background image

16

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

SL

HG

PO

GB

<Example>
Indoor 1: 125

A: ø15.88

40 m

a: ø9.52

10 m

2: 100

B: ø12.7

10 m

b: ø9.52

5 m

3: 40

C: ø12.7

15 m

c: ø6.35

10 m

4: 32

D: ø12.7

10 m

d: ø6.35

10 m

5: 63

e: ø9.52

10 m

The total length of each liquid line is as follows:
ø15.88: A = 40 = 40 m
ø12.7: B + C + D = 10 + 15 + 10 = 35 m
ø9.52: a + b + e = 10 + 5 + 10 = 25 m
ø6.35: c + d = 10 + 10 = 20 m
Therefore,
<Calculation example>
Additional refrigerant charge

= 40 

× 

0.2 + 35 

×

 0.12 + 25 

×

 0.06 + 20 

×

 0.024 + 3.5 = 17.7 kg

Value of  

α

Total capacity of connecting indoor units

α

Models

~

80

2.0 kg

Models

81 ~ 160

2.5 kg

Models

161 ~ 330

3.0 kg

Models

331 ~ 390

3.5 kg

Models

391 ~ 480

4.5 kg

Models

481 ~ 630

5.0 kg

Models

631 ~ 710

6.0 kg

Models

711 ~ 800

8.0 kg

Models

801 ~ 890

9.0 kg

Models

891 ~1070

10.0 kg

Models 1071 ~

12.0 kg

10.2. Precautions concerning piping connec-

tion and valve operation

Conduct piping connection and valve operation accurately and carefully.

Removing the pinched connecting pipe
When shipped, a pinched connecting pipe is attached to the on-site liquid and
gas valves to prevent gas leakage.
Take the following steps 

1

 through 

4

 to remove the pinched connecting pipe

before connecting refrigerant pipes to the outdoor unit.

1

Check that the refrigerant service valve is fully closed (turned clockwise all
the way).

2

Connect a charging hose to the service port on the liquid/gas refrigerant
service valve, and extract the gas in the pipe section between the refriger-
ant service valve and the pinched connecting pipe (Tightening torque
12 N·m).

3

After vacuuming gas from the pinched connecting pipe, sever the pinched
connecting pipe at the location shown in [Fig.10.2.1] and drain the
refrigerant.

4

After completing 

2

 and 

3

 heat the brazed section to remove the pinched

connecting pipe.

[Fig. 10.2.1] (P.6)

<A> Refrigerant service valve (liquid side/brazed type)

<B> Refrigerant service valve (gas side/brazed type)

A

Shaft
Fully closed at the factory, when connecting the piping, and when vacuuming.
Open fully after these operations are completed.
<When opening>
• Turn the shaft counterclockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
<When closing>
• Turn the shaft clockwise with a hexagonal wrench.
• Turn around the shaft until it stops.

B

Service port
Available for gas venting of the pinched connecting pipe, or vacuuming in the
refrigerant pipes on the site.
(Tightening torque 12 N·m)

C

Cap
Remove the cap before operating the shaft. Be sure to return it to the original
position after completing the operation.

D

Pinched connecting pipe severing portion

E

Pinched connecting pipe brazing portion

 Warning:

The section of the pipe on the unit between the two refrigerant service
valves is filled with gas. Extract the gas in the above-mentioned pipe
section before heating the brazed section to remove the refrigerant service
valve connecting pipe.
- If the brazed section is heated without first extracting the gas, the pipe may

burst or the connecting pipe may blow off causing serious injury.

 Caution:

Place a wet towel on the refrigerant service valve before heating the brazed
section to keep the temperature of the valve from exceeding 120 ˚C.

Direct the flame away from the wiring and metal sheets inside the unit to
prevent heat damage.

At the
conditions
below:

 Caution:

Do not vent R410A into the atmosphere.

R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol,
with a Global Warming Potential (GWP) = 1975.

Refrigerant pipe connection
This product includes connecting pipes for front piping and bottom post-piping.
(Refer to [Fig.10.2.2])
Check the liquid/gas piping dimensions before connecting the refrigerant pipe.
Refer to item 9.2 Refrigerant piping system for piping dimensions.
Make sure that the refrigerant pipe is not touching other refrigerants pipes, unit
panels, or base plates.
Be sure to use non-oxidative brazing when connecting pipes.

<Refrigerant piping connection examples>

[Fig.10.2.2] (P.6)

<A> Front pipe routing

<B> Bottom pipe routing

<C> Included with outdoor unit

A

Gas pipe (field supply required)

B

Liquid pipe (field supply required)

C

Shape

Front pipe routing

Bottom pipe routing

*1 In the case the unit is used in combination with other outdoor units.
*2 In the case of R22.

Satisfy the minimum insertion depth in the table below when expanding on-site
piping.

Pipe diameter (mm)

Minimum insertion depth (mm)

5 or more  less than 8

6

8 or more  less than 12

7

12 or more  less than 16

8

16 or more  less than 25

10

25 or more  less than 35

12

35 or more  less than 45

14

After evacuation and refrigerant charging, ensure that the handle is fully open.
If operating with the valve closed, abnormal pressure will be imparted to the
high- or low-pressure side of the refrigerant circuit, giving damage to the com-
pressor, four-way valve, etc.

Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing
piping connection work.

Liquid side

Gas side

RP200,RP250,RP300

RP200 *1,RP250 *1

RP350

RP350 *1

RP200,RP250,
RP300,RP350 *1
RP200 *1

RP200 *2
RP250 *1,RP300 *1

RP350

Use the included connecting pipe 

2

 and

8

 to connect.

Use the included connecting pipe 

8

 to con-

nect.
Use the included connecting pipe 

3

 and

9

 to connect.

Use the included connecting pipe 

9

 to con-

nect.
Use the included elbow 

1

 and connecting

pipe 

6

 to connect.

Use the included elbow 

1

 and connecting

pipe 

4

 to connect.

Use the included elbow 

1

 to connect.

Use the included elbow 

1

 and connecting

pipe 

5

 to connect.

Use the included elbow 

1

 and connecting

pipe 

7

 to connect.

Liquid side

Gas side

RP200,RP250,RP300

RP200 *1,RP250 *1

RP350

RP350 *1

RP200,RP250,
RP300,RP350 *1
RP200 *1

RP200 *2

RP250 *1,RP300 *1

RP350

Use the included connecting pipe 

2

 to con-

nect.
Expand the liquid side on-site piping (ID
ø9.52)
and connect to the refrigerant service valve
piping.
Use the included connecting pipe 

3

 to con-

nect.
Expand the liquid side on-site piping (ID
ø12.7)
and connect to the refrigerant service valve
piping.
Use the included connecting pipe 

6

 to con-

nect.
Use the included connecting pipe 

4

 to con-

nect.
Expand the gas side on-site piping (ID
ø25.4)
and connect to the refrigerant service valve
piping.
Use the included connecting pipe 

5

 to con-

nect.
Use the included connecting pipe 

7

 to con-

nect.

WT06215X01_en_e.p65

10.12.17, 13:54

16

Содержание City Multi PUHY-RP-YJM-B

Страница 1: ...новке до выполнения установки кондиционера MONTAJ ELKİTABI Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz PŘÍRUČKA K INSTALACI V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci NÁVOD NA INŠTALÁCIU Pre bezpečné a správne použitie si pred...

Страница 2: ... A Front B Unit height C Back D Air outlet guide Procured at the site A Front B Must be open C Wall height H 15 15 450 300 A A 100 450 50 50 A A A B B 500 H h h H 240 45 A D C 50 C 1000 30 450 300 C B B C A 100 450 100 B B C C A 450 100 C C B A A A B 450 450 15 C A A A 450 450 900 300 300 B B C C A 1000 900 300 B B C A mm 8m 8m 40 ...

Страница 3: ...First branch C Indoor unit D Cap E Outdoor twinning kit RP400 RP650 RP700 RP900 B E A A2 A1 A B C D e a b c d C C C C C unit 2 A unit 1 E A A2 A1 A unit 2 A unit 1 B a b c d e C D C C C C B A B C D e a b c d C C C C C A B A a b c d e C D C C C C A B B C D e a b c d C C C C C E A3 A4 A2 unit 3 A A A unit 2 unit 1 E A1 A E A3 A4 A2 A unit 3 A A A unit 2 unit 1 E A1 B a b c d e C D C C C C A Fig 8 1 ...

Страница 4: ...19 05 ø19 05 Ç Gas pipe ø34 93 ø34 93 ø34 93 ø34 93 ø34 93 Unit combination A A1 1 A2 1 A3 1 A4 9 2 9 1 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for unit 1 2 and 3 change make sure to use the appropriate pipe size 2 ø25 4 for R22 B C D mm a b c d e mm Ï Downstream unit model tota...

Страница 5: ... unit side from the twinning pipe exceeds 2 m ensure a trap gas pipe only within 2 m C Slope of twinning pipes 15 F G D Pipe connection example H I H J A Downward slope B Upward slope C Indoor unit D Trap gas pipe only E Within 2 m F Twinning pipe G Slope of the twinning pipe is at an angle within 15 to the ground H Pipes on site I Twinning kit J Straight run of pipe that is 500 mm or more ...

Страница 6: ...ø9 52 ODø19 05 IDø25 4 ODø28 58 IDø25 4 IDø12 7 ODø12 7 A Front pipe routing B Bottom pipe routing C Included with outdoor unit A Gas pipe field supply required B Liquid pipe field supply required C Shape B D A E C A B A Refrigerant service valve liquid side brazed type B Refrigerant service valve gas side brazed type A Shaft B Service port C Cap D Pinched connecting pipe severing portion E Pinche...

Страница 7: ...4 2 C A B D E Fig 10 4 1 B A D C E E E D A B A B A Inner wall concealed A B D C B Outer wall A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B A Liquid pipe B Gas pipe C Electric wire D Finishing tape E Insulator D F G B D Floor waterproofing E I B C Outer wall exposed F H D B G E Roof pipe shaft I A J 1m 1m F Penetrating portion on fire limit...

Страница 8: ...2S TB5 06 L 2 L1 101 RC 105 RC 103 RC 155 OC M1M2 M1M2 S TB7 TB3 CN40 52 OC r3 A B S System controller L3 L 6 L4 L 5 r 2 r 4 r 1 A B A B A B A B CN40 A Cable strap B Power source line C Transmission line 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to...

Страница 9: ...remote controller Address A Change the jumper connec tor from CN41 to CN40 1 B SW2 1 ON 2 C Keep the jumper connector on CN41 B SW2 1 ON 2 Fig 11 3 3 RC IC M1M2 S TB5 IC M1M2 S TB5 RP Ground A B A B A B S TB2 A B S TB3 L 4 r 1 r 1 M1 M2 TB3 M1 M2 TB3 M1 M2 M1M2 S TB3 TB7 M1M2 S TB7 M1M2 S TB7 OC 51 L 7 RC IC M1M2 S TB5 IC M1M2 S TB5 L6 L5 L3 L2 L1 OS1 52 OS2 53 To another refrigerant system Fig 11...

Страница 10: ...ot touch the heat exchanger fins Improper handling may result in injury If refrigerant gas leaks during installation work ventilate the room If the refrigerant gas comes into contact with a flame poisonous gases will be released Install the air conditioner according to this Installation Manual If the unit is installed improperly water leakage electric shock or fire may result Have all electric wor...

Страница 11: ...al regulation or standards The size of the wire and capacities of the switch for the main power supply are applicable if local regulations are not available Pay special attention to the place of installation such as a basement etc where refrigeration gas can accumulate since refrigeration is heavier than the air For outdoor units that allow fresh air intake to the indoor unit the instal lation sit...

Страница 12: ... 12 5 CWB 20 CWB Model Noise level 50 60Hz External static pressure Indoor units Total capacity Model Quantity Standard type Fresh air intake type PUHY RP200YJM B 56dB A 1 13 PUHY RP250YJM B 57dB A 1 16 PUHY RP300YJM B 59dB A 1 16 PUHY RP350YJM B 60dB A 1 20 PUHY RP400YSJM B 61dB A 1 20 PUHY RP450YSJM B 62dB A 1 20 PUHY RP500YSJM B 60dB A 1 20 PUHY RP550YSJM B 61dB A 1 20 PUHY RP600YSJM B 62dB A 1...

Страница 13: ... asterisk If there is a wall at both the front and the rear of the unit install up to 6 units consecutively in the side direction and provide a space of 1000 mm or more as inlet space passage space for each 6 units 7 Lifting method Fig 7 0 1 P 2 Use suspension ropes that will withstand the weight of the unit When moving the unit use a 4 point suspension and avoid giving impacts to the unit Do not ...

Страница 14: ...the branched sections are brazed Warning Do not use refrigerant other than the type indicated in the manuals pro vided with the unit and on the nameplate Doing so may cause the unit or pipes to burst or result in explosion or fire during use during repair or at the time of disposal of the unit It may also be in violation of applicable laws MITSUBISHI ELECTRIC CORPORATION cannot be held responsible...

Страница 15: ...r purge Always evacuate using a vacuum pump B Always insulate the piping properly Insufficient insulation will result in a de cline in heating cooling performance water drops from condensation and other such problems Refer to item 10 4 for thermal insulation of refrigerant piping C When connecting the refrigerant piping make sure the valve of the outdoor unit is completely closed the factory setti...

Страница 16: ...ve before heating the brazed section to keep the temperature of the valve from exceeding 120 C Direct the flame away from the wiring and metal sheets inside the unit to prevent heat damage At the conditions below Caution Do not vent R410A into the atmosphere R410A is a Fluorinated Greenhouse gas covered by the Kyoto Protocol with a Global Warming Potential GWP 1975 Refrigerant pipe connection This...

Страница 17: ...e the liquid refriger ant by turning the cylinder upside down as shown in Fig 10 3 3 If the cylinder has a syphon pipe like that shown in the picture on the right the liquid refriger ant can be charged with the cylinder standing upright Therefore give careful attention to the cylinder specifications If the unit should be charged with gas refrigerant replace all the refrigerant with new refrigerant...

Страница 18: ...arity 9 Group is set by operating the remote controller 11 2 Control box and connecting position of wiring 1 Outdoor unit 1 Remove the front panel of the control box by removing the 4 screws and push ing it up a little before pulling it out 2 Connect the indoor outdoor transmission line to the terminal block TB3 for the indoor outdoor transmission line If multiple outdoor units are connected in th...

Страница 19: ...connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON Fig 11 3 2 MA Remote Controller P 9 A Change the jumper connector from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on CN41 A Group 1 B Group 3 C Grou...

Страница 20: ...hed flexible cord design 245 IEC57 For example use wiring such as YZW 6 A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer Warning Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections If connections are not fixed firmly heating or fire may result Be sure to use the appropriate typ...

Страница 21: ... problem The LEV is slightly open to prevent refrigerant of the indoor unit that is not performing the heating operation from being liquefied This does not imply a problem Phenomenon Indoor unit does not perform cooling heating operation The auto vane rotates and begins to blow air horizontally Fan setting changes during heating Fan stops during heating operation Fan does not stop while operation ...

Страница 22: ... K HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT06215X01 This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive...

Отзывы: