27
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW11
1s digit
address
setting
SW12
10s digit
address
setting
Rotary switch
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
10
SW11
1
Address setting
should be done
when M-NET
remote controller is
being used.
Before
power
supply
ON
Indoor controller board
<Initial setting>
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
SW11
SW14
Connection
No.
setting
Rotary switch
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
This is the switch
to be used when
the indoor unit is
operated with R2
series outdoor unit
as a set.
Indoor controller board
<Initial setting>
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
SW21
Function
Selection
1
Setting the ceiling height
Depending on the combination
of SW21-1 and SW21-2.
Refer to <Table E> below.
Under
suspension
Indoor controller board
<Initial setting>
ON
OFF
1 2 3 4 5 6
2
Setting the ceiling height
3
Setting the number of air outlet
Depending on the combination
of SW21-3 and SW21-4.
Refer to <Table E> below.
4
Setting the number of air outlet
5
Setting for optional parts
Option
Standard
6
Not used
Not used
Not used
PLFY-P20/25/32/40/50/63/80VEM-E
PLFY-P100/125VEM-E
Low ceiling
Standard
High ceiling
Low ceiling
Standard
High ceiling
SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
4 directions
SW21-3
OFF
2.5 m
2.7 m
3.5 m
2.7 m
3.2 m
4.5 m
SW21-4
ON
3 directions
SW21-3
OFF
2.7 m
3.0 m
3.5 m
3.0 m
3.6 m
4.5 m
SW21-4
ON
2 directions
SW21-3
OFF
3.0 m
3.3 m
3.5 m
3.3 m
4.0 m
4.5 m
SW21-4
ON
Note: The setting with
indicates the initial setting; To change it to other than
, switch setting is necessary.
Blowout directions
Ceiling height
<Table E>
Continue to the next page
OCH657