16
17
OCH728A
Model
PLFY-M80VEM-E
PLFY-M80VEM-ET
PLFY-M100VEM-E
PLFY-M100VEM-ET
PLFY-M125VEM-E
PLFY-M125VEM-ET
Power source
1-phase 220-240 V 50 Hz, 1-phase 220 V 60 Hz
Cooling capacity
*
1
(Nominal)
*
1
*
1
*
2
kW
9.0
11.2
14.0
kcal/h
7,700
9,600
12,000
BTU/h
30,700
38,200
47,800
kcal/h
8,000
10,000
12,500
Power input
kW
0.05
0.07
0.11
Current input
A
0.50
0.67
1.06
Heating capacity
*
3
(Nominal)
*
3
*
3
kW
10.0
12.5
16.0
kcal/h
8,600
10,800
13,800
BTU/h
34,100
42,700
54,600
Power input
kW
0.05
0.07
0.11
Current input
A
0.43
0.60
0.99
External finish
Galvanized steel sheet
External dimension
H × W × D
mm
258 × 840 × 840
10-3/16 × 33-3/32 × 33-3/32
298 × 840 × 840
11-3/4 × 33-13/32 × 33-13/32
inch
Net weight
kg (lb)
21(46)
24(53)
24(53)
Grille
model
PLP-6EA
External finish
MUNSELL (1.0Y 9.2/0.2)
Dimension
H × W × D
mm
40 × 950 × 950
inch
1-9/16 × 37-13/32 × 37-13/32
Net weight
kg (lb)
5 (11)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
Fan
Type × Quantity
Turbo fan × 1
Turbo fan × 1
Turbo fan × 1
External static
press.
Pa
0
0
0
mmH
2
O
0
0
0
Motor type
DC motor
Motor output
kW
0.050
0.120
0.120
Driving mechanism
Direct-drive
Airflow rate
(Low-Mid2-
Mid1-High)
K
/min
14 - 17 - 20 - 23
20 - 23 - 26 - 29
22 - 26 - 30 - 35
L/s
233 - 283 - 333 - 383
333 - 383 - 433 - 483
367 - 433 - 500 - 583
cfm
494 - 600 - 706 - 812
706 - 812 - 918 - 1024
777 - 918 - 1060 - 1236
Sound pressure level
(Low-Mid2-Mid1-High)
(measured in anechoic room)
dB <A>
28 - 31 - 34 - 37
34 - 37 - 39- 41
35 - 39 - 42 - 45
Insulation material
PS
Air filter
PP honeycomb
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R32/R410A CITY MULTI
Diameter of
refrigerant
pipe
Liquid
(R32/R410A)
mm (inch)
[
9.52 (
[
3/8) Flare
[
9.52 (
[
3/8) Flare
[
9.52 (
[
3/8) Flare
Gas
(R32/R410A)
mm (inch)
[
15.88 (
[
5/8) Flare
[
15.88 (
[
5/8) Flare
[
15.88 (
[
5/8) Flare
Field drain pipe size
mm
O.D.
[
32 (VP-25)
Standard
attachment
Document
Accessory
Installation Manual, Instruction Book
Remark
Optional parts
Grille **1
PLP-6EA
Air outlet shutter plate
PAC-SJ37SP-E
High efficiency filter
element **2
PAC-SH59KF-E
Multi-function
casement
PAC-SJ41TM-E
**1. PLFY-M-VEM-(E/ET) should be used together with PLP-6EA.
**2. PAC-SJ41TM-E is necessary to use with filter PAC-SH59KF-E.
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*1 Nominal cooling condition
Indoor :
Outdoor :
Pipe length :
Level difference :
27
˚CDB/19˚CWB (81˚FDB/66˚FWB)
35
˚CDB (95˚FDB)
7.5
m (24-9/16 ft)
0
m (0 ft)
*2 Nominal cooling condition
27
˚CDB/19.5˚CWB (81˚FDB/67˚FWB)
35
˚CDB (95˚FDB)
5
m (16-3/8 ft)
0
m (0 ft)
*3 Nominal heating condition
20
˚CDB (68˚FDB)
7˚CDB/6˚CWB (45˚FDB/43˚FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
*1 and *3 are subject to JIS B8615-1.
2.
Due to continuing improvement, above specification may be subject to change without notice.
1. Nominal conditions
Notes:
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
cfm = m3/min × 35.31
lb = kg/0.4536
*Above specification data is