background image

7

GB

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

SL

HG

PO

8

For indoor and outdoor branching, be sure to use the following twinning pipe
sets in the table 1 (sold separately).

9

Use an adapter if a specified refrigerant pipe has a different diameter from that
of a branching pipe.

0

Braze only with non-oxide brazing material for piping. Failure to do so
may damage the compressor. Be sure to perform the non-oxidation braz-
ing with a nitrogen purge.

Do not use any commercially available anti-oxidizing agent since it may
cause pipe corrosion and degrading of the refrigerant oil.

Please contact Mitsubishi Electric for more details.

(Refer to item 10.2. for details of the piping connection and valve operation)

A

Always insulate the piping properly.  Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation  forming
and other such problems. (Refer to item 10.4 for thermal insulation of refriger-
ant piping.)

B

When connecting the refrigerant piping, make sure the valve of the outdoor
unit is completely closed (the factory setting). Do not operate it until the refrig-
erant piping for the outdoor and indoor units has been connected, a refrigerant
leakage test has been performed, and the evacuation process has been com-
pleted.

C

Never use refrigerant to perform an air purge.  

Always evacuate using a

vacuum pump.

D

Be sure to charge the system using liquid refrigerant.

E

Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. When serv-
icing, always check the notes concerning pipe length and amount of additional
refrigerant at both locations, the refrigerant volume calculation table on the
back of the service panel and the additional refrigerant section on the labels
for the combined number of indoor units. (Refer to item 9.2. for detailed infor-
mation on refrigerant piping system.)

9. Refrigerant piping installation

The pipe is connected via a terminal-branch type connection in which refrigerant
piping from the outdoor unit is branched at the terminal and is connected to each
of the indoor units.
The method of pipe connection is as follows: flare connection for the indoor units,
gas pipes and liquid pipes for outdoor units, brazed connection. Note that the branched
sections are brazed.

 Warning:

Always use extreme care to prevent the refrigerant gas from leaking while
using fire or flame. If the refrigerant gas comes in to contact with a flame
from any source, such as a gas stove, it breaks down and generates a poi-
sonous gas which can cause gas poisoning. Never weld in an unventilated
room. Always conduct an inspection for gas leakage after installation of the
refrigerant piping has been completed.

9.1. Caution

This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes. (Refer to the table on the right.)

1

Use the following materials for refrigeration piping.

Material: Use copper alloy seamless pipes made of phosphorus deoxi-
dized copper. Ensure the inner and outer surfaces of the pipes are clean
and free from hazardous sulfur, oxide, dusts, shaving particles, oils, and
moisture (contamination).

Size: Refer to item 9.2. for detailed information on refrigerant piping system.

2

Always observe the restrictions on the refrigerant piping (such as rated length,
height difference, and piping diameter) to prevent equipment failure or a de-
cline in heating/cooling performance.

3

Branching cannot be made after header branching (corresponding parts are
marked with   in the diagram below).

To the outdoor unit

To the outdoor unit

CAP

4

Do not install outdoor unit piping when it is raining.

5

Commercially available piping often contains dust and other materials.  Always
blow it clean with a dry inert gas.

6

Use care to prevent dust, water or other contaminants from entering the piping
during installation.

7

Reduce the number of bending portions as much as possible, and make bend-
ing radius as big as possible.

Note:

1. Height of frame base for snow damage prevention (H) shall be twice as high as

expected snowfall. Width of frame base shall not exceed that of the unit. The
frame base shall be made of angle steel, etc., and designed so that snow and
wind slip through the structure. (If frame base is too wide, snow will be
accumulated on it.)

2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.

Material : Galvanized steel plate 1.2T
Painting : Overall painting with polyester powder
Color

: Munsell 5Y8/1 (same as that of unit)

4. When the unit is used in a cold region and the heating operation is continu-

ously performed for a long time when the outside air temperature is below
freezing, install a heater to the unit base or take other appropriate measures to
prevent water from freezing on the base.

 Warning:

Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.

Have installation work in order to protect against strong winds and earthquakes.
Any installation deficiency may cause unit to fall down, resulting in a personal injury.

When building the foundation, give full attention to the floor strength, drain water dis-
posal <during operation, drain water flows out of the unit>, and piping and wiring routes.

Precautions when routing the pipes and wires below the unit

When routing the pipes and wires below the unit, be sure that the foundation and
base work do not block the base through-holes. Also make sure the foundation is
at least 100 mm [3-15/16 in] high so that the piping can pass under the unit.

[Fig. 8.1.2]

Outlet

Inlet

Inlet

Inlet

H

In abnormally harsh environments such as cold and/or windy areas, sufficient
countermeasures to guard against excessive wind and snow should be taken
to ensure the unit's correct operation. When the unit is expected to operate in
cooling mode in conditions under 10°C [50°F], in snowy areas, in environments
subject to strong winds or rain, install air inlet and outlet ducting as shown in
[Fig. 8.1.2].

Size (mm)

Size (inch)

Radial thickness

Radial thickness

Pipe type

(mm)

(mil)

ø6.35

ø1/4"

0.8

32

Type-O

ø9.52

ø3/8"

0.8

32

Type-O

ø12.7

ø1/2"

0.8

32

Type-O

ø15.88

ø5/8"

1.0

40

Type-O

*ø19.05

ø3/4"

1.2

48

Type-O

*ø19.05

ø3/4"

1.0

40

Type-1/2H or H

ø22.2

ø7/8"

1.0

40

Type-1/2H or H

ø25.4

ø1"

1.0

40

Type-1/2H or H

ø28.58

ø1-1/8"

1.0

40

Type-1/2H or H

ø31.75

ø1-1/4"

1.1

44

Type-1/2H or H

ø34.93

ø1-3/8"

1.2

48

Type-1/2H or H

ø41.28

ø1-5/8"

1.4

56

Type-1/2H or H

Copper pipe size and radial thickness for R410A CITY MULTI.

* Both pipe types can be used for pipe size ø19.05 (3/4 inch) for R410A air condi-

tioner.

Содержание City Multi PUHY-P168TSJMU-A

Страница 1: ...ATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Страница 2: ... and fire may result Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mi...

Страница 3: ...ping made of phosphorus deoxidized copper and cop per alloy seamless pipes and tubes In addition be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur oxides dust dirt shaving particles oils moisture or any other contami nant Contaminants on the inside of the refrigerant piping may cause the refriger ant oil to deteriorate Store the piping to be used during...

Страница 4: ...BS PUHY P72YJMU A BS PUHY P96YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P144YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P96YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P144YJMU A BS PUHY P144YJMU A BS PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P144YJMU A BS PUHY P72YJMU A BS PUHY P96YJMU A BS PUHY P96YJMU A BS PUHY P168 to P360YSJMU ...

Страница 5: ...900 300 300 B B C C A 35 7 16 11 13 16 11 13 16 1000 900 300 B B C A 11 13 16 35 7 16 39 3 8 A Front B Must be open C Wall height H When multiple units are installed adjacent to each other secure enough space to allow for air circulation and walkway between groups of units as shown in the figures At least two sides must be left open As with the single installation add the height that exceeds the h...

Страница 6: ... the unit is covered The projecting length of the anchor bolt should be less than 30 mm 1 3 16 in Post installed anchor bolts i e bolts not firmly cemented into the base are not compatible with this product unless fixing brackets are first mounted on the four locations 7 Transporting the unit Fig 7 0 1 1 P72 3 P120 P144 Use suspension ropes that will withstand the weight of the unit When moving th...

Страница 7: ...ant piping system 2 Always observe the restrictions on the refrigerant piping such as rated length height difference and piping diameter to prevent equipment failure or a de cline in heating cooling performance 3 Branching cannot be made after header branching corresponding parts are marked with in the diagram below To the outdoor unit To the outdoor unit CAP 4 Do not install outdoor unit piping w...

Страница 8: ... to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate Do not use special detergents for washing piping Lower st...

Страница 9: ...espond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for unit 1 2 and 3 change make sure to use the appropriate pipe size Precautions for outdoor unit combinations Refer to Fig 9 2 2 for the positioning of twinning pipes Fig 9 2 2 A Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards towards the twinning pipes B C F Do...

Страница 10: ...efrigerant line Use the table below as a guide for calculating the amount of additional charg ing and then charge the system accordingly If the calculation results in a fraction of less than 0 1 kg 4 oz round up to the next 0 1 kg 4 oz For example if the result of the calculation was 12 38 kg 437 oz round the result up to 12 4 kg 438 oz Additional Charge Additional refrigerant charge kg oz 10 Addi...

Страница 11: ...rn the shaft clockwise Turn around the shaft until it stops C Stopper pin Prevents the shaft from turning 90 or more D Service port Available for gas venting of the pinched connecting pipe or vacuuming in the refrigerant pipes on the site E Cap Remove the cap before operating the shaft Be sure to return it to the original position after completing the operation F Pinched connecting pipe severing p...

Страница 12: ...4 to connect Use the included connecting pipe 3 to connect Expand the liquid side on site piping ID ø12 7 mm 1 2 in and connect to the refrigerant service valve piping Use the included connecting pipe 5 to connect Use the included connecting pipe 6 to connect Use the included connecting pipe 7 to connect Expand the gas side on site piping ID ø28 58 mm 1 1 8 in and connect to the refrigerant servic...

Страница 13: ...nt I Valve J Valve K R410A cylinder L Scale M Vacuum pump N To indoor unit O Outdoor unit 2 Evacuation Evacuate with the valve of the outdoor unit closed and evacuate both the connection piping and the indoor unit from the service port provided on the valve of the outdoor unit using a vacuum pump Always evacuate from the service port of both liquid pipe and gas pipe After the vacuum reaches 650 Pa...

Страница 14: ...2 in min 11 Wiring For details refer to the installation manual of each indoor outdoor unit and controller 11 1 Caution 1 Follow ordinance of your governmental organization for technical standard re lated to electrical equipment wiring regulations and guidance of each electric power company 2 Wiring for control hereinafter referred to as transmission line shall be 5 cm or more 2 in or more apart f...

Страница 15: ... with a suitable material 2 Conduit tube installation Open by hammering the knockout holes for the conduit tube located on the base and the bottom part of the front panel When installing the conduit tube directly through the knockout holes remove the burr and protect the tube with masking tape Use the conduit tube to narrow down the opening if there is a possibility of small animals entering the u...

Страница 16: ... units to ON Fig 11 3 2 MA Remote Controller 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON A Change the jumper connec tor from CN41 to CN40 1 B SW2 1 ON 2 C Keep the j...

Страница 17: ...50 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting 1 OC OS1 and OS2 of the outdoor units in the same refrigerant system are automatically identified They are identified as OC OS1 and OS2 in descending order of capacity If the capacity is the same ...

Страница 18: ...or 100mA 0 1sec or less 40A 30mA or 100mA 0 1sec or less 50A 100mA 0 1sec or less 60A 100mA 0 1sec or less 40A 30mA or 100mA 0 1sec or less 30A 30mA or 100mA 0 1sec or less 50A 100mA 0 1sec or less 30A 30mA or 100mA 0 1sec or less 50A 100mA 0 1sec or less 40A 30mA or 100mA 0 1sec or less 50A 100mA 0 1sec or less 50A 100mA 0 1sec or less 60A 100mA 0 1sec or less 50A 100mA 0 1sec or less 60A 100mA 0...

Страница 19: ...YSJMU A PUHY P120YJMU A BS PUHY P96YJMU A BS PUHY P240YSJMU A PUHY P120YJMU A BS PUHY P120YJMU A BS PUHY P264YSJMU A PUHY P144YJMU A BS PUHY P120YJMU A BS PUHY P288YSJMU A PUHY P144YJMU A BS PUHY P144YJMU A BS PUHY P120YJMU A BS PUHY P312YSJMU A PUHY P120YJMU A BS PUHY P72YJMU A BS PUHY P120YJMU A BS PUHY P336YSJMU A PUHY P120YJMU A BS PUHY P96YJMU A BS PUHY P144YJMU A BS PUHY P360YSJMU A PUHY P12...

Страница 20: ...shing and disappears After turning off the cooling operation unit continues to operate the drain pump for 3 minutes then shuts it off Unit also continues to operate drain pump if condensate has been generated This is a normal sound of the refrigerant circuit operating properly Unstable flow of the refrigerant emits a sound This is temporary and does not imply a problem The LEV is slightly open for...

Страница 21: ...oz 7 0 kg 15 LBS 7 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz Allowable pressure Ps HP 4 15 MPa 601 psi LP 2 21 MPa 320 psi Net weight 300 kg 662 LBS 240 kg 530 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS Model PUHY P312YSJMU A PUHY P336YSJMU A Unit combination PUHY P12...

Страница 22: ...anneau n est pas installé correctement la poussière ou l eau peut pénétrer dans l unité extérieure et un incendie ou un choc électrique peut en résulter En installant et en déplaçant le climatiseur vers un autre site ne le chargez pas avec un frigorigène différent de celui qui est spécifié sur l unité Si un autre frigorigène ou de l air est mélangé au frigorigène original le cycle frigorifique peut ...

Страница 23: ...ez vous que les surfaces intérieures et extérieures des tuyaux sont propres et dépourvues de soufre d oxydes de poussières saletés de particules de rasage d huile d humidité ou de n importe quel autre contaminant dangereux Les contaminants à l intérieur de la tuyauterie du frigorigène peuvent détériorer l huile du frigorigène Entreposez à l intérieur la tuyauterie à utiliser pour l installation et...

Страница 24: ...s composants sur site 4 Spécifications Modèle PUHY P72TJMU A BS PUHY P96TJMU A BS PUHY P120TJMU A BS PUHY P144TJMU A BS PUHY P168TSJMU A BS PUHY P192TSJMU A BS PUHY P216TSJMU A BS PUHY P240TSJMU A BS PUHY P72YJMU A BS PUHY P96YJMU A BS PUHY P120YJMU A BS PUHY P144YJMU A BS PUHY P168YSJMU A BS PUHY P192YSJMU A BS PUHY P216YSJMU A BS PUHY P240YSJMU A BS Niveau de bruit 60 Hz 58dB A 58dB A 60dB A 61dB...

Страница 25: ... 4 S il y a des obstacles à la partie supérieure de l unité C Quand il y a peu d espace jusqu à une obstruction Unité mm in 240 9 15 32 1 31 32 39 3 8 45 50 1000 A Avant B Hauteur de l unité C Dos D Guide de sortie d air fourni sur le terrain 2 En cas d installation collective Fig 6 0 2 Unité mm in 30 450 300 11 13 16 17 23 32 1 3 16 100 450 100 3 15 16 17 23 32 3 15 16 100 450 450 450 17 23 32 17...

Страница 26: ...blage comme fondation de l unité Des vibrations peuvent être transmises à la section d installation et bruit et vibration peuvent être produits par le plancher et les murs selon les conditions d installation Fournissez par conséquent une protection suffisante contre les vibrations coussinets cadre de coussin etc Construisez les fondations de sorte que le coin du pied d installation soit correctemen...

Страница 27: ...rigorigène ait été exécuté et que le processus d évacuation ait été complété c N utilisez jamais de frigorigène pour exécuter une purge d air Servez vous toujours d une pompe à vide pour évacuer d Soyez sûr de charger le système avec un frigorigène liquide e Un manque ou un excès de frigorigène provoque un arrêt d urgence de l unité Chargez le système d une quantité appropriée de frigorigène Au co...

Страница 28: ...manomètre à vide équipement de récupération du frigorigène Le mélange de frigorigène conventionnel et d huile réfrigérant peut détériorer l huile réfrigérante Le mélange d eau détériore l huile réfrigérante Le frigorigène R410A ne contient aucun chlore Par conséquent les détecteurs de fuite de gaz pour les frigorigènes conventionnels ne réagissent pas Gérez les outils utilisés pour le R410A plus s...

Страница 29: ...ø9 52 3 8 ø22 2 7 8 145 240 CMY Y202 G2 109 144 ø12 7 1 2 ø28 58 1 1 8 La 1ère branche de P144 P240 145 240 ø15 88 5 8 ø28 58 1 1 8 241 CMY Y302 G2 241 308 ø19 05 3 4 ø34 93 1 3 8 La 1ère branche de P264 P360 309 ø19 05 3 4 ø41 28 1 5 8 a b c d e Unité mm in Numéro de modèle Tube de fluide Tube de gaz 06 08 12 15 18 ø6 35 1 4 ø12 7 1 2 24 27 30 36 48 54 ø9 52 3 8 ø15 88 5 8 72 ø9 52 3 8 ø19 05 3 4 ...

Страница 30: ...m ft 3 12 oz ft m 0 2 kg m ft 2 16 oz ft m 0 12 kg m ft 1 30 oz ft Taille de tube de fluide Longueur totale de ø9 52 mm 3 8 in Taille de tube de fluide Longueur totale de ø6 35 mm 1 4 in α m 0 06 kg m ft 0 65 oz ft m 0 024 kg m ft 0 26 oz ft Exemple Intérieur 1 48 A ø12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm ...

Страница 31: ... précision Retirer le tube de connexion rétréci Une fois expédié un tube de connexion rétréci est attaché sur site aux valves haute et basse pression pour empêcher la fuite de gaz Prenez les mesures suivantes 1 à 4 pour retirer le tube de connexion rétréci avant de connecter les tubes de frigorigène à l unité extérieure 1 Vérifiez que la valve de frigorigène est complètement fermée tournée à fond d...

Страница 32: ...r les ouvertures permettant de raccorder les tubes de frigorigène et les câbles à l unité Les petits animaux l eau de pluie ou la neige pénétrant par les ouvertures peuvent endommager l appareil A B Tuyaux vers l avant et tuyaux vers le bas Vendus séparément Unité mm in No 1 3 5 7 9 Forme No 2 4 6 8 Forme No 1 2 3 4 5 6 7 8 9 P72 CMY YS100UEB 1pc 1pc 1pc P96 CMY YS200UEB 1pc 1pc 1pc 1pc P120 CMY Y...

Страница 33: ... fluide et ajustez la tuyauterie de gaz pour obtenir une quantité appropriée de frigorigène pendant le fonctionnement N exécutez jamais de purge d air à l aide du frigorigène Remarque Ajoutez toujours une quantité appropriée de frigorigène En outre chargez toujours le système avec du frigorigène liquide Utilisez un manomètre de pression un tuyau flexible de charge et d autres pièces pour le frigorig...

Страница 34: ...r caché B Mur extérieur C Mur extérieur exposé D Sol imperméabilisation E Cheminée des tuyaux du toit F Partie pénétrant dans le coupe feu et le mur limite 1000 1000 39 3 8 39 3 8 A Manchon B Isolant thermique C Calorifuge D Matériau de calfeutrage E Bande F Couche étanche G Manchon avec bord H Matériau calorifuge I Mortier ou autre matériau de calfeutrage non combustible J Matériau d isolation th...

Страница 35: ...0 utilisez un orifice défonçable 5 En cas d espace autour des câbles veillez à le remplir d un matériau approprié 2 Installation des conduits Ouvrez en martelant les orifices à dégager pour le conduit situé sur la base et la partie inférieure du panneau avant Quand vous installez le conduit directement à travers l orifice à dégager retirez les ébarbures et protégez le tube à l aide de bande cache Uti...

Страница 36: ... un contrôleur de système est utilisé réglez SW2 1 sur tous les appareils extérieurs sur ON marche Fig 11 3 2 Télécommande MA A Changez le cavalier de CN41 à CN40 1 B SW2 1 ON marche 2 C Laissez le cavalier sur CN41 B SW2 1 ON marche 2 1 Quand l alimentation n est pas connectée à la ligne de transmission pour la commande centralisée débranchez le connecteur mâle de l alimentation CN41 sur UN appar...

Страница 37: ...principale au sein du même groupe plus 100 M NET R C secondaire 151 à 200 Réglez sur une adresse IC principale au sein du même groupe plus 150 MA R C Définition inutile d adresse définition principale secondaire nécessaire 1 OC OS1 et OS2 des appareils extérieurs dans le même système frigorifique sont automatiquement identifiés Ils sont identifiés comme OC OS1 et OS2 dans l ordre décroissant de capacit...

Страница 38: ...A BS 5 3 10 5 3 10 30 30 30 30 A 30 mA ou 100 mA 0 1 sec ou moins 25 39 PUHY P216TSJMU A BS PUHY P120TJMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 49 76 PUHY P96TJMU A BS 8 4 8 8 4 8 40 40 40 40 A 30 mA ou 100 mA 0 1 sec ou moins 36 59 PUHY P240TSJMU A BS PUHY P120TJMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 49 76 PUHY P120TJMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 ...

Страница 39: ...5 A 30 mA ou 100 mA 0 1 sec ou moins 23 35 PUHY P120YJMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 23 35 PUHY P96YJMU A BS 3 3 12 3 3 12 20 20 20 20 A 30 mA ou 100 mA 0 1 sec ou moins 17 27 PUHY P360YSJMU A PUHY P144YJMU A BS 5 3 10 5 3 10 30 30 30 30 A 30 mA ou 100 mA 0 1 sec ou moins 27 43 PUHY P120YJMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 23 ...

Страница 40: ...nutes puis l arrête L unité continue également de commander la pompe de drainage si le condensat a été généré L unité intérieure émet un bruit en basculant du chauffage au refroidissement et inversement Affichage normal Ce bruit indique que le circuit du frigorigène fonctionnement correctement Immédiatement après la mise en route l unité intérieure émet le bruit de l écoulement du frigorigène Affich...

Страница 41: ... oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz 11 8 kg 26 LBS 1 oz Pression autorisée Ps HP 4 15 MPa 601 psi LP 2 21 MPa 320 psi Poids net 300 kg 662 LBS 240 kg 530 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS 300 kg 662 LBS Modèle PUHY P312YSJMU A PUHY P336YSJMU A Unité combinée PUHY P120YJMU A BS PUHY P120...

Страница 42: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: