4. Insulation Cover Installation 

Install the insulation cover on the twinning kit after brazing the pipes and twinning kit. 
Insulate all refrigerant pipes. Insulate the high-pressure and low-pressure pipes separately, and pipes located inside the unit as well as
the outside. Use heat-resistant insulation material (Heat resistant : at least 120˚C [248˚F], Thickness: high-pressure = 10 mm [13/32 in],
low-pressure = 20 mm [13/16 in] ). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a
gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied). 

Downward slope

To BC controller 

High-pressure twinning pipe 

100mm [4 in] 
or more

A

B

Upward slope

To BC controller 

Total pipe length = A + B < 5m [16-7/16 ft]

Tape (field-supplied) 

Overlap margin of the tape 

Insulation cover 

Heat-resistant insulation material (field-supplied) 

Insulation covers can shrink. 
Overlap the tape as shown in the left 
figure so that there will be no gap in 
between the insulation cover or 
field-installed insulation material. 

field-supplied pipe 

Heat-resistant insulation material (field-supplied) 

Heat-resistant insulation material (field-supplied) 

field-supplied pipe 

field-supplied pipe 

2

High-pressure 

   twinning pipe 

L

Insulation cover 

Tape (field-supplied) 

To be gap free 

To be gap free

4

See reverse.

3. Pipe Connection Example 

Connect the pipes between outdoor units, 
using the figure below as a reference. 

Main low-pressure pipe (field-supplied) 

Main high-pressure pipe (field-supplied) 

2

High-pressure twinning pipe 

Low-pressure connecting pipe 

(field-supplied) 

High-pressure connecting pipe 

(field-supplied) 

1

Low-pressure twinning kit 

· If high-pressure twinning pipe is installed above the base of the 

outdoor unit, it should be no more than 200mm [7-7/8 in].

Outdoor unit 2

Outdoor unit 1

High-pressure 

twinning pipe 

200mm max.

To indoor unit 

5. Miscellaneous Notes 

Secure the field-supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as
necessary. 

(7) Pipe connection (high-pressure side) 

Make sure pipes from the twinning pipe to the outdoor unit are sloped downwards.

(6) The length of the straight pipe between indoor units and the twinning pipe (high-pressure pipe) 

Use the pipes supplied in the twinning kit, and make sure the section of the field-supplied pipe that connects to the twinning 
pipe has at least 500 mm [19-11/16 in] of straight section. (The section of the field-supplied pipe that connects to the twinning 
pipe must have at least 500 mm [19-11/16 in] of straight section.) If the straight section is less than 500 mm [19-11/16 in], 
it may result in equipment damage. 

Содержание CMY-R100VBK

Страница 1: ...r alterations Consult your dealer for repair Improper installation may result in water leakage electric shock or fire In the event of a refrigerant leak thoroughly ventilate the room If refrigerant leaks and comes in contact with an open flame toxic gases will be generated Properly install all parts according to the instructions in the Installation Manual If the wrong twinning pipe or wrong size c...

Страница 2: ...P72 P96 P96 P120 D0 CMY R100VBK CMY R200VBK CMY R100VBK CMY R100VBK CMY R100VBK F0 Twinning pipe Outdoor unit Low pressure E or F A3 B3 C3 D3 E3 PURY YHM PURY YHMU PURY THMU A1 A2 A3 P200 Ø15 88 Ø19 05 EP200 Ø15 88 Ø19 05 P72 Ø15 88 Ø19 05 P72 Ø15 88 Ø19 05 B1 B2 B3 P250 Ø19 05 Ø22 2 EP300 Ø19 05 Ø22 2 P96 Ø19 05 Ø22 2 P96 Ø19 05 Ø22 2 C1 C2 C3 P300 Ø19 05 Ø22 2 A P120 Ø19 05 Ø28 58 P120 Ø19 05 Ø2...

Страница 3: ...e cover and attach compressor cables to item 9 pipe cover with item M cable tie to keep them out of direct contact with the pipes 1 3 5 6 Field supplied pipes Field supplied pipes Connect the pipe so that the dimples on the 7 high pressure pipe are on an imaginary line parallel to the edge of the cutout hole 9 Wrap the pipe cover here Attach compressor cables to Pipe cover with Cable tie to keep t...

Страница 4: ... 2High pressure twinning pipe LInsulation cover Tape field supplied To be gap free To be gap free 4 See reverse 3 Pipe Connection Example Connect the pipes between outdoor units using the figure below as a reference Main low pressure pipe field supplied Main high pressure pipe field supplied 2High pressure twinning pipe Low pressure connecting pipe field supplied High pressure connecting pipe fiel...

Отзывы: