3. Installing BC controller

3.1. Checking the accessories with BC con-

troller

The following items are supplied with each BC controller.

Item

Qty

1

Drain hose

1

2

Pipe cover for drain hose

1

3

Tie band

2

4

Hose band

1

5

Reducer (large & small)

Same number as

branch holes

6

Refrigerant conn. pipe

1

2. When stacking on a rack

(This is a reference view showing the least installation space.)

[Fig. 2.2.2] (P.2)

Model name

A

CMB-P104V-F

648

CMB-P105V-F

648

CMB-P106V-F

648

CMB-P108V-F

648

CMB-P1010V-F

648

CMB-P1013V-F

1098

CMB-P1016V-F

1098

A

On the side of outdoor unit piping

B

On the side of indoor unit piping

2.3. Checking the installation site

Check that the difference of elevation between indoor and outdoor units and the
length of refrigerant piping are within the following limitations.

[Fig. 2.3.1] (P.2)

A

Outdoor unit

B

BC controller

C

Indoor unit

D

More than 81

E

Less than H=50 m (when the outdoor unit is higher than the indoor unit)

F

Less than H1=40 m (when the outdoor unit is lower than the indoor unit)

G

Branch pipe (for Y Series) CMY-Y102S-F

J

Combined pipe (CMY-R160-HA: optional)

K

Less than 70 (60 m)

L

Less than 30 m

M

Up to three units for 1 branch hole

Total capacity: less than 80 (but same in cooling/heating mode)

L

Less than h1=15 m (10 m or less for 125, 140 unit type)

M

Less than h2=15 m

(Unit: m)

Item

Piping portion

Allowable value

Total piping length

A+B+a+b

Below 220

+c+d+e

Longest piping length

A+e

Below 100

(Below 90)*1

Between outdoor and BC

A

Below 70

controllers

(Below 60)*1

Between indoor and BC controllers

e

Below 30

Above outdoor

H

Below 50

Below outdoor

H1

Below 40

Between indoor and BC controllers

h1

Below 15

(Below 10)*2

Between indoor and indoor

h2

Below 15

(Below 10)*2

Notes:
*1 In the table, if the total capacity of indoor units exceeds 130 % of outdoor

units, it will be the values inside parentheses.

*2 10m or less, with indoor units with model numbers of 125, 140.

Length

Diff

erence of ele

v

ation

Between indoor

and outdoor

3.2. Installing BC controllers

Installing hanging bolts

Install locally procured hanging bolts (all screws) firmly following the procedure
given in the figure. The hanging bolt size is ø10 (M10 screw).
To hang the unit, use a lifting machine to lift and pass it through the hanging bolts.

[Fig. 3.2.1] (P.2)

1

Hanging method

2

Installing-on-the-floor method

A: Min.30

A

Hanging bolt ø10 (field supply)

B

Nut (field supply)

C

Washer (field supply)

D

Double nuts (field supply)

E

Anchor bolt M10 (field supply)

s

Be sure to install the BC controllers at level. Installing obliquely may
cause a risk of drain leakage. Use a level to check the unit’s level. If it is
oblique, loosen the fixing nut and make an adjustment.

 Caution:

Be sure to install the unit body at level.

4. Connecting refrigerant pipes and drain pipes

4.1. Connecting refrigerant pipes

1. Connect the liquid and gas pipes of each indoor unit to the same end connec-

tion numbers as indicated on the indoor unit flare connection section of each
BC controller. If connected to wrong end connection numbers, there will be no
normal operation.

2. List indoor unit model names in the name plate on the BC controller control

box (for identification purposes), and BC controller end connection numbers
and address numbers in the name plate on the indoor unit side.

3. If the number of connected indoor units is less than the number of branch

holes, it does not matter which end connections you leave.
Seal unused end connections using flare nuts with end caps just as they were
capped when shipped from the factory. No end cap means refrigerant leakage.

4. When using branch pipes (CMY-Y102S-F), be sure to connect them at level.

5. Be sure to tighten the flare nuts using a double spanner. Otherwise the refrig-

erant may leak.

6. Be sure to use non-oxidative brazing where necessary. If you do not use non-

oxidative brazing, it may clog the pipes.

7. After completing pipe connection, support the pipes to prevent that load is

imparted to the BC controller’s end connections (particularly to the gas pipes
of indoor units).

 Warning :

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant (R407C or R22) specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-
ing particles, oils, moisture, or any other contaminant.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

Use Suniso 4GS or 3GS (small amount) refrigerator oil to coat the flare
and flange connection part. (For models using R22)

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections. (For models using R407C)

- The refrigerant used in the unit is highly hygroscopic and mixes with water

and will degrade the refrigerator oil.

Содержание CMB-P-V-F

Страница 1: ...etto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado...

Страница 2: ...me A CMB P104V F 648 CMB P105V F 648 CMB P106V F 648 CMB P108V F 648 CMB P1010V F 648 CMB P1013V F 1098 CMB P1016V F 1098 Length Between indoor and outdoor Unit m Item Piping portion Allowable value Total piping length A B a b Below 220 c d e Longest piping length A e Below 100 Below 90 1 Between outdoor and BC A Below 70 controllers Below 60 1 Between indoor and BC controllers e Below 30 Above ou...

Страница 3: ...for CITYMULTI Y Series CMY Y102S F Selection of refrigerant piping Piping size of A B sections in the above fig ure Select the size according to the total capacity of indoor units to be installed downstream Total capacity of indoor units Liquid line Gas line Below 80 ø9 52 ø15 88 81 to 160 ø12 7 ø19 05 E E E E E I E A B G 2 H 1D 50 63 100 140 3 C 4F A BC controller B Locally procured pipe ø28 56 C...

Страница 4: ...ng the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heater stove oven or other heat source it may generate noxious gases Do not reconstruct or change the...

Страница 5: ...tal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them If children play with a plastic bag which was not torn apart they face the risk of suffocation 1 5 Before starting the test run Caution Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main p...

Страница 6: ... If it is oblique loosen the fixing nut and make an adjustment Caution Be sure to install the unit body at level 4 Connecting refrigerant pipes and drain pipes 4 1 Connecting refrigerant pipes 1 Connect the liquid and gas pipes of each indoor unit to the same end connec tion numbers as indicated on the indoor unit flare connection section of each BC controller If connected to wrong end connection ...

Страница 7: ...with the main body itself Warning Do not mix anything other than the specified refrigerant R 22 or R407C into the refrigerating cycle when installing or moving Mixing air may cause the refrigerating cycle to get abnormally high temperature resulting in a burst Outdoor unit side Caution Cut the tip of the indoor unit piping remove the gas and then remove the brazed cap Fig 4 2 1 P 3 A Cut here B Re...

Страница 8: ...e outdoor unit However if this would result in it having the same ad dress as another outdoor unit set the address between 51 and 100 mak ing sure that it is different from the address of other controllers Please refer to the outdoor unit installation manual 7 Test run Before getting test run checked s After installing piping and wiring the indoor units and BC controllers check to see again that t...

Страница 9: ... электрошоку При установке и перемещении кондиционера на другой объект не заряжайте его другим хладагентом кроме хладагента R407С или R22 указанного на приборе При смешении другого хладагента или воздуха с первоначальным хладагентом может произойти сбой цикла охлаждения и прибор может быть поврежден Если кондиционер установлен в небольшом помещении необходимо принять меры для предотвращения концен...

Страница 10: ...может приветси к электрошоку Используйте сетевой кабель достаточной мощности напряжения Кабели слишком малой мощности могут прогореть вызвать перегрев и пожар Используйте прерыватель цепи и предохранитель указанной мощности Предохранитель или прерыватель цепи большей мощности или использование стального или медного провода могут вызвать общую поломку прибора или пожар Не мойте детали кондиционера ...

Страница 11: ...D Двойные гайки Приобретаются на месте E Анкерный болт М10 Приобретается на месте Поместите таким образом чтобы обеспечить достаточную легкость прокладки труб для воды хладагента и электропроводки Избегайте установки в местах подверженных скоплению притоку образованию или утечки возгорающихся и сернистых газов Помещайте таким образом чтобы обеспечить возможность прокладки дренажных труб под наклон...

Страница 12: ... мм Часть трубы Часть PURY 200 ø25 4 Пайка PURY P200 ø19 05 PURY 250 Пайка ø28 58 Пайка PURY P250 ø9 52 ø15 88 колокообразный колокообразный A К внешнему прибору B Концевое соединение C Регулятор BC D Переходник поставлен E Внутренний прибор F Менее 40 G Набор соединения труб название модели CMY R160 H H Труба ответвления наименование модели CMY Y102S F I До трех приборов на одно отверстие креплен...

Страница 13: ...а Обязательно обверните полиэтиленовую температуроустойчивую изоляцию свыше 10 мм толщиной на трубы жидкости и газа а также поместите ее в места соединения между внутренним прибором и изолирующим материалом таким образом чтобы не было зазора Неполная изоляция может привести к образованию конденсации Проявляйте особое вни мание в особенности при установке прибора в потолке Fig 4 3 1 P 3 A Изолирующ...

Страница 14: ...адрес в пределах от 51 до 100 При этом убедитесь что данный адрес отличается от адресов других регуляторов См Руководство по установке внешнего прибора 7 Выполнение испытания До проведения испытания s По завершении инсталляции трубных соединений и электросоединений внутренних устройств и регуляторов еще раз убедитесь в отсутствии утечки хладагентов и провисания кабелей питания и регулировки s Испо...

Страница 15: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: