To outdoor unit (MAIN BC CONTROLLER)

B

End connection (brazing)

C

BC controller (MAIN BC CONTROLLER/SUB BC CONTROLLER)

D

Reducer

E

Indoor unit

F

Less than 50

G

Combined piping kit (Model name: CMY-R160-J1)

H

Twinning pipe (Model name: CMY-Y102S-G2)

I

Up to three units for 1 branch hole; total capacity: below 80 (but same in cooling/
heating mode)

The size of BC controller’s branch piping is for 63 to 140 type indoor units.
Therefore, if you want to connect indoor units other than the above, connect piping
following the procedures below.

*1. For connecting 15 to 50 type indoor units

Have pipe expansion of indoor unit connecting port by cutting the piping at the
cutting point which depends on the indoor unit capacity.

Note:
Remove burr after cutting the piping to prevent entering the piping.
Check that there is no crack at the pipe expansion part.

*2. To connect a unit with a capacity of higher than 81.

After combining two branches using an optionally available piping kit (CMY-R160-
J1), connect indoor units.

*3. Connection of plural indoor units with one connection (or joint pipe)

Total capacity of connectable indoor units: Less than 80 (Less than 250 with
joint pipe)

Number of connectable indoor units: Maximum 3 Sets

Twinning pipe: Use the twinning pipe for CITY MULTI Y Series (CMY-Y102S-
G2)

Selection of refrigerant piping

Select the size according to the total capacity of indoor units to be installed
downstream.

Total capacity of indoor units

Liquid line

Gas line

Below 140

ø15.88

141 to 200

ø9.52

ø19.05

201 to 250

ø22.2

6. Be sure to use non-oxidative brazing where necessary. If you do not use non-

oxidative brazing, it may clog the pipes.
While under a nitrogen purge, braze the indoor unit connecting port before
brazing the outdoor unit connecting port of BC controller.
When brazing the indoor unit connecting port, supply a nitrogen gas into the
outdoor unit connecting port of BC controller.
When brazing the outdoor unit connecting port of BC controller, supply a nitrogen
gas into the pipe between the outdoor unit and BC controller.

7. After completing pipe connection, support the pipes to ensure that load is not

imparted to the BC controller’s end connections (particularly to the gas pipes
of indoor units).

 Warning :

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant (R410A) specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes. In addition, be sure that the inner and
outer surfaces of the pipes are clean and free of hazardous sulphur, oxides,
dust/dirt, shaving particles, oils, moisture, or any other contaminant.

- R410A is a high-pressure refrigerant and can cause the existing piping to burst.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor failure may result.

Apply a small amount of ester oil, ether oil, or alkyl benzene to flares. (for
indoor unit)

- Infiltration of a large amount of mineral oil may cause the refrigerant oil to

deteriorate.

Do not vent R410A into the atmosphere.

R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol
with a Global Warming Potential (GWP) = 1975.

*1 Use the supplied pipe.

[Fig. 4.1.2] (P.5)

Note:
Be sure to use non-oxidative brazing.

4.2. Refrigerant piping work

After connecting the refrigerant pipes of all indoor and outdoor units with the out-
door units’ stop valves remained fully closed, evacuate vacuum from the outdoor
units’ stop valve service ports.
After completing the above, open the outdoor units’ stop valves. This connects the
refrigerant circuit (between outdoor and BC controller) completely.
How to handle stop valves is described on each outdoor unit.

Notes:

After pipe connection, be sure to check that there is no gas leakage,
using a leak detector or soap-and-water solution.

Before brazing the refrigerant piping, 

always wrap the piping on the main

body, and the thermal insulation piping, with damp cloths to prevent heat
shrinkage and burning the thermal insulation tubing.

 Take care to ensure

that the flame does not come into contact with the main body itself.

Do not use leak-detection additives.

 Warning:

Do not mix anything other than the specified refrigerant (R410A) into the
refrigerating cycle when installing or moving. Mixing air may cause the refrig-
erating cycle to reach abnormally high temperature, resulting in burst pipes.

 Caution:

Cut the tip of the outdoor unit piping, remove the gas, and then remove the
brazed cap.

[Fig. 4.2.1] (P.6)

A

Cut here

B

Remove brazed cap

1. Size of BC controller’s end connection piping

Outdoor unit side

PURY-(E) P400

PQRY-P400

PURY-(E) P450

PQRY-P450

PURY-(E) P500

PQRY-P500

PURY-(E) P550

PQRY-P550

PURY-(E) P600

PQRY-P600
PURY-P650
PURY-P700
PURY-P750
PURY-P800

BC CONTROLLER/MAIN BC CONTROLLER

SUB BC CONTROLLER

Unit model

Model name

High pressure

side

Low pressure

side

Model name

Total capacity

of indoor units

High pressure

(gas) side

Low pressure

(gas) side

Liquid side

PURY-(E) P200

PQRY-P200

PURY-(E) P250

PQRY-P250

PURY-(E) P300

PQRY-P300

PURY-P350

Indoor unit side

(BC CONTROLLER)
CMB-P104V-G1
CMB-P105V-G1
CMB-P106V-G1
CMB-P108V-G1
CMB-P1010V-G1
CMB-P1013V-G1
CMB-P1016V-G1

(MAIN BC
CONTROLLER)
CMB-P108V-GA1
CMB-P1010V-GA1
CMB-P1013V-GA1
CMB-P1016V-GA1

(MAIN BC
CONTROLLER)
CMB-P1016V-HA1

When a system that has more than 16 branching points, use BC controllers (main and
sub) to connect the pipes.

CMB-P104V-GB1
CMB-P108V-GB1
CMB-P1016V-HB1

ø15.88*1
(Brazing)

ø19.05

(Brazing)

ø19.05*1
(Brazing)

ø22.2

(Brazing)

ø28.58*1
(Brazing)

ø28.58

(Brazing)

ø9.52 or ø6.35

(Brazing)

ø19.05*1
(Brazing)

ø22.2

(Brazing)

ø28.58*1
(Brazing)

ø28.58

(Brazing)

ø34.93*1
(Brazing)

ø15.88 or ø12.7

(Brazing)

below 200

ø15.88*1
(Brazing)

ø19.05*1
(Brazing)

ø9.52

(Brazing)

201~300

ø19.05

(Brazing)

ø22.2

(Brazing)

301~350

351~400

ø22.2*1

(Brazing)

ø28.58*1
(Brazing)

401~450

ø9.52 or ø6.35

(Brazing)

ø15.88 or ø12.7

(Brazing)

ø12.7*1

(Brazing)

ø15.88*1

(Brazing)

WT05845X01_en.p65

10.1.29, 0:03 PM

11

Содержание CITY MULTI CMB-P1010V-GA1

Страница 1: ...i installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î...

Страница 2: ...od els of indoor units at the same port 6 In the system to which indoor units of the P100 through P140 models are connected merge the two ports before connecting them Set DIP SW4 6 on the BC controller to ON 7 It is possible to connect the P100 through P140 models of indoor units to a single port Set DIP SW4 6 to OFF Note that the cooling capacity will somewhat decrease The factory setting for DIP...

Страница 3: ...the distance between main BC controller and farthest indoor unit exceeds 40 m Not applicable to the P250 model indoor unit 3 The values in the parentheses show the maximum piping length to be followed when the connection capacity of the indoor unit is 200 or more 4 In the system to which indoor units of the P200 model or above are con nected neither a branch joint nor a branch header may be used 5...

Страница 4: ... PURY EP400 450 500 550YSHM A 1 PQRY P400 450 500 550 600YSHM A 400 500 600 700 800 900 1000 A 800 900 1000 200 300 400 500 600 700 800 900 1000 10 20 30 40 50 60 70 80 90 100 110 A 200 300 10 20 30 40 50 60 70 80 90 100 110 400 500 600 700 800 900 1000 200 300 400 500 600 700 800 10 20 30 40 50 60 70 80 90 100 110 A 900 1000 A 200 300 400 500 600 700 A 10 20 30 40 50 60 70 80 90 100 110 10 20 30 ...

Страница 5: ...ection or joint pipe Total capacity of connectable indoor units Less than 80 Less than 250 with joint pipe Number of connectable indoor units Maximum 3 Sets Twinning pipe Use the twinning pipe for CITY MULTIY Series CMY Y102S G2 Selection of refrigerant piping Select the size according to the total capacity of indoor units to be installed downstream 1 Use the supplied pipe Outdoor unit side PURY E...

Страница 6: ...C Collecting pipe D Please ensure this length is at least 10 cm Fig 4 4 2 Fig 5 0 1 A Control box B Power source wiring C ø21 hole closed rubber bushing D Transmission wiring 5 B A C D VP 25 2 D E G F 4 2 Fig 4 2 1 F E D A C B 4 3 Fig 4 3 1 A Cut here B Remove brazed cap B A A Locally procured insulating material for pipes B Bind here using band or tape c Do not leave any opening D Lap margin more...

Страница 7: ...ioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving...

Страница 8: ...to ensure proper drainage Wrap thermal insulation around the pipes to prevent condensation Improper drain piping may cause water leakage causing damage to furniture and other possessions Be very careful about transporting the product One person should not carry the product Its weight is in excess of 20 kg Some products use PP bands for packaging Do not use any PP bands as a means of transportation...

Страница 9: ...tem Piping portion Allowable value A B a b Total piping length c d e Longest piping length A e Between outdoor unit and A Below 110 BC controller Between indoor units and BC controller e Below 40 2 Above outdoor unit H Below 50 Below outdoor unit H1 Below 40 Between indoor units and BC controller h1 Below 15 Below 10 3 Between indoor units h2 Below 15 Below 10 3 Difference of elevation Between ind...

Страница 10: ...40 Between indoor units and BC controller h1 Below 15 Below 10 3 Between indoor units h2 Below 15 Below 10 3 Between BC controller main or sub h3 Below 15 and BC controller sub Between outdoor units h4 Below 0 1 Difference of elevation Between indoor and outdoor units Not to exceed the maximum refriger ant piping length 1 165 m or less Equivalent length of 190 m or less Notes A system that has mor...

Страница 11: ...t before brazing Store elbows and other joints in a plastic bag If dust dirt or water enters the refrigerant cycle deterioration of the oil and compressor failure may result Apply a small amount of ester oil ether oil or alkyl benzene to flares for indoor unit Infiltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate Do not vent R410A into the atmosphere R410A is a...

Страница 12: ... not use any adhesive because the drain hose will need to be removed for servicing at a later date Do not use any odor trap around the discharge port Fig 4 4 1 P 6 A 25 cm B 1 5 2 m A Downward pitch of more than 1 100 B Insulating material C Supporting bracket D Drain discharge port E Drain hose 200 mm long accessory F Tie band accessory G Hose band accessory As shown in 3 install a collecting pip...

Страница 13: ...должны выполняться квалифицированным электриком в полном соответствии с Электротехническими стандартами и Нормами проведения внутренней проводки и инструкциями указанными в Руководстве по установке Характеристики электропитания должны строго соответствовать рекомендованным Несоответствие характеристик подаваемого питания рекомендованным или нарушение правил установки могут привести с сбоям в работ...

Страница 14: ...аличие масел пара испарений серы и т д может вызвать значительное ухудшение рабочих показателей кондиционера или выход его компонентов из строя При установке прибора в больнице на станции связи или в аналогичном помещении обеспечьте достаточную защиту от шума Преобразовательное оборудование частный электрогенератор высоковольтное медицинское оборудование или оборудование для радиосвязи могут вызва...

Страница 15: ...скоплению притоку образованию или утечки возгорающихся и сернистых газов Обеспечьте нисходящий уклон дренажной трубы не менее 1 100 Правильно установите блок на устойчивую несущую поверхность 1 При укреплении на потолке Fig 2 2 1 P 2 Предусмотрите смотровое отверстие размером 450 кв мм на поверхности потолка как показано на Fig 2 3 1 P 2 Установите блок в подходящем месте например на потолке корид...

Страница 16: ... ниже чем внутренний N Меньше чем h1 15 м 10 м и менее для блоков типоразмера 200 250 O Меньше чем h2 15 м Длина Разница по высоте Часть трубы A B a b c d e A e A e H H1 h1 h2 Часть Общая длина трубы Самый длинный отрезок трубы Между внешним прибором и регулятором ВС Между внутренним приборами и регулятором ВС Над внешним прибором Ниже внешнего прибором Между внутренним приборами и регулятором ВС ...

Страница 17: ...ности блока P450 11 Внутренние блоки подсоединенные к одному ответвителю не могут одновременно работать в разных рабочих режимах 12 Не подключайте внутренние блоки моделей P200 или P250 и другие модели внутренних блоков к одному порту Fig 2 4 3 P 4 A Общая длина трубопровода м B Длина трубопровода между блоком управления и ВС контроллером м 4 Подсоединение труб хладагента и дренажных труб 4 1 Подс...

Страница 18: ...ружного блока PURY E P400 PQRY P400 PURY E P450 PQRY P450 PURY E P500 PQRY P500 PURY E P550 PQRY P550 PURY E P600 PQRY P600 PURY P650 PURY P700 PURY P750 PURY P800 Модель блока PURY E P200 PQRY P200 PURY E P250 PQRY P250 PURY E P300 PQRY P300 PURY P350 Сторона внутреннего блока ВС КОНТРОЛЛЕР CMB P104V G1 CMB P105V G1 CMB P106V G1 CMB P108V G1 CMB P1010V G1 CMB P1013V G1 CMB P1016V G1 ГЛАВНЫЙ ВС КО...

Страница 19: ...е поставленный дренажный шланг на порту слива используя поставленную шланговую ленту Не используйте для монтажа клей так как дренажный шланг позднее необходимо будет снять для обслуживания Не ставьте никакой ловушки запахов вокруг выпускного отверстия Fig 4 4 1 P 6 A 25 см B 1 5 2 м A Наклон вниз свыше 1 100 B Изолирующий материал C Поддерживающая скоба D Порт слива дренажа E Дренажный шланг 200 м...

Страница 20: ...задайте другой адрес в пределах от 51 до 100 При этом убедитесь что данный адрес отличается от адресов других регуляторов См Руководство по установке внешнего прибора 7 Выполнение испытания Перед пробным пуском проверьте следующее s После монтажа подсоединения трубопроводов и электропроводки к внутреннему блоку и ВС контроллеру убедитесь в отсутствии течи хладагента и провисания силовых кабелей и ...

Страница 21: ... at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan ...

Отзывы: