Torque control by real sensorless vector control, vector control
Parameter
6 - 110
6.4
Torque control by real sensorless vector control, vector
control
6.4.1
Setting procedure of real sensorless vector control (torque control)
Purpose
Parameter that must be Set
Refer to
Section
Selection of torque command
source and setting of torque
command value
Torque command
Pr. 803–Pr. 806
Prevent the motor overspeed
Speed limit
Pr. 807–Pr. 809
Improve torque control accuracy
Gain adjustment for torque control
Pr. 824, Pr. 825,
Pr. 834, Pr. 835
Stabilize the torque detection signal Torque detection filter
Pr. 827, Pr. 837
Fig. 6-24:
Setting procedure of real sensorless vector control (torque control)
Sensorless
Sensorless
Sensorless
Set the motor. (Pr. 71) (Refer to section 6.12.2.)
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to section 6.2.2.)
Test run
Set the motor capacity (kW) in Pr. 80 "Motor capacity" and set the
number of motor poles in Pr. 81 "Number of motor poles".
(V/f control is performed when the setting is "9999" (initial value).)
앫
Select online auto tuning as required. (Pr. 95) (Refer to section 6.12.4.)
앫
Select manual input torque control gain adjustment as required. (Refer to section. 6.4.5.)
Perform secure wiring.
Select a control method. (Refer to section 6.2.2.)
Set either "11" (torque control) or "12" (speed-torque switchover) in
Pr. 800 and make torque control valid.
Perform offline auto tuning. (Pr. 96)
Set "3" (standard motor) or "13" (constant torque motor) in Pr. 71
"Applied motor".
Set the torque command. (Pr. 804)
Set the speed limit. (Pr. 807)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......