Length

(Unit: m)

Item

Piping portion

Allowable value

F+G+A+B+C

Total piping length

+D+E+a+b

+c+d+e+f

Longest piping length

F(G)+A+C+E+f

Between outdoor unit and

F(G)+A

Below 110

BC controller

Between indoor units and BC controller B+d or C+D+e or C+E+f

Below 40 *2

Between outdoor units

F+G

Below 5

Above outdoor unit

H

Below 50

Below outdoor unit

H1

Below 40

Between indoor units and BC controller

h1

Below 15

(Below 10)*3

Between indoor units

h2

Below 15

(Below 10)*3

Between BC controller (main or sub)

h3

Below 15

and BC controller (sub)

Between outdoor units

h4

Below 0.1

Diff

erence of ele

v

ation

Between

indoor and

outdoor units

Not to exceed the

maximum refriger-

ant piping length *1

[Fig. 2.4.2]

2.4

CMB-P108, 1010, 1013, 1016GA1, P104, 108GB1 (GA1: In the case the outdoor unit is 26-hp (P650 model) or less.)

CMB-P1016HA1, 1016HB1 (HA1: In the case the outdoor unit is 28-hp (P700 model) or more.)

a

C

b

B

c

d

f

D

E

A

e

F

G

h2

h1

h3

h1

C

C

D

D

D

D

D

D

F

A

A

B

I

J

H

G

E

L

M

N

O

H1

H

h4

*6

K

A

Outdoor unit

B

MAIN BC controller

C

SUB BC controller

D

Indoor unit

E

The twinning kit is connected inside the outdoor unit on the low-pressure side.

When outdoor units of different capacities are connected, connect the twinning kit
to the unit with a higher capacity.

F

Twinning pipe (for R2 series) CMY-R100VBK, CMY-R200VBK

(for WR2 series) CMY-Q100VBK

G

Twinning pipe (for Y series) CMY-Y202-G2, CMY-Y102L-G2, CMY-Y102S-G2

H

Twinning pipe (CMY-R160-J1: optional)

I

Twinning pipe (for Y series) CMY-Y102S-G2

J

P100 - P250 model: 2 ports merged

K

Maximum of 3 units per a pair of ports

Total capacity of 80 or below

All units connected to the same port must be in the same operation mode.

L

Less than H=50 m (when the outdoor unit is higher than the indoor unit)

M

Less than H1=40 m (when the outdoor unit is lower than the indoor unit)

N

Less than h1=15 m (10 m or less for 200, 250 unit type)

O

Less than h2=15 m

Notes:

A system that has more than 16 branching points requires 2 to 3 BC control-
lers (main and sub) and 3 pipes to connect the main and the sub BC control-
lers.
*1 Refer to “Restrictions on piping length” on P. 4.
*2 Please refer to the figure “Distance between main BC controller and far-

thest Indoor unit” when the distance between main BC controller and
farthest indoor unit exceeds 40 m. (Not applicable to the P250 model
indoor unit)

*3 The values in the parentheses show the maximum piping length to be

followed when the connection capacity of the indoor unit is 200 or more.

*4 In the system to which indoor units of the P200 model or above are con-

nected, neither a branch joint nor a branch header may be used.

*5 When connecting two sub BC controllers, the total piping length must be

equal to or less than the maximum length as listed in on the left.

*6 When connecting two sub BC controllers, install them in parallel.
*7 In the system to which indoor units of the P100 through P140 models are

connected, merge the two ports before connecting them. (Set DIP SW4-6
on the main BC controller to ON.)

*8 It is possible to connect the P100 through P140 models of indoor units to

a single port. (Set DIP SW4-6 to OFF.) Note that the cooling capacity will
somewhat decrease. (The factory setting for DIP SW4-6 is OFF.)

*9 When the outdoor unit is 28-hp (P700 model) or more, use the HA-type

main BC controller. The G-type BC controller cannot be connected to the
models between 16-hp (P400 model) and 26-hp (P650 model), and the G-
and GA-type BC controllers cannot be connected to the 28-hp (P650
model) or more.

*10 For Sub BC controller GB type, the connectable indoor unit capacities

may sum to equal that of a P350 unit or less. However, if two sub control-
lers are used the TOTAL sum of connectable units connected to BOTH
sub controllers must also not exceed that of a P350 unit.
For sub BC controller HB type, the connectable indoor unit capacities
may sum to equal that or a P350 unit or less. However, if two sub control-
lers are used the TOTAL sum of connectable units connected to BOTH
sub controllers must also not exceed that of a P450 unit.

*11 Indoor units that are connected to the same branch joint cannot be si-

multaneously operated in different operation modes.

*12 Do not connect the P200 or P250 models of indoor units and other mod-

els of indoor units at the same port.

<System that has more than 16 branching points>

Distance between MAIN BC controller
and farthest indoor unit

Height difference between 
MAIN BC controller and 
farthest indoor unit (m)

15

10

5

20
10

0

0

Distance between MAIN BC controller

and farthest indoor unit (m)

70
60
50
40
30

165 m or less

(Equivalent length

of 190 m or less)

3

Содержание CITY MULTI CMB-P1010V-GA1

Страница 1: ...i installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î...

Страница 2: ...od els of indoor units at the same port 6 In the system to which indoor units of the P100 through P140 models are connected merge the two ports before connecting them Set DIP SW4 6 on the BC controller to ON 7 It is possible to connect the P100 through P140 models of indoor units to a single port Set DIP SW4 6 to OFF Note that the cooling capacity will somewhat decrease The factory setting for DIP...

Страница 3: ...the distance between main BC controller and farthest indoor unit exceeds 40 m Not applicable to the P250 model indoor unit 3 The values in the parentheses show the maximum piping length to be followed when the connection capacity of the indoor unit is 200 or more 4 In the system to which indoor units of the P200 model or above are con nected neither a branch joint nor a branch header may be used 5...

Страница 4: ... PURY EP400 450 500 550YSHM A 1 PQRY P400 450 500 550 600YSHM A 400 500 600 700 800 900 1000 A 800 900 1000 200 300 400 500 600 700 800 900 1000 10 20 30 40 50 60 70 80 90 100 110 A 200 300 10 20 30 40 50 60 70 80 90 100 110 400 500 600 700 800 900 1000 200 300 400 500 600 700 800 10 20 30 40 50 60 70 80 90 100 110 A 900 1000 A 200 300 400 500 600 700 A 10 20 30 40 50 60 70 80 90 100 110 10 20 30 ...

Страница 5: ...ection or joint pipe Total capacity of connectable indoor units Less than 80 Less than 250 with joint pipe Number of connectable indoor units Maximum 3 Sets Twinning pipe Use the twinning pipe for CITY MULTIY Series CMY Y102S G2 Selection of refrigerant piping Select the size according to the total capacity of indoor units to be installed downstream 1 Use the supplied pipe Outdoor unit side PURY E...

Страница 6: ...C Collecting pipe D Please ensure this length is at least 10 cm Fig 4 4 2 Fig 5 0 1 A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring 5 B A C D VP 25 2 D E G F 4 2 Fig 4 2 1 F E D A C B 4 3 Fig 4 3 1 A Cut here B Remove brazed cap B A A Locally procured insulating material for pipes B Bind here using band or tape c Do not leave any opening D Lap margin more...

Страница 7: ...ioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving...

Страница 8: ...to ensure proper drainage Wrap thermal insulation around the pipes to prevent condensation Improper drain piping may cause water leakage causing damage to furniture and other possessions Be very careful about transporting the product One person should not carry the product Its weight is in excess of 20 kg Some products use PP bands for packaging Do not use any PP bands as a means of transportation...

Страница 9: ...tem Piping portion Allowable value A B a b Total piping length c d e Longest piping length A e Between outdoor unit and A Below 110 BC controller Between indoor units and BC controller e Below 40 2 Above outdoor unit H Below 50 Below outdoor unit H1 Below 40 Between indoor units and BC controller h1 Below 15 Below 10 3 Between indoor units h2 Below 15 Below 10 3 Difference of elevation Between ind...

Страница 10: ...40 Between indoor units and BC controller h1 Below 15 Below 10 3 Between indoor units h2 Below 15 Below 10 3 Between BC controller main or sub h3 Below 15 and BC controller sub Between outdoor units h4 Below 0 1 Difference of elevation Between indoor and outdoor units Not to exceed the maximum refriger ant piping length 1 165 m or less Equivalent length of 190 m or less Notes A system that has mor...

Страница 11: ...t before brazing Store elbows and other joints in a plastic bag If dust dirt or water enters the refrigerant cycle deterioration of the oil and compressor failure may result Apply a small amount of ester oil ether oil or alkyl benzene to flares for indoor unit Infiltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate Do not vent R410A into the atmosphere R410A is a...

Страница 12: ... not use any adhesive because the drain hose will need to be removed for servicing at a later date Do not use any odor trap around the discharge port Fig 4 4 1 P 6 A 25 cm B 1 5 2 m A Downward pitch of more than 1 100 B Insulating material C Supporting bracket D Drain discharge port E Drain hose 200 mm long accessory F Tie band accessory G Hose band accessory As shown in 3 install a collecting pip...

Страница 13: ...должны выполняться квалифицированным электриком в полном соответствии с Электротехническими стандартами и Нормами проведения внутренней проводки и инструкциями указанными в Руководстве по установке Характеристики электропитания должны строго соответствовать рекомендованным Несоответствие характеристик подаваемого питания рекомендованным или нарушение правил установки могут привести с сбоям в работ...

Страница 14: ...аличие масел пара испарений серы и т д может вызвать значительное ухудшение рабочих показателей кондиционера или выход его компонентов из строя При установке прибора в больнице на станции связи или в аналогичном помещении обеспечьте достаточную защиту от шума Преобразовательное оборудование частный электрогенератор высоковольтное медицинское оборудование или оборудование для радиосвязи могут вызва...

Страница 15: ...скоплению притоку образованию или утечки возгорающихся и сернистых газов Обеспечьте нисходящий уклон дренажной трубы не менее 1 100 Правильно установите блок на устойчивую несущую поверхность 1 При укреплении на потолке Fig 2 2 1 P 2 Предусмотрите смотровое отверстие размером 450 кв мм на поверхности потолка как показано на Fig 2 3 1 P 2 Установите блок в подходящем месте например на потолке корид...

Страница 16: ... ниже чем внутренний N Меньше чем h1 15 м 10 м и менее для блоков типоразмера 200 250 O Меньше чем h2 15 м Длина Разница по высоте Часть трубы A B a b c d e A e A e H H1 h1 h2 Часть Общая длина трубы Самый длинный отрезок трубы Между внешним прибором и регулятором ВС Между внутренним приборами и регулятором ВС Над внешним прибором Ниже внешнего прибором Между внутренним приборами и регулятором ВС ...

Страница 17: ...ности блока P450 11 Внутренние блоки подсоединенные к одному ответвителю не могут одновременно работать в разных рабочих режимах 12 Не подключайте внутренние блоки моделей P200 или P250 и другие модели внутренних блоков к одному порту Fig 2 4 3 P 4 A Общая длина трубопровода м B Длина трубопровода между блоком управления и ВС контроллером м 4 Подсоединение труб хладагента и дренажных труб 4 1 Подс...

Страница 18: ...ружного блока PURY E P400 PQRY P400 PURY E P450 PQRY P450 PURY E P500 PQRY P500 PURY E P550 PQRY P550 PURY E P600 PQRY P600 PURY P650 PURY P700 PURY P750 PURY P800 Модель блока PURY E P200 PQRY P200 PURY E P250 PQRY P250 PURY E P300 PQRY P300 PURY P350 Сторона внутреннего блока ВС КОНТРОЛЛЕР CMB P104V G1 CMB P105V G1 CMB P106V G1 CMB P108V G1 CMB P1010V G1 CMB P1013V G1 CMB P1016V G1 ГЛАВНЫЙ ВС КО...

Страница 19: ...е поставленный дренажный шланг на порту слива используя поставленную шланговую ленту Не используйте для монтажа клей так как дренажный шланг позднее необходимо будет снять для обслуживания Не ставьте никакой ловушки запахов вокруг выпускного отверстия Fig 4 4 1 P 6 A 25 см B 1 5 2 м A Наклон вниз свыше 1 100 B Изолирующий материал C Поддерживающая скоба D Порт слива дренажа E Дренажный шланг 200 м...

Страница 20: ...задайте другой адрес в пределах от 51 до 100 При этом убедитесь что данный адрес отличается от адресов других регуляторов См Руководство по установке внешнего прибора 7 Выполнение испытания Перед пробным пуском проверьте следующее s После монтажа подсоединения трубопроводов и электропроводки к внутреннему блоку и ВС контроллеру убедитесь в отсутствии течи хладагента и провисания силовых кабелей и ...

Страница 21: ... at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan ...

Отзывы: