34
OPERATING PROCEDURE
PHOTOS
4. Removing the room temperature thermistor (TH21)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connector CN20 (Red) from the indoor
controller board.
(3) Remove the room temperature thermistor with its
holder. (See Photo 4)
Photo 3
Photo 4
5. Removing the indoor controller board (I.B)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connectors:
CNMF (White) for fan motor
CNV (White) for vane motor
CN5Y (White) for motor for i-see Sensor (Option)
CN4Z (White) for sensor for i-see Sensor (Option)
CN90 (White) for signal receiver (Option)
CNP (White) for drain pump
CN4F (White) for float switch
CN44 (White) for thermistor (TH22/TH23)
CN60 (White) for LEV
CN01 (Black) for Indoor/Outdoor connecting line
CN3C (Blue) for Indoor/Outdoor transmission
Disconnect the connectors for optional parts, if any.
(3) Disconnect the lead wire connected to the TB5 on the
indoor controller board.
TB5: M-NET transmission connecting wire
(4) For the unit controlled with the wireless remote control
-
ler, disconnect the lead wire connected to the TB15 on
the indoor controller board.
(5) Remove the indoor controller board (3 holders/4
hooks). (See Photo 5)
Photo 5
Holders
Hooks
Electrical box fixing
screws (M5 ×10)
Electrical box fixing
screws (M5 × 10)
CN20
Room temperature
detection thermistor
Indoor
controller board
Electrical box
Thermistor holder
Thermistor (TH1)
OCH657