GB
15
WT07349X04
PFFY-P-VLEM-E/PFFY-P-VLRM(M)-E series
P20VLEM-E
P25VLEM-E
P32VLEM-E
P40VLEM-E
P50VLEM-E
P63VLEM-E
Power source
~220-240 V 50 Hz/~208-230 V 60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Dimension (Height/Width/Depth)
mm
630/1050/220
630/1050/220
630/1170/220
630/1170/220
630/1410/220
630/1410/220
Net weight
kg
28
28
30
32
36
37
Fan
Airflow rate
(Low-High)
m
3
/min
5.5-6.5
5.5-6.5
7.0-9.0
9.0-11.0
12.0-14.0
12.0-15.5
Sound pressure level (Low-High)*
3 *4
dB(A)
34-40
34-40
35-40
38-43
38-43
40-46
Filter
Standard filter
P20VLRM-E
P25VLRM-E
P32VLRM-E
P40VLRM-E
P50VLRM-E
P63VLRM-E
Power source
~220-240 V 50 Hz/~208-230 V 60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Dimension (Height/Width/Depth)
mm
639/886/220
639/886/220
639/1006/220
639/1006/220
639/1246/220
639/1246/220
Net weight
kg
22
22
24
25
29
30
Fan
Airflow rate
(Low-High)
m
3
/min
5.5-6.5
5.5-6.5
7.0-9.0
9.0-11.0
12.0-14.0
12.0-15.5
Sound pressure level (Low-High)*
3 *4
dB(A)
34-40
34-40
35-40
38-43
38-43
40-46
Filter
Standard filter
P20VLRMM-E
P25VLRMM-E
P32VLRMM-E
P40VLRMM-E
P50VLRMM-E
P63VLRMM-E
Power source
~220-240 V 50 Hz/60 Hz
Cooling capacity
*1
/Heating capacity
*1
kW
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
Dimension (Height/Width/Depth)
mm
639/886/220
639/886/220
639/1006/220
639/1006/220
639/1246/220
639/1246/220
Net weight
kg
21
21
24
25
29
29
Fan
Airflow rate
(Low-Middle-High)
m
3
/min
4.5-5.5-6.5
4.5-5.5-6.5
6.5-7.5-9.0
8.0-9.5-10.0
10.0-12.0-14.0
11.0-13.0-15.5
External static pressure
*2
Pa
20/40/60
20/40/60
20/40/60
20/40/60
20/40/60
20/40/60
Sound pressure level
(Low-Middle-High)*
2 *4
dB(A)
31-36-40
31-36-40
27-32-37
30-36-40
32-37-41
35-40-44
Filter
Standard filter
* Operation temperature of indoor unit
Cooling mode: 15°CWB - 24°CWB
Heating mode: 15°CDB - 27°CDB
*1
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
<Cooling> Indoor: 27°CDB/19°CWB, Outdoor: 35°CDB
<Heating> Indoor: 20°CDB, Outdoor: 7°CDB/6°CWB
*2
The external static pressure is set to 20 Pa at factory shipment.
*3
The figures represent a 240 V/50 Hz unit measured at a point which is 1 m away from the front of the unit and at a height of 1 m from the floor.
The noise is approximately 1 dB(A) less for a 230 V unit and approximately 2 dB(A) less for a 220 V unit. The noise is approximately 3 dB(A) less when the
measurement point is 1.5 m away from the front of the unit and at a height of 1.5 m from the floor.
*4 The operating noise is the data that was obtained in an anechoic room.
Содержание CITY MULTI PEFY-P-VMA(L)-E Series
Страница 33: ......