LGH-35RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
0.98
145
350
97
160
–
–
–
32.5
SP3
0.56
72
263
73
90
–
–
–
28.0
SP2
0.28
35
175
49
40
–
–
–
20.0
SP1
0.13
13
88
24
10
–
–
–
18.0
Model
Electrical power supply
Ventilation mode
Fan speed
Running current (A)
Input power (W)
Airflow
(m
3
/h)
(L/s)
External static pressure (Pa)
Temperature exchange efficiency (%)
Enthalpy exchange
efficiency (%)
Heating
Cooling
Noise (dB)
Weight (kg)
Specific energy consumption class
SP4
0.98
140
350
97
160
80.0
71.5
71.0
32.0
SP3
0.54
70
263
73
90
82.5
74.0
73.0
28.0
SP2
0.26
31
175
49
40
86.0
78.5
78.0
20.0
SP1
0.12
11
88
24
10
88.5
83.5
82.0
17.0
LGH-25RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
0.48
63
250
69
85
–
–
–
27.5
SP3
0.29
35
188
52
48
–
–
–
23.0
SP2
0.16
17
125
35
21
–
–
–
20.0
SP1
0.11
9
63
17
5
–
–
–
17.0
SP4
0.48
62
250
69
85
79.0
69.5
68.0
27.0
SP3
0.28
33
188
52
48
80.0
72.0
70.0
22.0
SP2
0.16
16
125
35
21
82.0
76.0
74.5
20.0
SP1
0.10
7.5
63
17
5
86.0
83.0
83.0
17.0
LGH-15RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
0.41
52
150
42
95
–
–
–
29.0
20
A
23
A
30
–
SP3
0.25
28
113
31
54
–
–
–
24.0
SP2
0.15
14
75
21
24
–
–
–
19.0
SP1
0.10
8
38
10
6
–
–
–
18.0
SP4
0.40
49
150
42
95
80.0
73.0
71.0
28.0
SP3
0.24
28
113
31
54
81.0
75.5
74.5
24.0
SP2
0.15
14
75
21
24
83.0
78.0
78.0
19.0
SP1
0.10
7
38
10
6
84.0
79.0
79.0
17.0
LGH-80RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
1.97
340
800
222
150
–
–
–
36.0
SP3
0.86
151
600
167
85
–
–
–
30.0
SP2
0.40
64
400
111
38
–
–
–
23.0
SP1
0.15
20
200
56
10
–
–
–
18.0
48
Model
Electrical power supply
Ventilation mode
Fan speed
Running current (A)
Input power (W)
Airflow
(m
3
/h)
(L/s)
External static pressure (Pa)
Temperature exchange efficiency (%)
Enthalpy exchange
efficiency (%)
Heating
Cooling
Noise (dB)
Weight (kg)
SP4
1.82
335
800
222
150
79.0
71.0
70.0
34.5
SP3
0.83
151
600
167
85
82.5
73.5
72.5
30.0
SP2
0.36
60
400
111
38
84.0
78.0
78.0
23.0
SP1
0.15
18
200
56
10
85.0
81.0
81.0
18.0
LGH-65RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
1.72
262
650
181
120
–
–
–
35.5
SP3
0.86
131
488
135
68
–
–
–
29.0
SP2
0.38
47
325
90
30
–
–
–
22.0
SP1
0.16
17
163
45
8
–
–
–
18.0
38
SP4
1.65
252
650
181
120
77.0
68.5
66.0
34.5
SP3
0.90
131
488
135
68
81.0
71.0
69.5
29.0
SP2
0.39
49
325
90
30
84.0
76.0
74.0
22.0
SP1
0.15
15
163
45
8
86.0
82.0
81.0
18.0
LGH-50RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
1.15
173
500
139
120
–
–
–
35.0
SP3
0.59
81
375
104
68
–
–
–
29.0
SP2
0.27
35
250
69
30
–
–
–
20.0
SP1
0.13
14
125
35
8
–
–
–
18.0
SP4
1.15
165
500
139
120
78.0
69.0
66.5
34.0
SP3
0.59
78
375
104
68
81.0
71.0
68.0
28.0
SP2
0.26
32
250
69
30
83.5
75.0
72.5
19.0
SP1
0.13
12
125
35
8
87.0
82.5
82.0
18.0
33
LGH-200RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
4.54
853
2000
556
150
–
–
–
41.0
SP3
2.06
372
1500
417
84
–
–
–
36.0
SP2
0.87
150
1000
278
38
–
–
–
27.0
SP1
0.35
49
500
139
10
–
–
–
19.0
110
Model
Electrical power supply
Ventilation mode
Fan speed
Running current (A)
Input power (W)
Airflow
(m
3
/h)
(L/s)
External static pressure (Pa)
Temperature exchange efficiency (%)
Enthalpy exchange
efficiency (%)
Heating
Cooling
Noise (dB)
Weight (kg)
SP4
4.88
850
2000
556
150
80.0
72.5
71.0
40.0
SP3
2.20
400
1500
417
84
83.0
74.0
73.0
36.0
SP2
0.88
153
1000
278
38
86.5
78.0
77.0
28.0
SP1
0.33
42
500
139
10
89.5
87.0
85.5
18.0
LGH-150RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
3.85
698
1500
417
175
–
–
–
40.5
SP3
1.78
311
1125
313
98
–
–
–
33.0
SP2
0.78
124
750
208
44
–
–
–
26.0
SP1
0.30
44
375
104
11
–
–
–
18.0
98
SP4
3.71
670
1500
417
175
80.0
72.0
70.5
39.0
SP3
1.75
311
1125
313
98
82.5
73.5
72.5
32.0
SP2
0.70
123
750
208
44
84.0
78.0
78.0
24.0
SP1
0.29
38
375
104
11
85.0
81.0
81.0
18.0
LGH-100RVX-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
2.50
420
1000
278
170
–
–
–
38.0
SP3
1.20
200
750
208
96
–
–
–
32.0
SP2
0.51
75
500
139
43
–
–
–
24.0
SP1
0.19
23
250
69
11
–
–
–
18.0
SP4
2.50
420
1000
278
170
80.0
72.5
71.0
37.0
SP3
1.20
200
750
208
96
83.0
74.0
73.0
31.0
SP2
0.50
75
500
139
43
86.5
78.0
77.0
23.0
SP1
0.17
21
250
69
11
89.5
87.0
85.5
18.0
54
LGH-250RVXT-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
6.90
1298
2500
694
175
100
–
–
–
44.0
SP3
3.10
587
1875
521
98
56
–
–
–
38.5
SP2
1.30
212
1250
347
44
25
–
–
–
31.0
SP1
0.49
69
625
174
11
6
–
–
–
22.5
Model
Electrical power supply
Ventilation mode
Fan speed
Running current (A)
Input power (W)
Airflow
(m
3
/h)
(L/s)
Supply
Return
External static pressure (Pa)
Temperature exchange efficiency (%)
Enthalpy exchange
efficiency (%)
Heating
Cooling
Weight (kg)
SP4
7.60
1446
2500
694
175
100
77.0
68.0
65.5
43.0
SP3
3.60
687
1875
521
98
56
79.0
71.5
69.0
39.0
SP2
1.40
244
1250
347
44
25
80.5
74.0
71.5
32.0
SP1
0.57
82
625
174
11
6
82.5
79.0
76.5
24.0
LGH-200RVXT-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
5.00
916
2000
556
175
100
–
–
–
40.5
SP3
2.20
407
1500
417
98
56
–
–
–
34.5
SP2
0.85
150
1000
278
44
25
–
–
–
27.0
SP1
0.34
45
500
139
11
6
–
–
–
20.5
159
198
SP4
5.40
1000
2000
556
175
100
80.0
72.5
70.0
39.5
SP3
2.70
494
1500
417
98
56
81.0
73.5
71.0
35.5
SP2
1.10
197
1000
278
44
25
82.5
77.0
74.5
28.0
SP1
0.39
56
500
139
11
6
84.0
83.0
80.5
22.0
LGH-150RVXT-E
220-240V/50Hz, 220V/60Hz
Heat recovery mode
Bypass mode
SP4
3.40
625
1500
417
175
100
–
–
–
39.0
SP3
1.80
334
1125
313
98
56
–
–
–
33.0
SP2
0.77
134
750
208
44
25
–
–
–
26.5
SP1
0.31
37
375
104
11
6
–
–
–
20.5
SP4
4.30
792
1500
417
175
100
80.0
70.0
69.0
39.5
SP3
2.40
421
1125
313
98
56
80.5
71.0
70.0
35.5
SP2
1.10
176
750
208
44
25
81.0
73.0
72.0
29.5
SP1
0.36
48
375
104
11
6
81.5
75.0
74.0
22.0
156
GUF-50RD4
Model
Electrical power supply
Ventilation mode
Fan speed
Running current (A)
Input power (W)
Airflow
(m
3
/h)
(L/s)
External static pressure (Pa)
Temperature exchange efficiency (%)
Enthalpy exchange
efficiency (%)
Heating
Humidifying
Humidifying capacity (kg/h)
Water supply pressure
Cooling
Cooling capacity (kW)
Heating capacity (kW)
Capacity equivalent to the indoor unit
Humidifier
Noise (dB)
(Measured at 1.5m under the center of the unit)
Weight (kg)
GUF-100RD4
220-240V/50Hz
Heat recovery mode
Bypass mode
High
1.15
235-265
500
139
140
77.5
68
65
33.5-34.5
High
1.15
235-265
500
139
140
–
–
–
35-36
5.57 (1.94)
6.21 (2.04)
P32
–
–
–
48
Low
0.70
150-165
400
111
90
80
71
67
29.5-30.5
Low
0.70
150-165
400
111
90
–
–
–
29.5-30.5
220-240V/50Hz
Heat recovery mode
Bypass mode
High
2.20
480-505
1000
278
140
79.5
71
69
38-39
High
2.25
490-515
1000
278
140
–
–
–
38-39
11.44 (4.12)
12.56 (4.26)
P63
–
–
–
82
Low
1.73
370-395
800
222
90
81.5
74
71
34-35
Low
1.77
385-410
800
222
90
–
–
–
35-36
(Measured at 1.5m under the center
of the unit in an anechoic chamber)
(Measured at 1.5m under the center
of the unit in an anechoic chamber)
(Measured at 1.5m under the center
of the unit in an anechoic chamber)
Noise (dB)
(Measured at 1.5m under the center
of the unit in an anechoic chamber)
• LGH-RVX Series
• LGH-RVXT Series
• GUF Series
For LGH-RVX and LGH-RVXT Series
*The running current, the input power, the efficiency and the noise are based on the rating airflow, 230V/50Hz, and 220V/60Hz.
*Figures in the chart is measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.
For GUF Series
*Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27°C DB/19°C WB Outdoor: 35°C DB/24°C WB
Heating: Indoor: 20°C DB/13.8°C WB Outdoor: 7°C DB/6°C WB
*The figures in ( ) indicates heat recoverying capacity of heat exchange core.
*Figures in the chart is measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.
185
CHARACTERISTIC CURVES
VRF
Y-Series
VRF
Lineup
VRF
R2-Series
VRF
Zubadan
VRF
WY-Series
VRF
WR2-Series
VRF
S-Series
VRF
Indoor Units
Ventilation
Systems
Technologies and Functions
Remote Controller
Hot Water Solution
VRF
BC Controllers
VRF
S-Series
Содержание City Multi R2 Series
Страница 1: ...CM20AN E NZ VRF City Multi Product Catalogue ...
Страница 101: ...BC Controllers 101 ...
Страница 112: ...Indoor Units VRF 112 ...
Страница 114: ...Ceiling Cassette Type 4 Way Airflow Type 114 ...
Страница 122: ...Ceiling Cassette Type 2 Way Airflow Type 122 ...
Страница 128: ...Ceiling Concealed Type 128 ...
Страница 150: ...Wall Mounted Type 150 ...
Страница 154: ...Floor Standing Type 154 ...
Страница 181: ...Ventilation Systems 181 ...
Страница 190: ...Remote Controllers 190 ...