Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-

ant in the cylinder will change and performance may drop.

Do not use a refrigerant other than R407C.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may

cause the refrigerator oil to deteriorate.

Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the

refrigerator oil to deteriorate.

Do not use the following tools that are used with conventional refriger-
ants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R407C,

the refrigerant may deteriorated.

- If water is mixed in the R407C, the refrigerator oil may deteriorate.
- Since R407C does not contain any chlorine, gas leak detectors for conven-

tional refrigerants will not react to it.

Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-

rate.

1.3. Before getting installed

 Caution:

Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision instru-
ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical

equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air condi-
tioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.

Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80% or when the drain pipe is clogged,

condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.

The indoor models should be installed the ceiling over than 2.5 m from
floor.

1.4. Before getting installed (moved) - elec-

trical work

 Caution:

Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or

telephone ground lines. Improper grounding may result in electric shock.

Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.

Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.

Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.

Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may

result in a general unit failure or fire.

Do not wash the air conditioner units.
- Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury

or property damage.

Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping may cause water leakage and damage to furniture

and other possessions.

Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a

means of transportation. It is dangerous.

- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on

the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.

Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause

stabs or other injuries.

- Tear apart and throw away plastic packaging bags so that children will not

play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.

1.5. Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can

result in severe damage to internal parts. Keep the power switch turned on
during the operational season.

Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.

Do not touch the refrigerant pipes during and immediately after opera-
tion.
- During and immediately after operation, the refrigerant pipes are may be hot

and may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.

Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,

water leakage and trouble may occur.

2. Indoor unit accessories

The unit is provided with the following accessories:

No.

Name

Quantity

1

Attachment connector

1

3. Selecting an installation site

Select a site with sturdy fixed surface sufficiently durable against the weight of
unit.

Before installing unit, the routing to carry in unit to the installation site should
be determined.

Select a site where the unit is not affected by entering air.

Select a site where the flow of supply and return air is not blocked.

Select a site where refrigerant piping can easily be led to the outside.

Select a site which allows the supply air to be distributed fully in room.

Do not install unit at a site with oil splashing or steam in much quantity.

Do not install unit at a site where combustible gas may generate, flow in, stag-
nate or leak.

Do not install unit at a site where equipment generating high frequency waves
(a high frequency wave welder for example) is provided.

Do not install unit at a site where fire detector is located at the supply air side.
(Fire detector may operate erroneously due to the heated air supplied during
heating operation.)

When special chemical product may scatter around such as site chemical plants
and hospitals, full investigation is required before installing unit. (The plastic
components may be damaged depending on the chemical product applied.)

3.1. Install the indoor unit on a ceiling strong

enough to sustain its weight

 Warning:

The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down causing
injuries.

Содержание CITY MULTI PEFY-P-VML-A

Страница 1: ...un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidad...

Страница 2: ...e beam C Tie beam D Square timber for hanging the air conditioner E Pitch F G H F Insert 100 to 150 kg 1 piece field supply G M10 hanging bolt field supply H Reinforcement 4 4 1 Fig 4 1 1 197 142 57 178 43 A B C A Refrigerant pipe liquid pipe HP B Refrigerant pipe gas pipe LP C Drain pipe A B A B A Filter B Bottom plate A Filter B Bottom plate B A A C D C E D A Unit body B Lifting machine C Nuts f...

Страница 3: ...ential wire between duct work to air conditioner G Air filter H Inlet grille A B D E C C C C C C C A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box 8 8 2 Fig 8 1 1 Fig 8 2 1 8 1 Fig 8 1 2 9 Fig 9 0 1 10 10 1 Fig 10 1 1 Fig 10 2 1 10 2 A A C TB5 TB5 S M1M2 S M1M2 C B TB3 M1M2 A A C TB5 TB15 TB5 TB15 S M1M2 S M1M2 B TB3 M1M2 2 1 C 2 1 A...

Страница 4: ...ntroller A Terminal bed B Round terminal C Shield wire D Two shield wires may be connected together at the shield relay terminal bed E One shield wire is connected with another shield wire Terminal connection F Insulation tape for the earthing of shield and the prevention of contact to transmission terminal A Terminal bed box connector White B Motor connector White C Attachment connector Blue Acce...

Страница 5: ...aken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult th...

Страница 6: ... cause personal injury or property damage Install the drain piping according to this Installation Manual to ensure proper drainage Wrap thermal insulation around the pipes to prevent condensation Improper drain piping may cause water leakage and damage to furniture and other possessions Be very careful about product transportation Only one person should not carry the product if it weighs more than...

Страница 7: ...ed with the panel to confirm that the unit body and hanging bolts are positioned in place If they are not positioned in place it may result in dew drops due to wind leak Be sure to check the positional relationship s s s s s Use a level to check that the surface indicated by A A A A A is at level Ensure that the hanging bolt nuts are tightened to fix the hanging bolts s s s s s To ensure that drai...

Страница 8: ...en the inlet grille and the fan over 850 mm If it is less than 850 mm install a safety guard not to touch the fan Fig 9 0 1 P 3 A Air inlet B Air outlet C Access door D Ceiling surface E Canvas duct F Connect common reference potential wire between duct work to air conditioner G Air filter H Inlet grille 8 Connecting refrigerant pipes and drain pipes 8 1 Refrigerant piping work This piping work mu...

Страница 9: ... block for outdoor transmission cable C Remote controller DC 9 to 13 V between 1 and 2 MA remote controller DC 24 to 30 V between M1 and M2 M NET remote controller Fig 10 2 3 P 3 MA Remote controller Fig 10 2 4 P 3 M NET Remote controller A Non polarized B Upper level TB15 C Remote Controller D Lower level TB5 The MA remote controller and the M NET remote controller cannot be used at the same time...

Страница 10: ...taching the terminal bed box cover Doing so may cause a risk of disconnection When accommodating the terminal bed box make sure that the connec tors on the box side are not removed If removed it cannot operate nor mally 10 4 Selecting the power source It is 240V 230V setting at factory shipment So it is necessary to change the setting in other power supply districts Please remove the connector of ...

Страница 11: ...а питания или неправильном выполнении электроработ может возникнуть электрошок или пожар Надежно установите крышку панель коробки терминала выводов наружного прибора Если крышка панель коробки терминала выводов не установлена надлежащим образом то в наружный прибор может попасть пыль или вода что в свою очередь может привести к пожару или электрошоку При установке и перемещении кондиционера на дру...

Страница 12: ...я радиосвязи могут вызвать сбой в работе кондиционера или его отключение С другой стороны кондиционер может мешать работе такого оборудования создаваемым шумом который нарушает ход медицинских процедур или радиовещания Не устанавливайте прибор на конструкции которая может стать причиной утечки При влажности в помещении свыше 80 или при засорении дренажной трубы с внутреннего прибора может капать к...

Страница 13: ...ызгивание масла или большие объемы пара Не устанавливайте прибор в таком месте где возможно образование приток застой или утечка горючего газа Не устанавливайте прибор в таком месте где функционирование другого оборудования приводит к образованию высокочастотных волн например оборудование высокочастотной сварки Не устанавливайте прибор в таком месте где со стороны подачи воздуха расположен детекто...

Страница 14: ...у ВС для соединения между внутренними приборами Ограничения параметров длины трубы и допустимые перепады возвышения указаны в руководстве к прибору предназначенному для установки снаружи Методом трубного соединения является метод пайки Осторожно Установите трубы хладагента для внутреннего прибора в соответствии со следующими инструкциями 1 Обрежьте конец трубы внутреннего прибора удалите газ затем...

Страница 15: ...масел влаги или других загрязнений Никогда не пользуйтесь имеющимися трубами хладагента Большое количество хлорина в обычном хладагенте и масле охлаждения в имеющихся трубах вызовет ухудшение нового хладагента Храните трубы предназначенные для установки в помещении оба конца труб должны быть герметически закрыты до непосредственного момента спайки При попадании пыли грязи или воды в цикл охлаждени...

Страница 16: ...ровода Технические условия соединения кабелей указаны в руководстве по установке наружного прибора Установите пульт дистанционного управления следуя инструкциям приведенным в поставленном вместе с ним руководстве Подсоедините 1 и 2 на TB15 внутреннего блока кондиционера к контроллеру ДУ MA Неполяризованный 2 жильный кабель Подсоедините M1 и M2 на TB5 внутреннего блока кондиционера к контроллеру ДУ...

Страница 17: ...передачи с соединительной колодкой передачи через пропускное отверстие соединительной коробки с помощью обычной втулки Fig 10 3 3 P 4 E Для предотвращения воздействия растягивающего усилия на точки соединения проводов источника питания блока выводов используйте проходной изолятор например соединение PG или тому подобное F Проводка источника питания G Растягивающее усилие H Используйте обычный прох...

Страница 18: ...tact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: