14
WT07349X04
PEFY-P-VMH-E-F series
P80VMH-E-F
P140VMH-E-F
Power source
~220-240 V 50 Hz/~208-230 V 60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
9.0/8.5
16.0/15.1
Dimension (Height/Width/Depth)
mm
380/1000/900
380/1200/900
Net weight
kg
50
67
Fan
Airflow rate (High)
m
3
/min
9
18
External static pressure
Pa
220 V 50 Hz
40/115/190
50/115/190
230 V 50 Hz
50/130/210
60/130/220
240 V 50 Hz
80/170/220
100/170/240
208 V 60 Hz
35/85/170
35/85/170
220 V 60 Hz
40/115/190
50/115/190
230 V 60 Hz
50/130/220
60/130/220
Sound pressure level (High)
*2
dB(A)
208, 220 V
27/83/43
28/38/43
230, 240 V
33/43/45
34/43/45
Filter
Long life filter (option)
P200VMH-E-F
P250VMH-E-F
Power source
3 N ~380-415 V 50/60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
22.4/21.2
28.0/26.5
Dimension (Height/Width/Depth)
mm
470/1250/1120
470/1250/1120
Net weight
kg
100
100
Fan
Airflow rate
m
3
/min
28
35
External static pressure
Pa
380 V
140/200
110/190
400 V
150/210
120/200
415 V
160/220
130/210
Sound pressure level
dB(A)
380 V
39/42
40/44
400 V
40/43
40/45
415 V
40/44
41/46
Filter
Long life filter (option)
*1
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
<Cooling> Indoor: 33°CDB/28°CWB, Outdoor: 33°CDB
<Heating> Indoor: 0°CDB/-2.9°CWB, Outdoor: 0°CDB/-2.9°CWB
*2 The operating noise is the data that was obtained in an anechoic room.
PEFY-P-VMHS-E-F series
P125VMHS-E-F
P200VMHS-E-F
P250VMHS-E-F
Power source
~220-240 V 50/60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
14.0/8.9
22.4/13.9
28.0/17.4
Dimension (Height/Width/Depth)
mm
380/1200/900
470/1250/1120
470/1250/1120
Net weight
kg
46
79
82
Fan
Airflow rate (High)
m
3
/min 14.0-15.5-18.0-(20.0) 22.5-25.0-28.0-(32.0) 28.0-31.0-35.0-(40.0)
External static pressure
Pa
100/150/200/250
Sound pressure level (High)
*2
dB(A)
34/37/41
35/38/41
38/40/44
Filter
Long life filter (option)
*1
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
<Cooling> Indoor: 33°CDB/28°CWB, Outdoor: 33°CDB
<Heating> Indoor: 0°CDB/-2.9°CWB, Outdoor: 0°CDB/-2.9°CWB
*2 The operating noise is the data that was obtained in an anechoic room.