Parameter
Selection of operation mode and operation location
FR-A700 EC
6 - 415
6.22
Selection of operation mode and operation location
6.22.1
Operation mode selection (Pr. 79)
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external signals (external operation),
operation from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation
and external operation (external/PU combined operation, and network operation (when RS-485
terminals or a communication option is used).
The above parameter can be changed during a stop in any operation mode.
Purpose
Parameters that must be set
Refer to
Section
Operation mode selection
Operation mode selection
Pr. 79
Started in network operation mode
Operation mode at power on
Pr. 79, Pr. 340
Selection of control source
Selection of control source, speed com-
mand source and control location during
communication operation
Pr. 338, Pr. 339,
Pr. 550, Pr. 551
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode
selection
0
0
External/PU switchover mode
External operation mode at power on
15
4–6
24–27
232–239
75
161
178–189
190–196
340
550
Jog frequency
Multi-speed
operation
Reset selection/
disconnected PU
detection/
PU stop selection
Frequency setting/
key lock operation
selection
Input terminal func-
tion selection
Output terminal
function selection
Communication
start-up mode
selection
NET mode opera-
tion command
source selection
1
Fixed to PU operation mode
2
Fixed to external operation mode
Operation can be performed by switching
between external and NET operation
mode
3
External/PU combined operation mode 1
Running frequency:
PU (FR-DU07/FR-PU04/FR-PU07) set-
ting or external signal input (multi-speed
setting, across terminals 4-5 (valid when
AU signal turns on))
Start signal:
External signal input (terminal STF, STR)
4
External/PU combined operation mode 2
Running frequency:
External signal input (terminal 2, 4, 1,
JOG, multi-speed setting, etc.)
Start signal:
Input from the PU (FR-DU07/FR-PU04/
FR-PU07), (FWD/REV keys)
6
Switch-over mode
Switch among PU operation, external
operation, and NET operation while keep-
ing the same operation status.
7
External operation mode (PU operation
interlock)
X12 signal ON::
Can be shifted to PU operation mode
(output stop during external operation)
X12 signal OFF:
Operation mode can not be switched to
PU operation mode.
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......