11. M-NET CONTROL
Hyper Heating Inverter Y-Series
11-4-3. System examples
Factory setting
Setting at the site
DipSW5-1 (Outdoor)
: When the System Controller is used, all the Dip SW5-1 at the outdoor units should be
set to "ON". * Dip SW5-1 remains OFF when only LM-AP is used.
DipSW1-2 (LM-AP)
: When the LM-AP is used together with System Controller, DipSW1-2 at the LM-AP should be
set to "ON".
CN40/CN41
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LM-AP will activate transmission power supply to LM-AP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.
11-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. No address setting is needed.
3. For a system having more than 32 indoor unit, confirm the need of Booster at
11-3. "System configuration restrictions".
4. When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
NOTE:
Indoor unit
MA R/C
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*1
00
00
00
00
00
TB15
TB5
TB5
TB5
TB5
TB5
TB15
TB15
TB15
TB15
Group 2
Group 1
Group 3
Group 4
<Three outdoor units>
<Two outdoor units>
<One outdoor unit>
TB3
TB3
TB3
00
00
00
OC
OS1
OS2
PUHY
TB3
TB3
00
00
OC
OS1
PUHY
TB3
00
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
PUHY
Original switch setting of the outdoors, indoors, controllers, LM-AP, and BM ADAPTER at shipment is as follows.
Outdoor unit
: Address: 00, CN41: ON (Jumper), DipSW5-1: OFF
Indoor unit
: Address: 00
ME remote controller : Address: 101
LM-AP
: Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
BM ADAPTER
: Address: 000, CN41: ON (Jumper)
0000006537.BOOK 87 ページ 2022年4月14日 木曜日 午前10時41分