background image

19

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

SL

HG

PO

GB

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
i.

When the centralized remote controller is connected to the system, set centralized control switches (SW2-1) on control boards in all outdoor units (OC, OS) to “ON”.

*1 OC, OS1, and OS2 of the outdoor units in the same refrigerant system are automatically identified. They are identified as OC, OS1, and OS2 in descending order of

capacity (If the capacity is the same, they are identified in the ascending order of their address number).

<Permissible Lengths>

1

M-NET Remote controller

Max length via outdoor units: L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

3

+L

5

 and L

1

+L

2

+L

6

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length: L

and L

3

+L

4

 and L

3

+L

5

 and L

6

 and L

2

+L

6

  

=

 200 m (1.25 mm

2

 or more)

Remote controller cable length:

r

1

r

2

r

3

r

4

  

=

 10 m (0.3 to 1.25 mm

2

)

If the length exceeds 10 m, use a 1.25 mm

2

 shielded wire.  The length of this section (L

8

) should be included in the calculation of the

maximum length and overall length.

2

MA Remote controller

Max length via outdoor unit (M-NET cable): L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

6

 

=

 500 m (1.25 mm

2

 or more)

Max transmission cable length (M-NET cable): L

and L

3

+L

4

 and L

6

 and L

2

+L

6

  

=

 200 m (1.25 mm

or more)

Remote controller cable length:

c

1

+

c

2

 and 

c

1

+

c

2

+

c

3

+

c

4  

=

 200 m (0.3 to 1.25 mm

2

)

3

Transmission booster

Max transmission cable length (M-NET cable):

1

 L

1

+L

2

+L

3

+L

5

+L

6

 

=

 200 m (1.25 mm

2

)

2

 L

1

+L

2

+L

3

+L

5

+L

7

 

=

 200 m (1.25 mm

2

)

3

 L

1

+L

2

+L

4

 

=

 200 m (1.25 mm

2

)

4

 L

6

+L

5

+L

3

+L

4

, L

4

+L

3

+L

5

+L

7

 

=

 200 m (1.25 mm

2

)

Unit

Range

Setting Method

Indoor unit (Main)

01 to 50

Use the most recent address within the same group of  indoor units

Indoor unit (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)

Outdoor Unit (OC, OS)

51 to 100

Set the addresses of the outdoor units in the same refrigerant system in the order of sequential number. OC, OS1, and
OS2 are automatically identified. (*1)

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are

necessary.)

<Examples of transmission cable wiring>

[Fig. 11.3.1] M-NET Remote Controller (P.8)

*1:

When the power supply unit is not connected to the transmission line for centralized control, disconnect the male power supply connector (CN41) from ONE
outdoor unit in the system and connect it to CN40.

*2:

If a system controller is used, set SW2-1 on all of the outdoor units to ON.

[Fig. 11.3.2] MA Remote Controller (P.9)

<A> Change the jumper connector from CN41 to CN40

<B> SW2-1:ON

<C> Keep the jumper connector on CN41

A

Group 1

B

Group 3

 

C

Group 5

D

Shielded wire

E

Sub remote controller

(  ) Address

[Fig. 11.3.3] Combination of outdoor units and transmission booster unit (P.9)

<Wiring Method and Address Settings>

a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, OC-OS, OS-OS, and IC-IC wiring

intervals.

b. Use feed wiring to connect terminals M1 and M2 and the earth terminal 

 on the transmission line terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2

and terminal S on the transmission line block of the indoor unit (IC). For OC and OS, connect TB3 to TB3.

c.

Connect terminals 1 (M1) and 2 (M2) on the transmission line terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal
block on the remote controller (RC).

d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit in a different refrigerant system (OC). For OC and

OS in the same refrigerant system, connect TB7 to TB7.

e. When the power supply unit is not installed on the central control transmission line, change the jumper connector on the control board from CN41 to CN40 on only one

outdoor unit in the system.

f.

Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which the jumper connector was inserted into CN40 in the
step above to the earth terminal 

 in the electrical component box.

g. Set the address setting switch as follows.
*

To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.

2

Wiring examples

Controller name, symbol and allowable number of controllers.

Name

Code

Possible unit connections

Outdoor unit

Indoor unit
Remote controller
Other

Main unit
Sub unit
Indoor unit controller
Remote controller (*1)
Transmission booster unit

– (*2)
– (*2)
1 to 32 units per 1 OC (*1)
2 units maximum per group
0 to 1 unit per 1 OC (*1)

OC

OS1, OS2

IC

RC
RP

*1 A transmission booster (RP) may be required depending on the number of connected indoor unit controllers.
*2 OC, OS1, and OS2 of the outdoor units in the same refrigerant system are automatically identified. They are identified as OC, OS1, and OS2 in descending order of

capacity. (If the capacity is the same, they will be in ascending order of their address number.)

WT06215X01_en_e.p65

10.12.17, 13:54

19

Содержание City Multi PUHY-RP-YJM-B

Страница 1: ...новке до выполнения установки кондиционера MONTAJ ELKİTABI Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz PŘÍRUČKA K INSTALACI V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci NÁVOD NA INŠTALÁCIU Pre bezpečné a správne použitie si pred...

Страница 2: ... A Front B Unit height C Back D Air outlet guide Procured at the site A Front B Must be open C Wall height H 15 15 450 300 A A 100 450 50 50 A A A B B 500 H h h H 240 45 A D C 50 C 1000 30 450 300 C B B C A 100 450 100 B B C C A 450 100 C C B A A A B 450 450 15 C A A A 450 450 900 300 300 B B C C A 1000 900 300 B B C A mm 8m 8m 40 ...

Страница 3: ...First branch C Indoor unit D Cap E Outdoor twinning kit RP400 RP650 RP700 RP900 B E A A2 A1 A B C D e a b c d C C C C C unit 2 A unit 1 E A A2 A1 A unit 2 A unit 1 B a b c d e C D C C C C B A B C D e a b c d C C C C C A B A a b c d e C D C C C C A B B C D e a b c d C C C C C E A3 A4 A2 unit 3 A A A unit 2 unit 1 E A1 A E A3 A4 A2 A unit 3 A A A unit 2 unit 1 E A1 B a b c d e C D C C C C A Fig 8 1 ...

Страница 4: ...19 05 ø19 05 Ç Gas pipe ø34 93 ø34 93 ø34 93 ø34 93 ø34 93 Unit combination A A1 1 A2 1 A3 1 A4 9 2 9 1 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for unit 1 2 and 3 change make sure to use the appropriate pipe size 2 ø25 4 for R22 B C D mm a b c d e mm Ï Downstream unit model tota...

Страница 5: ... unit side from the twinning pipe exceeds 2 m ensure a trap gas pipe only within 2 m C Slope of twinning pipes 15 F G D Pipe connection example H I H J A Downward slope B Upward slope C Indoor unit D Trap gas pipe only E Within 2 m F Twinning pipe G Slope of the twinning pipe is at an angle within 15 to the ground H Pipes on site I Twinning kit J Straight run of pipe that is 500 mm or more ...

Страница 6: ...ø9 52 ODø19 05 IDø25 4 ODø28 58 IDø25 4 IDø12 7 ODø12 7 A Front pipe routing B Bottom pipe routing C Included with outdoor unit A Gas pipe field supply required B Liquid pipe field supply required C Shape B D A E C A B A Refrigerant service valve liquid side brazed type B Refrigerant service valve gas side brazed type A Shaft B Service port C Cap D Pinched connecting pipe severing portion E Pinche...

Страница 7: ...4 2 C A B D E Fig 10 4 1 B A D C E E E D A B A B A Inner wall concealed A B D C B Outer wall A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B A Liquid pipe B Gas pipe C Electric wire D Finishing tape E Insulator D F G B D Floor waterproofing E I B C Outer wall exposed F H D B G E Roof pipe shaft I A J 1m 1m F Penetrating portion on fire limit...

Страница 8: ...2S TB5 06 L 2 L1 101 RC 105 RC 103 RC 155 OC M1M2 M1M2 S TB7 TB3 CN40 52 OC r3 A B S System controller L3 L 6 L4 L 5 r 2 r 4 r 1 A B A B A B A B CN40 A Cable strap B Power source line C Transmission line 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to...

Страница 9: ...remote controller Address A Change the jumper connec tor from CN41 to CN40 1 B SW2 1 ON 2 C Keep the jumper connector on CN41 B SW2 1 ON 2 Fig 11 3 3 RC IC M1M2 S TB5 IC M1M2 S TB5 RP Ground A B A B A B S TB2 A B S TB3 L 4 r 1 r 1 M1 M2 TB3 M1 M2 TB3 M1 M2 M1M2 S TB3 TB7 M1M2 S TB7 M1M2 S TB7 OC 51 L 7 RC IC M1M2 S TB5 IC M1M2 S TB5 L6 L5 L3 L2 L1 OS1 52 OS2 53 To another refrigerant system Fig 11...

Страница 10: ...ot touch the heat exchanger fins Improper handling may result in injury If refrigerant gas leaks during installation work ventilate the room If the refrigerant gas comes into contact with a flame poisonous gases will be released Install the air conditioner according to this Installation Manual If the unit is installed improperly water leakage electric shock or fire may result Have all electric wor...

Страница 11: ...al regulation or standards The size of the wire and capacities of the switch for the main power supply are applicable if local regulations are not available Pay special attention to the place of installation such as a basement etc where refrigeration gas can accumulate since refrigeration is heavier than the air For outdoor units that allow fresh air intake to the indoor unit the instal lation sit...

Страница 12: ... 12 5 CWB 20 CWB Model Noise level 50 60Hz External static pressure Indoor units Total capacity Model Quantity Standard type Fresh air intake type PUHY RP200YJM B 56dB A 1 13 PUHY RP250YJM B 57dB A 1 16 PUHY RP300YJM B 59dB A 1 16 PUHY RP350YJM B 60dB A 1 20 PUHY RP400YSJM B 61dB A 1 20 PUHY RP450YSJM B 62dB A 1 20 PUHY RP500YSJM B 60dB A 1 20 PUHY RP550YSJM B 61dB A 1 20 PUHY RP600YSJM B 62dB A 1...

Страница 13: ... asterisk If there is a wall at both the front and the rear of the unit install up to 6 units consecutively in the side direction and provide a space of 1000 mm or more as inlet space passage space for each 6 units 7 Lifting method Fig 7 0 1 P 2 Use suspension ropes that will withstand the weight of the unit When moving the unit use a 4 point suspension and avoid giving impacts to the unit Do not ...

Страница 14: ...the branched sections are brazed Warning Do not use refrigerant other than the type indicated in the manuals pro vided with the unit and on the nameplate Doing so may cause the unit or pipes to burst or result in explosion or fire during use during repair or at the time of disposal of the unit It may also be in violation of applicable laws MITSUBISHI ELECTRIC CORPORATION cannot be held responsible...

Страница 15: ...r purge Always evacuate using a vacuum pump B Always insulate the piping properly Insufficient insulation will result in a de cline in heating cooling performance water drops from condensation and other such problems Refer to item 10 4 for thermal insulation of refrigerant piping C When connecting the refrigerant piping make sure the valve of the outdoor unit is completely closed the factory setti...

Страница 16: ...ve before heating the brazed section to keep the temperature of the valve from exceeding 120 C Direct the flame away from the wiring and metal sheets inside the unit to prevent heat damage At the conditions below Caution Do not vent R410A into the atmosphere R410A is a Fluorinated Greenhouse gas covered by the Kyoto Protocol with a Global Warming Potential GWP 1975 Refrigerant pipe connection This...

Страница 17: ...e the liquid refriger ant by turning the cylinder upside down as shown in Fig 10 3 3 If the cylinder has a syphon pipe like that shown in the picture on the right the liquid refriger ant can be charged with the cylinder standing upright Therefore give careful attention to the cylinder specifications If the unit should be charged with gas refrigerant replace all the refrigerant with new refrigerant...

Страница 18: ...arity 9 Group is set by operating the remote controller 11 2 Control box and connecting position of wiring 1 Outdoor unit 1 Remove the front panel of the control box by removing the 4 screws and push ing it up a little before pulling it out 2 Connect the indoor outdoor transmission line to the terminal block TB3 for the indoor outdoor transmission line If multiple outdoor units are connected in th...

Страница 19: ...connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON Fig 11 3 2 MA Remote Controller P 9 A Change the jumper connector from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on CN41 A Group 1 B Group 3 C Grou...

Страница 20: ...hed flexible cord design 245 IEC57 For example use wiring such as YZW 6 A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer Warning Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections If connections are not fixed firmly heating or fire may result Be sure to use the appropriate typ...

Страница 21: ... problem The LEV is slightly open to prevent refrigerant of the indoor unit that is not performing the heating operation from being liquefied This does not imply a problem Phenomenon Indoor unit does not perform cooling heating operation The auto vane rotates and begins to blow air horizontally Fan setting changes during heating Fan stops during heating operation Fan does not stop while operation ...

Страница 22: ... K HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT06215X01 This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive...

Отзывы: