1. Size of BC controller’s end connection piping

[Fig. 4.1.1] (P.3)

(Unit: mm)

Piping portion

High pressure

Low pressure

Item

(liquid) side

(gas) side

PURY-200

ø25.4 (Brazing)

PURY-P200

ø19.05

PURY-250

(Brazing)

ø28.58 (Brazing)

PURY-P250

Indoor unit side

ø9.52 (Flare)

ø15.88 (Flare)

A

To outdoor unit

B

End connection (brazing)

C

BC controller

D

Reducer (accessory)

E

Indoor unit

F

Less than 40

G

Combined piping kit (Model name: CMY-R160-H)

H

Branch pipe (Model name: CMY-Y102S-F)

I

Up to three units for 1 branch hole; total capacity: below 80 (but same in cooling/
heating mode)

The size of BC controller’s branch hole piping is for 50 to 63 type indoor units.
Therefore, if you want to connect indoor units other than the above, do pipe con-
nection following the procedure below.

*1. For connecting 20 to 40 type indoor units

Connect indoor units using the reducers (specials) supplied with BC controllers.

Note:
The flare nuts supplied with BC controllers should be used together.

*2. For connecting 100 to 140 type indoor units (or more than a total indoor

unit capacity of 81)

After combining two branch holes using an optionally available combined piping kit
(CMY-R160-H), connect indoor units.

*3. Connection of plural indoor units with one connection (or joint pipe)

Total capacity of connectable indoor units: Less than 80 (Less than 160 with
joint pipe)

Number of connectable indoor units: Maximum 3 Sets

Branch pipe: Use the branch pipe for CITYMULTI Y Series (CMY-Y102S-F)

Selection of refrigerant piping (Piping size of A/B sections in the above figure)
Select the size according to the total capacity of indoor units to be installed
downstream.

Total capacity of indoor units

Liquid line

Gas line

Below 80

ø9.52

ø15.88

81 to 160

ø12.7

ø19.05

2. Connecting to outside pipes (low pressure side pipes)

For PURY-250

PURY-P250

[Fig. 4.1.2] (P.3)

For PURY-200

PURY-P200

[Fig. 4.1.2] (P.3)

A

BC controller

B

Locally procured pipe ø28.58

C

Locally procured pipe ø25.4

D

Refrigerant conn. pipe (accessory)

Note:
Be sure to use non-oxidative brazing.

4.2. Refrigerant piping work

After connecting the refrigerant pipes of all indoor and outdoor units with the out-
door units’ stop valves remained fully closed, evacuate vacuum from the outdoor
units’ stop valve service ports.
After completing the above, open the valve rods of the indoor units’ stop valves.
This connects the refrigerant circuit (between outdoor and BC controller) com-
pletely.
How to handle stop valves is described on each outdoor unit.

Notes:

Before tightening the flare nut, apply refrigerating machine oil lightly over
the valve flare surface and its seating surface.

Use a double spanner for pipe connection.

After pipe connection, be sure to check that there is no gas leakage,
using a leak detector or soap-and-water solution.

Before brazing the refrigerant piping, 

always wrap the piping on the main

body, and the thermal insulation piping, with damp cloths to prevent heat
shrinkage and burning the thermal insulation tubing.

 Take care to ensure

that the flame does not come into contact with the main body itself.

 Warning:

Do not mix anything other than the specified refrigerant (R-22 or R407C) into
the refrigerating cycle when installing or moving. Mixing air may cause the
refrigerating cycle to get abnormally high temperature, resulting in a burst.

Outdoor

unit side

 Caution:

Cut the tip of the indoor unit piping, remove the gas, and then remove the
brazed cap.

[Fig. 4.2.1] (P.3)

A

Cut here

B

Remove brazed cap

4.3. Insulating refrigerant pipes

Be sure to wind heat-resisting polyethylene form of more than 10mm in thickness
onto both liquid and gas pipes and also put it into the joints between indoor unit
and insulating material so that there will be no gap. Incomplete insulation may
cause a risk of dew drop. Pay careful attention, particularly when insulating above
the ceiling.

[Fig. 4.3.1] (P.3)

A

Locally procured insulating material for pipes

B

Bind here using band or tape.

C

Do not have any opening.

D

Lap margin: more than 40

E

Insulating material (field supply)

F

Unit side insulating material

4.4. Drain piping work

1. Drain piping work

Ensure that the drain piping is downward (pitch of more than 1/100) to the
outdoor (discharge) side. If it is impossible to take any downward pitch, use an
optionally available drain-up mechanism to obtain a downward pitch of more
than 1/100.

Ensure that any cross-wise drain piping is less than 20 m. If the drain piping is
long, provide metal braces to prevent it from waving. Never provide any air vent
pipe. Otherwise drain may be ejected.

Connect the supplied drain hose to the discharge port on the unit body. Use
hard vinyl chloride pipes VP-25 (ø32) for drain piping (

2

). Tighten the supplied

drain hose onto the discharge port using the supplied hose band. (For this, do
not use any adhesive because the drain hose will be removed for service later.)

Do not have any odor trap around the discharge port.

[Fig. 4.4.1] (P.3)

A:

25 cm

B:

1.5 – 2 m

A

Downward pitch of more than 1/100

B

Insulating material

C

Supporting bracket

D

Drain discharge port

E

Insulated pipe (accessory)

F

Tie band (accessory)

G

Hose band (accessory)

H

Drain hose (200 mm long)

As shown in 

3

, install a collecting pipe about 10cm below the drain ports and

give it a downward pitch of more than 1/100. This collecting pipe should be of
VP-30.

Set the end of drain piping in a place without any risk of odor generation.

Do not put the end of drain piping into any drain where ionic gases are gener-
ated.

Although it is free to choose to take out piping in any direction, be sure to
observe the instructions above.

When using an optionally available drain-up mechanism, follow its instruction
manual for drain piping.

[Fig. 4.4.2] (P.3)

A

BC controller

B

Indoor unit

C

Collecting pipe

D

Take as large as possible. About 10 cm.

2. Discharge test

After completing drain piping work, open the BC controller panel, fill water, and test
drain discharge. At this moment, check to see that there is no water leakage from
the connections.

3. Insulating drain pipes

Provide sufficient insulation onto the drain pipes just as for refrigerant pipes.

 Caution:

Be sure to provide drain piping and heat-insulate it in order to prevent dew
condensation. If there is a deficiency in piping work, it may cause a risk of
water leakage and so wet your property.

Содержание CMB-P-V-F

Страница 1: ...etto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado...

Страница 2: ...me A CMB P104V F 648 CMB P105V F 648 CMB P106V F 648 CMB P108V F 648 CMB P1010V F 648 CMB P1013V F 1098 CMB P1016V F 1098 Length Between indoor and outdoor Unit m Item Piping portion Allowable value Total piping length A B a b Below 220 c d e Longest piping length A e Below 100 Below 90 1 Between outdoor and BC A Below 70 controllers Below 60 1 Between indoor and BC controllers e Below 30 Above ou...

Страница 3: ...for CITYMULTI Y Series CMY Y102S F Selection of refrigerant piping Piping size of A B sections in the above fig ure Select the size according to the total capacity of indoor units to be installed downstream Total capacity of indoor units Liquid line Gas line Below 80 ø9 52 ø15 88 81 to 160 ø12 7 ø19 05 E E E E E I E A B G 2 H 1D 50 63 100 140 3 C 4F A BC controller B Locally procured pipe ø28 56 C...

Страница 4: ...ng the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other heat source it may generate noxious gases Do not reconstruct or change the...

Страница 5: ...tal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them If children play with a plastic bag which was not torn apart they face the risk of suffocation 1 5 Before starting the test run Caution Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main p...

Страница 6: ... If it is oblique loosen the fixing nut and make an adjustment Caution Be sure to install the unit body at level 4 Connecting refrigerant pipes and drain pipes 4 1 Connecting refrigerant pipes 1 Connect the liquid and gas pipes of each indoor unit to the same end connec tion numbers as indicated on the indoor unit flare connection section of each BC controller If connected to wrong end connection ...

Страница 7: ...with the main body itself Warning Do not mix anything other than the specified refrigerant R 22 or R407C into the refrigerating cycle when installing or moving Mixing air may cause the refrigerating cycle to get abnormally high temperature resulting in a burst Outdoor unit side Caution Cut the tip of the indoor unit piping remove the gas and then remove the brazed cap Fig 4 2 1 P 3 A Cut here B Re...

Страница 8: ...e outdoor unit However if this would result in it having the same ad dress as another outdoor unit set the address between 51 and 100 mak ing sure that it is different from the address of other controllers Please refer to the outdoor unit installation manual 7 Test run Before getting test run checked s After installing piping and wiring the indoor units and BC controllers check to see again that t...

Страница 9: ... электрошоку При установке и перемещении кондиционера на другой объект не заряжайте его другим хладагентом кроме хладагента R407С или R22 указанного на приборе При смешении другого хладагента или воздуха с первоначальным хладагентом может произойти сбой цикла охлаждения и прибор может быть поврежден Если кондиционер установлен в небольшом помещении необходимо принять меры для предотвращения концен...

Страница 10: ...может приветси к электрошоку Используйте сетевой кабель достаточной мощности напряжения Кабели слишком малой мощности могут прогореть вызвать перегрев и пожар Используйте прерыватель цепи и предохранитель указанной мощности Предохранитель или прерыватель цепи большей мощности или использование стального или медного провода могут вызвать общую поломку прибора или пожар Не мойте детали кондиционера ...

Страница 11: ...D Двойные гайки Приобретаются на месте E Анкерный болт М10 Приобретается на месте Поместите таким образом чтобы обеспечить достаточную легкость прокладки труб для воды хладагента и электропроводки Избегайте установки в местах подверженных скоплению притоку образованию или утечки возгорающихся и сернистых газов Помещайте таким образом чтобы обеспечить возможность прокладки дренажных труб под наклон...

Страница 12: ... мм Часть трубы Часть PURY 200 ø25 4 Пайка PURY P200 ø19 05 PURY 250 Пайка ø28 58 Пайка PURY P250 ø9 52 ø15 88 колокообразный колокообразный A К внешнему прибору B Концевое соединение C Регулятор BC D Переходник поставлен E Внутренний прибор F Менее 40 G Набор соединения труб название модели CMY R160 H H Труба ответвления наименование модели CMY Y102S F I До трех приборов на одно отверстие креплен...

Страница 13: ...а Обязательно обверните полиэтиленовую температуроустойчивую изоляцию свыше 10 мм толщиной на трубы жидкости и газа а также поместите ее в места соединения между внутренним прибором и изолирующим материалом таким образом чтобы не было зазора Неполная изоляция может привести к образованию конденсации Проявляйте особое вни мание в особенности при установке прибора в потолке Fig 4 3 1 P 3 A Изолирующ...

Страница 14: ...адрес в пределах от 51 до 100 При этом убедитесь что данный адрес отличается от адресов других регуляторов См Руководство по установке внешнего прибора 7 Выполнение испытания До проведения испытания s По завершении инсталляции трубных соединений и электросоединений внутренних устройств и регуляторов еще раз убедитесь в отсутствии утечки хладагентов и провисания кабелей питания и регулировки s Испо...

Страница 15: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: