<C> Slope of twinning pipes
Make sure the slope of the twinning pipes are at an angle within ±15˚ to the ground.
If the slope exceeds the specified angle, the unit may be damaged.
±
15
°
F
G
<D> Pipe connection example
H
I
H
J
A
Downward slope
B
Upward slope
C
Indoor unit
D
Trap (gas pipe only)
E
Within 2 m [6 ft]
F
Twinning pipe
G
Slope of the twinning pipes are at an angle within ±15˚ to the ground
H
Pipes on site
I
Twinning Kit
J
Straight run of pipe that is 500 mm [19-11/16 in] or more
<Example>
Indoor
1: 48 A: ø12.7 mm [1/2
in
] 40 m [131 ft] a: ø9.52 mm [3/8
in
] 10 m [32 ft]
2: 36 B: ø9.52 mm [3/8
in
] 10 m [32 ft] b: ø9.52 mm [3/8
in
] 5 m [16 ft]
3: 15 C: ø9.52 mm [3/8
in
] 15 m [49 ft] c: ø6.35 mm [1/4
in
] 10 m [32 ft]
4: 12 D: ø9.52 mm [3/8
in
] 10 m [32 ft] d: ø6.35 mm [1/4
in
] 10 m [32 ft]
5: 24
e: ø9.52 mm [3/8
in
] 10 m [32 ft]
At the
conditions
below:
At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and addi-
tional charging of each refrigerant line will be required on site. In order that future
servicing may be properly provided, always keep a record of the size and length of
each refrigerant line and the amount of additional charge by writing it in the space
provided on the outdoor unit.
10.1. Calculation of additional refrigerant
charge
•
Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
•
Use the table below as a guide for calculating the amount of additional charg-
ing and then charge the system accordingly.
•
If the calculation results in a fraction of less than 0.1 kg [4 oz], round up to the
next 0.1 kg [4 oz]. For example, if the result of the calculation was 12.38 kg
[437 oz], round the result up to 12.4 kg [438 oz].
<Additional Charge>
+
+
+
Additional
refrigerant charge
(kg) [oz]
10. Additional refrigerant charge
=
+
+
Liquid pipe size
Total length of
ø12.7 mm [1/2 in]
(m)
×
0.12 (kg/m)
(ft)
×
1.30 (oz/ft)
Liquid pipe size
Total length of
ø15.88 mm [5/8 in]
(m)
×
0.2 (kg/m)
(ft)
×
2.16 (oz/ft)
Liquid pipe size
Total length of
ø19.05 mm [3/4 in]
(m)
×
0.29 (kg/m)
(ft)
×
3.12 (oz/ft)
Liquid pipe size
Total length of
ø9.52 mm [3/8 in]
(m)
×
0.06 (kg/m)
(ft)
×
0.65 (oz/ft)
Liquid pipe size
Total length of
ø6.35 mm [1/4 in]
(m)
×
0.024 (kg/m)
(ft)
×
0.26 (oz/ft)
The total length of each liquid line is as follows:
ø12.7 mm [1/2 in]: A = 40 m [131 ft] = 40 m [131 ft]
ø9.52 mm [3/8 in]: B + C + D + a + b + e
= 10 m [32 ft] + 15 m [49 ft] + 10 m [32 ft] + 10 m [32 ft] +
5 m [16 ft] + 10 m [32 ft] = 60 m [193 ft]
ø6.35 mm [1/4 in]: c + d = 10 m [32 ft] + 10 m [32 ft] = 20 m [64 ft]
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 m [131 ft]
×
0.12 kg/m [1.30 oz/ft] + 60 m [193 ft]
×
0.06 kg/m [0.65 oz/ft]
+ 20 m [64 ft]
×
0.024 kg/m [0.26 oz/ft] + 3.5 kg [124 oz] = 12.4 kg [438 oz]
Value of
Total capacity of connecting indoor units
Models
~ 27
2.0 kg
[71 oz]
Models 28 ~ 54
2.5 kg
[89 oz]
Models 55 ~ 126
3.0 kg
[106 oz]
Models 127 ~ 144
3.5 kg
[124 oz]
Models 145 ~ 180
4.5 kg
[159 oz]
Models 181 ~ 234
5.0 kg
[177 oz]
Models 235 ~ 273
6.0 kg
[212 oz]
Models 274 ~ 307
8.0 kg
[283 oz]
Models 308 ~ 342
9.0 kg
[318 oz]
Models 343 ~ 411
10.0 kg
[353 oz]
Models 412 ~ 480
12.0 kg
[424 oz]
Models 481 ~
14.0 kg
[494 oz]