicable inverter
model name
W
H
D D1
Mass
(kg)
Leakage
current
(mA) *
(reference
value)
SF1174B FR-A741-5.5K,
7.5K
213 360 38
-
1.8 51
SF1175 FR-A741-11K,
15K
253 530 60 25
4.7 76
SF1176 FR-A741-18.5K,
22K
303 600 60 29
5.9 108
SF1177 FR-A741-30K
327 700 80 29
9.4
156
SF1178 FR-A741-37K,
45K
450 770 80 36
16
156
SF1179 FR-A741-55K
467 920 80 36
19
156
* The leakage current indicated is equivalent to one-phase of cable for the three-phase three-wire star connection. For
a three-phase, three-wire, delta-connection power supply, the value is about three times greater than the indicated.
(Note) Outline dimension drawing shown is one of a typical model. The shape differs according to each model.
●
FR-E700 series
Outline
dimension
(Unit: mm)
EMC filter
model name
Applicable inverter
model name
Intercompatibility
attachment*1
W
H
D
Mass
(kg)
Leakage
current
(mA) *2
(reference
value)
Loss
(W)
SF1306
FR-E720-0.1K to 1.5K
-
110
200
36.5
0.7
10
7.3
FR-E720-2.2K, 3.7K
FR-E5T
SF1309
FR-E720S-2.2K FR-E7AT03
200
282
57
2.1 15 15
SF1320
FR-E720S-0.1K to 0.4K
-
70
168
30.5
0.4
10
2.7
SF1321 FR-E720S-0.75K
- 110
168
36.5
0.6
10
3.8
FR-E5NF-H0.75K
FR-E740-0.4K,
0.75K
-
140
210
46
1.1 22.6 5.5
FR-E5NF-H3.7K
FR-E740-1.5K to 3.7K
-
140
210
46
1.2
44.5
8
FR-E5NF-H7.5K FR-E740-5.5K,
7.5K
-
220
210
47
2
68.4
15
FR-S5NFSA-1.5K FR-E720S-1.5K
-
110
168
35
0.7 9.5 8.55
Outline
dimension
(Unit: mm)
EMC filter
model name
Applicable inverter
model name
Intercompatibility
attachment*1
W
H D D1
Mass
(kg)
Leakage
current
(mA) *2
(reference
value)
Loss
(W)
FR-E720-5.5K, 7.5K
FR-E5T-02
SF1260
FR-E720-11K FR-A5AT03
222 468 80 29
5 440
118
SF1261 FR-E720-15K FR-AAT02
253 600 86 28.5
9.3
71
37
SF1175 FR-E740-11K,
15K FR-AAT02
253 530 60 25
4.7 76 56
*1 When the intercompatibility attachment is mounted, the depth will increase by 12mm.
*2 The leakage current indicated is equivalent to one-phase of cable for the three-phase three-wire star connection. For
a three-phase, three-wire, delta-connection power supply, the value is about three times greater than the indicated.
(Note) Outline dimension drawing shown is one of a typical model. The shape differs according to each model.
W
D
D
D1
W
D
D1