8.3.  Air vent operation

This operation removes the air from the water circuit after water is supplied to it.
Perform this operation after completion of the following.

 *1

• Water piping work

 *2

• Air-tightness test of water piping
• Electrical work
• Refrigerant piping work

 *3

• Air-tightness test of refrigerant piping

 *3

• Evacuation of refrigerant circuits

 *3

• Refrigerant charging

 *3

*1.  Perform air vent operation after completion of water- and refrigerant-piping work, 

air-tightness tests, electrical work, evacuation of refrigerant circuits, refrigerant 
charging, and debris removal operation (shown on previous pages).

*2.  

Install an automatic air vent valve at the highest point of each branch pipe from the HBC (in two places at the highest point of the 
return pipe from the Sub-HBC, and in six places at the highest point of the return pipes from indoor units). (See Figure 1.)

  

Failure to install air vent valves may leave air in the water circuit and damage the pump. 

*3.  Air vent operation can be performed before completing the refrigerant piping work, air-tightness test of refrigerant piping, evacuation of 

refrigerant circuits, and refrigerant charging. 
In this case, 

perform an air vent operation again after refrigerant piping work, air-tightness test of refrigerant piping, evacuation of 

refrigerant circuits, and refrigerant charging have been completed,

 because the initial air vent operation may not be able to remove all 

dissolved oxygen in the water circuit.

1.   Preparation for air vent operation

1.  DIP SW settings

[Main-HBC]
Turn on DIP SW001-1. (Water circuit valve setting (valve open when stopped))

7XUQRQ',36:1XOOL¿FDWLRQRIWKHGUDLQRYHUÀRZHUURUIRUKRXUV$SSOLFDEOHZ%&&0%:09%%LVFRQQHFWHG

2.  Turn on the breaker for each unit, and then open the manual air vent valves on the Sub-HBC and the indoor units. (The Main-HBC does not 

have an manual air vent valve.)

1RWHWKDWLIWKHPDQXDODLUYHQWYDOYHVDUHRSHQHGWRRPXFKDODUJHDPRXQWRIZDWHUPD\EODVWRXWDQGRYHUÀRZIURPWKHGUDLQSDQ

,IWKHUHDUHDLUYHQWYDOYHVRQWKH¿HOGLQVWDOOHGSLSHVRSHQWKHYDOYHVDVZHOO

Maintenance-side

Maintenance-side

6XE+%&&0%:09%%

,QGRRUXQLW([DPSOH3()<:390$(

3.  Supply water from the water supply pipe on the HBC.

Water supply pipe

,QVWDOODQRQUHWXUQYDOYHWRSUHYHQWZDWHULQWKHXQLWIURPÀRZLQJEDFNWRWKH

water supply pipe, or remove the water supply hose after the air vent operation.

Connection of water supply pipe

4.  Check that water is coming out of the manual air vent valve on each unit, and perform the air vent operation.

Figure 1. Automatic air vent valve

Automatic air vent 
valve

Manual air 

vent valve

01_WT09805X01_en.book  21 ページ  2021年11月1日 月曜日 午前8時47分

Содержание CMB-WM1016V-BB

Страница 1: ...alar a unidade de ar condicionado sv INSTALLATIONSHANDBOK Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras för säker och korrekt användning tr MONTAJ ELKİTABI Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz pl PODRĘCZNIK INSTALACJI W celu bezpiecznego i poprawnego korzystania...

Страница 2: ...tdoor unit is higher than HBC F Less than H1 40 m when the outdoor unit is lower than HBC G Branch joint field supply H Junction pipe field supply I Less than 110 m J Less than 60 m K Connecting indoor unit less than 80 L Connecting indoor unit more than 100 M Up to three units for 1 branch port Total capacity less than 80 but in same mode cooling heating N Less than 15 m O Less than 15 m CMB WM35...

Страница 3: ...door unit side PURY E M200 HBC CMB WM350F AA ø15 88 Brazing ø19 05 Brazing PURY E M250 ø15 88 Brazing ø22 2 Brazing PURY E M300 ø15 88 Brazing ø22 2 Brazing PURY E M350 ø15 88 Brazing ø28 58 Brazing PURY E M400 HBC CMB WM500F AA ø19 05 Brazing ø28 58 Brazing PURY E M450 ø19 05 Brazing ø28 58 Brazing PURY E M500 ø19 05 Brazing ø28 58 Brazing Note Be sure to use non oxidative brazing A To outdoor un...

Страница 4: ...ew for drain pan A Holes for drain piping field supply B Drain pan C Socket field supply D Drain piping field supply E Insulation for drain piping field supply Unit mm 1 A A B C B A 25 cm B 1 5 2 m A Downward gradient of more than 1 100 B Insulating material C Supporting bracket D Sub HBC E Tie band accessory F Insertion margin G Drain hose accessory H Drain pipe O D ø32 PVC TUBE field supply I In...

Страница 5: ...ting port J Water inlet EXP VESSEL Note Remove burr after cutting the piping to prevent entering the pipe connection Check that there is no crack at the edge of the piping Water inlet port EXP VESSEL connecting port Sub HBC connecting port Indoor unit connecting port Main HBC connecting port Indoor unit connecting port Unit mm A B C C D D E E F F Note See Fig 5 1 5 when connecting valves to the on...

Страница 6: ... mm W WP WL151 W WP WL250 I D 32 6 mm I D 32 6 mm II D 39 6 mm W WP WL251 W WP WL300 I D 32 6 mm I D 39 6 mm I D 50 8 mm W WP WL301 W WP WL750 I D 50 8 mm I D 50 8 mm I D 50 8 mm A To outdoor unit B End connection brazing C Main HBC Maximum total capacity of connected indoor units W WP WL170 D Sub HBC Maximum total capacity of connected indoor units W WP WL250 E Indoor unit F Branch joint field su...

Страница 7: ...F Unit side insulating material C B A D C E F C E C A E Fig 6 0 1 A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring E Cable strap F Wire saddle CMB WM350F AA CMB WM500F AA A B C D E E A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring E Clip cables here CMB WM108V BB CMB WM1016V BB 01_WT09805X01_en book 7 ページ 2021年11月...

Страница 8: ...eration may lead to damage fire explosions etc Do not change the set values as this may lead to damage fire explosions etc Use of any product except that specified by this company may lead to damage fire explosions etc Do not spray water on electrical parts This could lead to shorting fire smoke electrical shock unit failure etc Do not create a situation where the refrigeration circuit is sealed y...

Страница 9: ...here food pets plants precision instruments or artwork are kept The quality of the food etc may deteriorate Do not use the air conditioner in special environments Oil steam sulfuric smoke etc can significantly reduce the performance of the air conditioner or damage its parts When installing the unit in a hospital communication station or similar place provide sufficient protection against noise So...

Страница 10: ...so that the drain pan can function correctly Install the HBC in an environment where the temperature in always above 0 C 2 3 Securing installation and service space 1 Installation This is a reference view showing the least installation space Fig 2 3 1 P 2 Fig 2 3 2 P 2 2 4 Checking the installation site Check that the difference of elevation between indoor and outdoor units and the length of refri...

Страница 11: ...hat load is not imparted to the HBC s end connections 3 When using mechanical couplings use the ones that meet ISO14903 4 Support the on site pipes near the HBC at 0 5 meter intervals or less and at 2 meter intervals or less in other areas Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant R32 specified on the unit Mixing of a different refrige...

Страница 12: ... must be covered with insulation with its seam facing upward and fastened with the bands 4 4 Additional refrigerant charge Notes Charge refrigerant in a liquid state Do not use a charging cylinder when charging refrigerant The use of a charging cylinder may change the composition of the refrigerant and lead to a performance drop The table below summarizes the factory charged amount of refrigerant ...

Страница 13: ...16 kg m High pressure pipe ø15 88 total length 0 11 kg m Outdoor unit model Amount kg HBC model Amount kg E M200 1 0 350F 5 6 E M250 1 0 500F 5 6 E M300 0 E M350 0 E M400 0 E M450 0 E M500 0 Amount of refrigerant to be charged for single module units Amount of additional charge kg High pressure pipe ø22 2 total length 0 19 kg m High pressure pipe ø19 05 total length 0 13 kg m High pressure pipe ø1...

Страница 14: ...t port on the HBC Failure to do so will result in incorrect running Please list the indoor units on the naming plate in the HBC unit with addresses and end connection numbers Use the reverse return method to insure proper pipe resistance to each unit Provide some joints and valves around inlet outlet of each unit for easy maintenance checkup and replacement Install a suitable air vent on the water...

Страница 15: ...to an HBC the pipes that connect the unit to the same set of HBC ports cannot be branched out to connect additional units Selection of water piping Select the size according to the total capacity of indoor units to be installed down stream Do not connect multiple indoor units to the same port when operating each of them in different modes cooling heating stop and thermo OFF The indoor units connec...

Страница 16: ...alve and pres sure reducing valve 5 3 Water treatment and quality control To preserve water quality use the closed type of water circuit When the circulating water quality is poor the water heat exchanger can develop scale leading to a reduction in heat exchange power and possible corrosion Pay careful attention to water processing and water quality control when installing the water circulation sy...

Страница 17: ...set to 000 when shipped from the factory Set the address switch to an address that equals the lowest address of the indoor units that are connected to the HBC Sub HBC plus 50 Assign the HBC address that equals the lowest address of the indoor units that are connected to the HBC Sub HBC plus 50 However if the address overlaps any other units addresses assign the address that equals the next lowest ...

Страница 18: ... on DIP SW001 1 Water circuit valve setting valve open when stopped 7XUQ RQ 3 6 1XOOL FDWLRQ RI WKH GUDLQ RYHUÀRZ HUURU IRU KRXUV SSOLFDEOH ZKHQ D 6XE 0 0 9 LV FRQQHFWHG 2 Turn on the breaker for each unit and then open the manual air vent valves on the Sub HBC and the indoor units The Main HBC does not have a manual air vent valve 1RWH WKDW LI WKH PDQXDO DLU YHQW YDOYHV DUH RSHQHG WRR PXFK D ODUJ...

Страница 19: ...al operation is being performed no other functions of the Maintenance Tool are available for use 1 Follow the procedures below after connecting the MN converter and starting up the Maintenance Tool Manuals are accessible from the Maintenance Tool Debris removal operation procedure without connection to an outdoor unit 2SWLRQĺ RPPLVVLRQLQJ VXSSRUWĺ 95 5 FRPPLVVLRQLQJ 1 6HOHFW 2SWLRQ ĺ RPPLVVLRQLQJ ...

Страница 20: ...ts inside IWHU FOHDQLQJ DQG UH WWLQJ WKH VWUDLQHU WXUQ Rႇ 3 6 7 Make sure the strainers are re installed properly Flowchart for debris removal operation Turn on DIP SW002 1 Air 1 Intermittent operation of water pump 20 min The operation is performed to discharge air from the water circuits Air1 Air 2 Water supply to all indoor units 20 min Debris in the pipe will accumulate into the strainer by su...

Страница 21: ...air tightness test of refrigerant piping evacuation of refrigerant circuits and refrigerant charging have been completed because the initial air vent operation may not be able to remove all dissolved oxygen in the water circuit 1 Preparation for air vent operation 1 DIP SW settings Main HBC Turn on DIP SW001 1 Water circuit valve setting valve open when stopped 7XUQ RQ 3 6 1XOOL FDWLRQ RI WKH GUDL...

Страница 22: ...to an outdoor unit 2SWLRQĺ RPPLVVLRQLQJ VXSSRUWĺ 95 5 FRPPLVVLRQLQJ 1 6HOHFW 2SWLRQ ĺ RPPLVVLRQLQJ VXSSRUW ĺ 95 5 commissioning 2 FRQ UPDWLRQ ZLQGRZ ZLOO DSSHDU KHFN WKH PHVVDJH DQG SUHVV Next to proceed 0DQXDOV DUH DFFHVVLEOH IURP WKH FRQ UPDWLRQ ZLQGRZ 3 After the units are searched for a sign that indicates the completion of preparation will appear Turn on DIP SW002 3 of the Main HBC to start t...

Страница 23: ...ndoor units extracts and releases saturated air from the water FLUFXLW LU ĺ LU 1 The operation can be forced to stop by turning on DIP SW002 4 2 If it is found during any step that air has not been discharged to the desired degree repeat the air discharge operation from the beginning 3 I DQ HUURU VLJQ UU DSSHDUV RQ WKH RQ WKH FLUFXLW ERDUG RI WKH WXUQ Rႇ WKH EUHDNHU WXUQ LW EDFN RQ DQG UHSHDW WKH ...

Страница 24: ...PS Date of manufacture is indicated in format yyyy mm in the YEAR OF MANUFACTURE field on the nameplate 01_WT09805X01_en book 25 ページ 2021年11月1日 月曜日 午前8時47分 ...

Страница 25: ... bortset fra forbindelseselementer som f eks bolte med den drevne enhed f eks aksel eller selve huset og må ikke være desig net på en sådan måde at motoren kan adskilles fuldstændig fra den drevne enhed og fungere uafhængigt Adskillelsesprocessen skal bevirke at motoren sættes ud af drift d den specifikke grund til DE a Herstellername oder Handelsmarke Handelsregisternummer und Adresse b Modellken...

Страница 26: ...zna nie może być sprawdzona niezależnie od produktu nawet przy zapewnieniu tymczasowego łożyska od strony tarczy i od strony napędu taki silnik musi posiadać wspólne komponenty oprócz elementów łączących takich jak śruby z napędzanym urządzeniem np wał lub obudowę i nie może być zaprojektowany w sposób umożliwiający jego całkowite oddzielenie od napędzanego urządzenia i niezależną eksploatację Pro...

Страница 27: ...01_WT09805X01_en book 31 ページ 2021年11月1日 月曜日 午前8時47分 ...

Страница 28: ...y Directive 2014 30 EU Pressure Equipment Directive 2014 68 EU Machinery Directive 2006 42 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN MANUFACTURER MITSUBISHI ELECTRIC CORPORATION Air conditioning Refrigeration Systems Works 5 66 Tebira 6 Chome Wakayama city 64...

Страница 29: ...Related Links Model Number CMB WM1016V BB CMB WM F V AA B _InstallationManual_WT09805X01 CMB WM F AA_ServiceHandbook_HWE21050 HVRF_Information_Pack_Ver1 0_ Vertical Horizontal HBC Databook MEES21K003 ...

Отзывы: