Product specification
Model name
EHWT17D-MHEDW
Nominal domestic hot water volume
170 L
Overall unit dimensions
1750 × 595 × 680 mm (Height × Width × Depth)
Weight (empty)
166 kg
Weight (full)
345 kg
Refrigerant
R32
The amount of refrigerant
0.9 kg
Water volume of heating circuit in the unit *1
5.47 L
Water volume of ambient loop in the unit
3.16 L
Safety device
Water circuit
(Primary)
Control thermistor
Heating
1 to 80°C
Pressure relief valve
0.3 MPa (3 bar)
Flow sensor
Min. flow 5.0 L/min
DHW tank
Control thermistor
40 to 70°C
Temperature/Pressure relief valve
90°C / 0.7 MPa (7 bar)
Immersion
heater
Manual reset
85°C
Ambient loop Control thermistor
−8 to 30°C
Flow switch
Min. flow 5.5 L/min
Refrigerant
circuit
Control thermistor (High)
−20 to 125°C
Control thermistor (Low)
−40 to 90°C
Pressure switch
4.14 ± 0.1 MPa
Pressure sensor
0 to 5.0 MPa
Primary circuit circulating Pump
DC motor
Sanitary circuit circulating Pump
AC motor
Connections
Water (Primary/DHW circuits)
28 mm compression primary circuit/
22 mm compression DHW circuit
Water (Ambient loop)
22 mm compression
Guaranteed
operating range
Ambient *2
0 to 35°C ( 80 %RH)
Water inlet temperature (Ambient loop)
10 to 30°C
Min. Water outlet temperature (Ambient loop)
4°C
Operating range
Heating
Room temperature
10 to 30°C
Flow temperature
20 to 60°C
DHW
40 to 60°C
Legionella prevention
60 to 70°C
Flow rate range
Primary circuit
Max.
27.7 L/min
Min.
7.1 L/min
Ambient loop
Max.
24.0 L/min
Min.
7.2 L/min
DHW tank performance
Maximum allowable hot water temperature
70°C
Declared load profile
L
Average climate
Water heating energy efficiency class
A+
Time to reheat 70% of DHW tank to 65°C *4
19.3 min
Time to raise DHW tank temp. 15 to 65°C *4
22.8 min
Electrical data
Heat pump
Power supply
(Phase, voltage, frequency)
~/N 230 V 50 Hz
Breaker
16 A
Immersion heater *3
Power supply
(Phase, voltage, frequency)
~/N 230 V 50 Hz
Capacity
3 kW
Current
13 A
Breaker
16 A
Sound power level at W10W35 (EN12102)
38 dB(A)
<Table 3.1>
The purpose of this installation manual is to instruct competent persons how to safely and efficiently install and commission the heat
pump unit system. The target readers of this manual are competent heating, plumbing and/or refrigeration engineers who have at-
tended and passed the requisite Mitsubishi Electric product training and have appropriate qualifications for installation of an unvented
hot water heat pump unit specific to their country.
Technical Information
3
Optional extras
• Wireless Remote Controller
PAR-WT50R-E
• Wireless Receiver
PAR-WR51R-E
• Remote Sensor
PAC-SE41TS-E
• Thermistor
PAC-TH011-E
• High temperature thermistor PAC-TH012HT-E
• ecodan Wi-Fi Interface
MAC-567IF-E1
• 2-zone kit
PAC-TZ02-E
• Expansion vessel (12L)
PAC-EVP12-E
*1 Volume of sanitary water circuit is not included in this value
*2 The environment must be frost-free.
*3 Do not fit immersion heaters without thermal cut-out. Use
only Mitsubishi Electric service parts as a direct replace-
ment.
*4 Tested under BS7206 conditions.