5. Installing the unit

5.1. Hanging the unit body

s

s

s

s

s

Bring the indoor unit to an installation site as it is packed.

s

s

s

s

s

To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.

s

s

s

s

s

When lifting with a lifting machine, in order to protect against damage,
reverse the unit body as is packed with the packing cap and lift it.

3.1. Securing installation and service space

[Fig. 3.1.1] (P.2)

Select a blowout direction suited for room shape, installation site and so on.

Piping, wiring and maintenance are all done on the bottom and the side. So,
secure the space given above for such work. Also, taking into consideration
serviceability and safety in hanging, secure as large space as possible.

4. Fixing hanging bolts

4.2. Ceiling hole and hanging bolt positions

Use the gauge supplied with the panel to fix hanging bolts so that the unit body
and ceiling hole are positioned in place as shown in the figure below. For how
to use the gauge, refer to the instruction manual supplied with the panel.

Notes:

The gauge may expand or shrink with changes in the temperature and
humidity. First be sure to check the product dimensions, and then use
the gauge.

The ceiling hole is adjustable as shown in the figure below. Align the
centers of both ceiling hole and unit body so that the unit body is not
biased to the ceiling hole and that the gaps between the ceiling hole
edges and the unit body’s external dimensions come to be identical.

Use M10 hanging bolts (for all bolts). (field supply)

Each hanging bolt must extrude C mm from the ceiling. It is possible to slide
the unit body 10 mm max. within part of the heights of the unit body and deco-
rative panel in  order to make fine installation adjustments to the finished ceil-
ing surface. Sliding the unit body and incorporating a high-performance filter
requires the dimensions given in the figure below. To this, attach nuts which will
fix a hanging bracket as shown in the figure.

[Fig. 4.2.1] (P.3)

A

Nut

B

Washer (supplied with the unit body)

C

Hanging bolt ø10 (M10 screw)

D

Ceiling hole dimensions

E

Hanging bolt pitch

F

Hanging bolt

G

Finished ceiling surface

H

Hanging bracket

Note:

Affixed on the back surface of each split flow duct end connection is
insulating material. Use a cutter knife to cut the insulating material along
the end connection.

3.3. Outdoor air inlet

[Fig. 3.3.1] (P.2)

A

Fresh air intake

B

Fresh air intake

240 

×

 45 knock out hole

C

Fresh air intake

ø150 knock out hole

D

4-ø2.9 mounting hole

E

Cut

Notes:

1

1

1

1

1

Make 4 cuts on the outdoor air inlet. When connecting a round flexible
duct, mount an optional outdoor air intake duct flange PAC-KH 110F (ø150).

2

2

2

2

2

The amount of suction air coming through the outdoor air inlet can be
adjusted by making two cuts on the outdoor air inlet as shown in the
figure above.

3.4. Combining indoor units with outdoor

units

For combining indoor units with outdoor units, refer to the outdoor unit installation
manual.

3.2. Split flow duct end connection - fresh

air intake

[Fig. 3.2.1] (P.2)

Knockouts are provided at each position as shown in the figure. Use them for
your purposes when installing the unit.

A

Split flow duct end connection

B

Split flow duct end connection (435 

×

 110 knock out on both sides)

C

Split flow duct end connection (754 

×

 110 knock out on both sides)

D

Split flow duct end connection (ø200 knock out on both sides)

E

10-ø2.9 mounting hole

F

6-ø2.9 mounting hole

G

4-ø2.9 mounting hole

4.1. Fixing hanging bolts

(Give site of suspension strong structure.)

Hanging structure

Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.

If necessary, reinforce the hanging bolts with anti-quake supporting members
as countermeasures against earthquakes.
* Use M10 for hanging bolts and anti-quake supporting members (field supply).

1

Reinforcing the ceiling with additional members (edge beam, etc.) must be
required to keep the ceiling at level and to prevent the ceiling from vibrations.

2

Cut and remove the ceiling members.

3

Reinforce the ceiling members, and add other members for fixing the ceiling
boards.

[Fig. 4.1.1] (P.2)

A

Center of gravity

Model name

20-40

50 · 63

80 · 100

125

A

1080

1250

1750

2010

B

More than 1000

C

More than 500

D

Lap: 20

E

More than 350

Model name

PLFY-P20VLMD-E
PLFY-P25VLMD-E
PLFY-P32VLMD-E
PLFY-P40VLMD-E
PLFY-P50VLMD-E
PLFY-P63VLMD-E
PLFY-P80VLMD-E
PLFY-P100VLMD-E
PLFY-P125VLMD-E

574
574
574
574
574
574
574
574
574

824
824
824
824
994
994

1494
1494
1756

172
172
172
172
172
172
172
172
203

287
287
287
287
287
287
287
287
287

370
370
370
370
445
445
655
655
758

160
160
160
160
160
160
160
160
181

23
23
24
24
27
28
44
47
56

6.5
6.5
6.5
6.5
7.5
7.5

12.5
12.5

13

W

L

H

X

Y

Z

Unit

Weight

(kg)

Panel

Weight

(kg)

Model name

20 – 40

50 · 63

80 · 100

125

A

1040

1210

1710

1970

B

824

994

1494

1756

C

157 – 167

155 – 165

D

More than 350

Center of gravity and Product  Weight

[Fig. 5.1.1] (P.3)

A

Drain pipe side

B

Unit body

C

Packing cap

D

Lifting machine

Содержание CITY MULTI PLFY-P-VLMD-E SERIES

Страница 1: ...E Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a ...

Страница 2: ... hole F 6 ø2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 Model name 20 40 50 63 80 100 125 A 1080 1250 1750 2010 B More than 1000 C More than 500 D Lap 20 E More than 350 F F B B 110 159 52 34 435 218 218 221 110 52 159 34 435 218 218 221 159 110 52 34 754 221 199 199 199 199 201 C E D 856 45 90 ø224 145 G 3 3 Fig 3 3 1 A E D B A E 2 216 45 197 240 1 1 C D 90 90 181 2 ø172 A 2 A 1 A Fresh...

Страница 3: ...sulation material J Flare K Pull in this direction L Insulation material M Flare N There must be no gap O Move to the original position Fig 6 3 2 C B A D E F G 2 20 20 20 20 3 4 A B C A Field refrigerant piping B There must be no gap C Unit body plate D OUTER E INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation Fig ...

Страница 4: ...7 2 1 Fig 7 2 2 Fig 7 3 1 Fig 8 1 1 D I C H G K I J 3 D C 28 cm D 170 5 mm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E Take as large as possible About 10 cm F Collected pipes A C B A B 1 A 25 cm B 1 5 2 ...

Страница 5: ...al bed for M NET outdoor transmission cable Use shielding earth cable on outdoor unit side Fig 8 3 1 Fig 8 3 3 Viewed from bottom of the terminal bed box Power Source N L M1 M2 S L N 1 2 2 2 D D H E F F H E G G 2 1 S S M1 M2 Fig 8 3 2 Fig 8 3 4 CN62 SW1 MADE IN JAPAN ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Fig 8 4 1 Addres...

Страница 6: ...air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could res...

Страница 7: ...h conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R410A or R407C the refrigerant may deteriorated If water is mixed in the R410A or R407C the refrigerator oil may deteriorate Since R410A or R407C does not contain ...

Страница 8: ...2 A Fresh air intake B Fresh air intake 240 45 knock out hole C Fresh air intake ø150 knock out hole D 4 ø2 9 mounting hole E Cut Notes 1 1 1 1 1 Make 4 cuts on the outdoor air inlet When connecting a round flexible duct mount an optional outdoor air intake duct flange PAC KH 110F ø150 2 2 2 2 2 The amount of suction air coming through the outdoor air inlet can be adjusted by making two cuts on th...

Страница 9: ...ovided pipe insula tion 1 on the liquid pipe of the refrigerant piping and then mount the flare insulation 2 on the gas pipe Fixing of insulated pipe Fixing of flare insulation Reference drawing Fig 6 3 1 P 3 Fig 6 3 2 P 3 Fig 6 3 2 P 3 Fig 6 3 3 P 3 Note 3 Fig 6 3 3 P 3 Note 4 Detail of work INNER and OUTER are marked on the in side of the flare insulation Mount the portion marked INNER near the ...

Страница 10: ...ate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amo...

Страница 11: ...he polyethylene plug C About 1000 cc D Water E Filling port 6 Never connect the power cable to leads for the transmission cables Otherwise the cables would be broken 7 Be sure to connect control cables to the indoor unit remote controller and the outdoor unit 8 Put the unit to the ground on the outdoor unit side 9 Select control cables from the conditions given in below Caution Be sure to put the ...

Страница 12: ...it installation manual Install a remote controller following the manual supplied with the remote con troller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polarized 2 wire Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is mor...

Страница 13: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: