System Set Up
5
EN
2. DIP switch
Turn DIP switch 3-6 ON.
3. 2-way valve 2a (for Zone1) / 2-way valve 2b (for Zone2)
Electrically wire 2-way valve 2a and 2b to the appropriate external output terminals. (Refer to "External outputs" in 5.2)
5.4 2-zone valve ON/OFF control
5.5 Indoor unit only operation (during installation work)
1. Pipe work
1. Zone1 2-way valve 2a (local supply)
2. Zone2 2-way valve 2b (local supply)
3. Water circulation pump 2 (local supply) *1
4. By-pass valve (local supply) *2
*1 Install according to system in the field.
*2 For safety protection, it is recommended to install a by-pass valve.
Note: 1. Freeze stat function is deactivated whilst this control is ON.
Use anti-freeze solution to avoid freezing, if necessary.
2. When mixing tank and DHW tank are installed, install a
3-way valve (OUT4) in the primary water circuit.
4. Room thermostat connection
Opening /closing 2-way valve provides a simple 2-Zone control.
Flow temperature is common for Zone1 and 2.
In the case when DHW or heating operation is required prior to connection of the outdoor unit; i.e. during installation work, an electric heater in indoor unit (*1) can be used.
*1 Model with electric heater only.
1. To start operation
● Check if the indoor unit power supply is OFF, and turn DIP switch 4-4 and 4-5 ON.
● Turn ON the indoor unit power supply.
2. To end operation *2
● Turn OFF the indoor unit power supply.
● Turn DIP switch 4-4 and 4-5 OFF.
*2 When the indoor unit only operation is ended, ensure to check over the settings after outdoor unit is connected.
Note:
Prolonged running of the this operation may affect the life of the electric heater.
Heating operation mode
Zone1
Zone2
Room temp. control
(Auto adaptation) *3
● Wireless remote controller (option)
● Room temperature thermistor (option)
● Main remote controller (remote position)
● Wireless remote controller (option)
Compensation curve or flow temp. control
● Wireless remote controller (option) *4
● Room temperature thermostat (local supply)
● Wireless remote controller (option) *4
● Room temperature thermostat (local supply)
*3 Ensure to install the room thermostat for Zone1 in main room since the Room temp. control for Zone1 is prioritized.
*4 The wireless remote controller can be used as a thermostat.
1
3
4
2
Zone1
Zone2
In DHW or heating operation, the commands in the table below can be used.
IN11
IN12
Meaning
OFF (open)
OFF (open)
Normal operation
ON (short)
OFF (open)
Switch-on recommendation*1
OFF (open)
ON (short)
Switch-off command
ON (short)
ON (short)
Switch-on command*2
Note:
• To activate this function, settings on the main remote controller are required.
(Main menu → Service → “Function settings” Ref. add: 0, Unit: 1)
• Heating operation mode (compensation curve or flow temp. control) requires
the optional wireless remote controller.
*1 Switch-on recommendation has following 2 modes:
Mode 7 Hot water operation
Additional boost temperature is added onto the usual DHW target temperature.
(1-Inactive (default) /2-Target temp. +3°C/3-Target temp. +5°C)
Mode 8 Heating operation
Heating ON (permitted heating with thermo ON) range is extended.
(1-Inactive (default ) /2-Thermo ON temp. +2°C/3-Thermo ON temp. +3°C)
*2 Switch-on command has following 2 modes:
Hot water operation
With electrical heater or DIP SW 1-2 ON → Target temp. : 60°C
Without electrical heater and DIP SW 1-2 OFF → Target temp. : 55°C
Heating operation
Heating is ALWAYS permitted.
5.6 Smart grid ready