Frequency setting by external terminals
Parameter
6 - 186
6.10.2
Jog operation (Pr. 15, Pr. 16)
You can set the frequency and acceleration/deceleration time for jog operation. Jog operation
can be performed from either the outside or PU.
Can be used for conveyor positioning, test operation, etc.
The above parameters are displayed as simple mode parameters only when the parameter unit
(FR-PU04) is connected. When the operation panel (FR-DU07) is connected, the above param-
eters can be set only when Pr. 160 "User group read selection" = 0.
Jog operation from outside
When the jog signal is on, a start and stop can be made by the start signal (STF, STR). (The jog
signal is assigned to the terminal JOG in the initial setting.)
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
15
Jog frequency
5Hz
0–400Hz
Set the frequency for jog operation.
13
29
20
21
79
178–189
Starting frequency
Acceleration/decel-
eration pattern
selection
Acceleration/decel-
eration reference
frequency
Acceleration/
deceleration time
increments
Operation mode
selection
Input terminal
function selection
16
Jog acceleration/
deceleration time
0.5s
0–3600/360s
Acceleration/deceleration time for jog
operation.
This setting is related to to the reference
frequency set in Pr. 20 and the increments
set in Pr. 21.
Pr. 21 = 0 (Initial setting)
Setting range: 0–3600s
Inrements: 0.1s
Pr. 21 = 1
Setting range: 0–360 s
Inrements: 0.01s
The acceleration and deceleration times
cannot be set separately.
I001128E
Fig. 6-68:
Connection diagram for external jog operation
Power
supply
Forward rotation start
Reverse rotation start
Jog operation
Motor
Inverter
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......