background image

9

GB

D

F

E

I

NL

P

GR

RU

TR

GB

GB

GB

GB

GB

5.2. Confirming the unit’s position and fix-

ing hanging bolts

s

s

s

s

s

Use the gage supplied with the panel to confirm that the unit body and
hanging bolts are positioned in place. If they are not positioned in place,
it may result in dew drops due to wind leak. Be sure to check the positional
relationship.

s

s

s

s

s

Use a level to check that the surface indicated by 

A

A

A

A

A

 is at level. Ensure

that the hanging bolt nuts are tightened to fix the hanging bolts.

6. Refrigerant pipe and drain pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the re-
frigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commer-
cially available insulating material (with a heat-resisting temperature of more than
100 

°

C and thickness given below) onto both liquid and gas pipes.

Be also sure to wind commercially available insulating material (with a form
polyethylene’s specific gravity of 0.03 and thickness given below) onto all pipes
which pass through rooms.

6.2. Refrigerant pipe, drain pipe and filling port

[Fig. 6.2.1] (P.3)

A

Refrigerant pipe (liquid pipe): HP

B

Drain pipe

C

Hanging bolt pitch

D

Refrigerant pipe (gas pipe): LP

E

Filling port

F

Drain hole

2

If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating
material’s thickness more than those given in the table above.

3

If there are customer’s specifications, simply follow them.

6.1. Refrigerant pipe and drain pipe specifications

[Fig. 6.1.1] (P.3)

A

Flare cutting dimensions

B

Refrigerant pipe sizes & Flare nut tightening torque

C

Apply refrigerating machine oil over the entire flare seat surface

* Use the provided flare nut for the following pipes: Liquid pipe of P50, P100, P125, and gas pipe of P50.

s

s

s

s

s

To ensure that drain is discharged, be sure to hang the unit at level using
a level.

 Caution:

Be sure to install the unit body at level.

[Fig. 5.2.1] (P.3)

A

Indoor unit’s bottom surface

(Surface to which a decorative panel is attached)

6.3. Request for refrigerant piping connection

Description of parts to be used

No.

1

2

3

Work procedures

Mount the provided pipe insula-
tion (1) on the liquid pipe of the
refrigerant piping, and then mount
the flare insulation (2) on the gas
pipe.

Fixing of insulated pipe

Fixing of flare insulation

Reference drawing

[Fig. 6.3.1] (P.3)

[Fig. 6.3.2] (P.3)

[Fig. 6.3.2] (P.3)

[Fig. 6.3.3] (P.3)

(Note *3)

[Fig. 6.3.3] (P.3)

(Note *4)

Detail of work

“INNER” and “OUTER” are marked on the in-
side of the flare insulation. Mount the portion
marked “INNER” near the unit body and the
portion marked “OUTER” on the field piping
side.

• Fasten the insulated pipe with the insula-

tion tape.

• Firmly secure the insulation with the pro-

vided tie band (4) at the position indicated
on the drawing.

• Fasten the flare insulation with the provided

tape (3).

• Fasten with the provided tie band (4) at the

position indicated on the drawing.

Item to be observed

• Using the flare insulation of a different model may

result in condensation forming. Check the model
name on the insulation and be sure to use the cor-
rect one.

• To prevent a gap from forming near the unit’s side

plate, be sure that the flare insulation firmly con-
tacts the unit’s side plate before mounting.

• Incorrectly mounting the “INNER” and “OUTER”

sides of the insulation may result in condensation
forming.

Seal the slit securely so that there are no openings.
Be sure to mount the insulation so that the slit is on
the top.

Seal the slit securely so that there are no openings.
Be sure to mount the insulation so that the slit is on
the top.

Copper pipe O.D. (mm)

ø6.35
ø9.52
ø12.7

ø15.88
ø19.05

Flare dimensions  øA dimensions (mm)

8.7 – 9.1

12.8 – 13.2
16.2 – 16.6
19.3 – 19.7
22.9 – 23.3

A

Flare cutting dimensions

B

Refrigerant pipe sizes & Flare nut tightening torque

P20/25/32/40
P50
P63/80
P100/125

O.D.ø6.35 (1/4")
O.D.ø6.35 (1/4")
O.D.ø9.52 (3/8")
O.D.ø9.52 (3/8")

Pipe size

Tightening

torque

(N·m)

14 – 18
34 – 42
34 – 42
34 – 42

O.D.ø12.7 (1/2")
O.D.ø12.7 (1/2")
O.D.ø15.88 (5/8")
O.D.ø15.88 (5/8")

Pipe size

Tightening

torque

(N·m)

49 – 61
68 – 82
68 – 82

100 – 120

O.D.ø6.35 (1/4")
O.D.ø9.52 (3/8")
O.D.ø9.52 (3/8")
O.D.ø9.52 (3/8")

Pipe size

Tightening

torque

(N·m)

14 – 18

34 – 42*

34 – 42
34 – 42

O.D.ø12.7 (1/2")
O.D.ø15.88 (5/8")
O.D.ø15.88 (5/8")
O.D.ø19.05 (3/4")

Pipe size

Tightening

torque

(N·m)

49 – 61

68 – 82*

68 – 82

100 – 120*

17
22
22
22

27
29
29
36

Liquid

pipe

(mm)

Gas
pipe

(mm)

Flare nut O.D.

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

R410A

R407C or R22

1

Select the thickness of insulating material by pipe size.

Pipe size

Insulating material’s thickness

6.4 mm to 25.4 mm

More than 10 mm

28.6 mm to 38.1 mm

More than 15 mm

Содержание CITY MULTI PLFY-P-VLMD-E SERIES

Страница 1: ...E Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a ...

Страница 2: ... hole F 6 ø2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 Model name 20 40 50 63 80 100 125 A 1080 1250 1750 2010 B More than 1000 C More than 500 D Lap 20 E More than 350 F F B B 110 159 52 34 435 218 218 221 110 52 159 34 435 218 218 221 159 110 52 34 754 221 199 199 199 199 201 C E D 856 45 90 ø224 145 G 3 3 Fig 3 3 1 A E D B A E 2 216 45 197 240 1 1 C D 90 90 181 2 ø172 A 2 A 1 A Fresh...

Страница 3: ...sulation material J Flare K Pull in this direction L Insulation material M Flare N There must be no gap O Move to the original position Fig 6 3 2 C B A D E F G 2 20 20 20 20 3 4 A B C A Field refrigerant piping B There must be no gap C Unit body plate D OUTER E INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation Fig ...

Страница 4: ...7 2 1 Fig 7 2 2 Fig 7 3 1 Fig 8 1 1 D I C H G K I J 3 D C 28 cm D 170 5 mm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E Take as large as possible About 10 cm F Collected pipes A C B A B 1 A 25 cm B 1 5 2 ...

Страница 5: ...al bed for M NET outdoor transmission cable Use shielding earth cable on outdoor unit side Fig 8 3 1 Fig 8 3 3 Viewed from bottom of the terminal bed box Power Source N L M1 M2 S L N 1 2 2 2 D D H E F F H E G G 2 1 S S M1 M2 Fig 8 3 2 Fig 8 3 4 CN62 SW1 MADE IN JAPAN ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Fig 8 4 1 Addres...

Страница 6: ...air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could res...

Страница 7: ...h conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R410A or R407C the refrigerant may deteriorated If water is mixed in the R410A or R407C the refrigerator oil may deteriorate Since R410A or R407C does not contain ...

Страница 8: ...2 A Fresh air intake B Fresh air intake 240 45 knock out hole C Fresh air intake ø150 knock out hole D 4 ø2 9 mounting hole E Cut Notes 1 1 1 1 1 Make 4 cuts on the outdoor air inlet When connecting a round flexible duct mount an optional outdoor air intake duct flange PAC KH 110F ø150 2 2 2 2 2 The amount of suction air coming through the outdoor air inlet can be adjusted by making two cuts on th...

Страница 9: ...ovided pipe insula tion 1 on the liquid pipe of the refrigerant piping and then mount the flare insulation 2 on the gas pipe Fixing of insulated pipe Fixing of flare insulation Reference drawing Fig 6 3 1 P 3 Fig 6 3 2 P 3 Fig 6 3 2 P 3 Fig 6 3 3 P 3 Note 3 Fig 6 3 3 P 3 Note 4 Detail of work INNER and OUTER are marked on the in side of the flare insulation Mount the portion marked INNER near the ...

Страница 10: ...ate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amo...

Страница 11: ...he polyethylene plug C About 1000 cc D Water E Filling port 6 Never connect the power cable to leads for the transmission cables Otherwise the cables would be broken 7 Be sure to connect control cables to the indoor unit remote controller and the outdoor unit 8 Put the unit to the ground on the outdoor unit side 9 Select control cables from the conditions given in below Caution Be sure to put the ...

Страница 12: ...it installation manual Install a remote controller following the manual supplied with the remote con troller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polarized 2 wire Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is mor...

Страница 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: